• ALM_RD (05H)

Reads alarm or warning

BYTE

COMMAND

RESPONSE

REMARKS

0

ALM_RD (05H)

ALM_RD (05H)

Read alarm or warning command

1

00H

00H

Not used

2

CMD_CTRL

CMD_STAT

Refer to CMD_CTRL/CMD_STAT.

3
4

0000H

0000H

Read current alarm or warning.  
12 points max. (2 bytes in 8th to 31st byte) 
Other than 0000H is not available.

5

6

0000H

0000H

0

7

≥ 8

00H

00H

0

• ALM_CLR (06H)

Clears alarm or warning

BYTE

COMMAND

RESPONSE

REMARKS

0

ALM_CLR (06H)

ALM_CLR (06H)

Clear alarm or warning command

1

00H

00H

Not used

2

CMD_CTRL

CMD_STAT

Refer to CMD_CTRL/CMD_STAT.

3
4

0000H

0000H

Clear current alarm or warning.  Other than 0000H is not 
available.

5

≥ 6

00H

00H

Reserve

• CONNECT (0EH)

Starts communication with master station.

BYTE

COMMAND

RESPONSE

REMARKS

0

CONNECT (0EH)

CONNECT (0EH)

Establish connection command

1

00H

00H

Not used

2

CMD_CTRL

CMD_STAT

Refer to CMD_CTRL/CMD_STAT.

3
4

30H

30H

MECHATROLINK application layer: 30H

5

00H

00H

Communication mode: Asynchronous, single transmission, 
subcommand disabled

6

COM_TIME

COM_TIME

Communication cycle: Multiple of transmission cycle. 
E.g. Transmission cycle: 0.5 msec., communication cycle: 2 
msec. Set 4 (=2/0.5)

7

30H or 01H

30H or 01H

Profile type
30H: Standard I/O profile
01H: Event-driven communication acquiring ID profile

≥ 8

00H

00H

Reserve

• DISCONNECT (0FH)

Stops communication with master station.

BYTE

COMMAND

RESPONSE

REMARKS

0

DISCONNECT (0FH)

DISCONNECT (0FH)

Release connection command

≥ 1

00H

00H

Reserve

Содержание R7F4HML3-D-DAC32A

Страница 1: ...ational range as indicated below 24V DC rating 24V 10 approx 100mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and I O signal for safety Before you remove the...

Страница 2: ...NK III LNK1 is established LNK2 Green Turns on at MECHATROLINK III LNK2 is established STATION ADDRESS Station Address is selected between 03H and EFH in hexa decimal The SA1 switch determines the MSD...

Страница 3: ...5 0V Power Input 0V TERMINAL ASSIGNMENTS I O Connection Recommended cable connector XG4M 4030 OMRON The cable connector is not included in the package 39 40 1 2 PIN No ID FUNCTION PIN No ID FUNCTION 1...

Страница 4: ...unit from the DIN rail 1 3 2 DIN RAIL MOUNTING RIGHT ANGLE Mounting 1 Insert the longer DIN rail mounter slider until it clicks twice as shown below 1 2 Set the upper hook at the rear side of the unit...

Страница 5: ...201 Fax 81 6 6659 8510 E mail info m system co jp EM 8002 A Rev 2 P 5 12 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 115 4 53 55 2 17 75 2 95 123 4 8...

Страница 6: ...5 11 16 17 18 19 20 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 3 25 X0 COM X15 PNP Connection NPN Connection X0 COM V Y5 V V Y15 Y7 Y14 Y6 Y13 Y12 Y1 Y4 Y11 Y3 Y10 Y2 Y9 V Y8 X6 COM COM X15...

Страница 7: ...or warning command ALM_CLR 06H Clear alarm or warning command CONNECT 0EH Establish connection command DISCONNECT 0FH Release connection command Standard I O profile DATA_RWA 20H Transmit I O data NOP...

Страница 8: ...CMD_STAT 3 4 0000H 0000H Clear current alarm or warning Other than 0000H is not available 5 6 00H 00H Reserve CONNECT 0EH Starts communication with master station BYTE COMMAND RESPONSE REMARKS 0 CONN...

Страница 9: ...ent from the slave to the master are set in the response With output data read back CH0 IN LO CH0 data low 8 bits Bit 0 through 7 of input data are set CH0 IN HI CH0 data high 8 bits Bit 8 through 15...

Страница 10: ...LO CH2 data low 8 bits Not used CH2 OUT HI CH2 data high 8 bits Not used CH3 OUT LO CH3 data low 8 bits Not used CH3 OUT HI CH3 data high 8 bits Not used CMD_CTRL CMD_CTRL command area is following BI...

Страница 11: ...125 sec 17H Max Transmission Cycle 4 Yes 0x0061A800 64 msec 18H Increments of Transmission Cycle 4 Yes 0x00000001 Available to 31 25 62 5 125 250 500 sec 1 64 msec 1 msec increments 19H Min Communica...

Страница 12: ...9 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 8002 A Rev 2 P 12 12 I O DATA DESCRIPTION DISCRETE I O MODULE Input 0 Input 1 Input 2 Input 3 Input 15 Input 7 Input 8 Output 0 Output 1 Output...

Отзывы: