background image

R7C-DC16B

EM-7801-H  Rev.6  P. 3 / 9

INDICATOR LED

 

STATUS INDICATOR LED

PWR

RUN

ERR

SD 

*

1

RD

STATUS 

*

2

ON

ON

BL

BL

ON

Communicates normally with occasional CRC errors due to noise interference.

ON

ON

BL

BL

ON

Communicates normally but the Baud Rate and/or Station Address switches failed.  
ERR LED blinks approximately in 0.5 seconds intervals.

ON

ON

BL

BL

OFF ----

ON

ON

BL

OFF

ON

CRC error found in the received data.  Unable to respond.

ON

ON

BL

OFF

OFF ----

ON

ON

OFF

BL

ON

Normal communication

ON

ON

OFF

BL

OFF ----

ON

ON

OFF

OFF

ON

Unable to receive data addressed to the station.

ON

ON

OFF

OFF

OFF ----

ON

OFF

BL

BL

ON

Performs the interval-timed responses but CRC error found in receiving the refresh 
data.

ON

OFF

BL

BL

OFF ----

ON

OFF

BL

OFF

ON

CRC error found in the data addressed to the station.

ON

OFF

BL

OFF

OFF ----

ON

OFF

OFF

BL

ON

Link is not started.

ON

OFF

OFF

BL

OFF ----

ON

OFF

OFF

OFF

ON

No data addressed to the station.  Or unable to receive data addressed to the station 
due to noise interference.  (Missing parts of the data sent from the master)

ON

OFF

OFF

OFF

OFF Unable to receive data due to wire breakdown

ON

OFF

ON

OFF ON/OFF Faulty Baud Rate and/or Station Address setting

OFF

OFF

OFF

OFF

OFF Power input removed.  Or power supply failure.

OFF = OFF, ON = ON, BL = Blinking
*1. SD LED may look not blinking but ON with high baud rate and fewer connected modules.
*2. LEDs indicated with “----” in STATUS rarely occurs in normal operation (LED failure or the like as possible cause).

 

DISCRETE OUTPUT STATUS INDICATOR LED

LED indicators show the signal status.
  ON  : LED ON
  OFF : LED OFF

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-DC16B

Страница 1: ...ation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the...

Страница 2: ...ting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1...

Страница 3: ...N OFF BL OFF ON CRC error found in the data addressed to the station ON OFF BL OFF OFF ON OFF OFF BL ON Link is not started ON OFF OFF BL OFF ON OFF OFF OFF ON No data addressed to the station Or unab...

Страница 4: ...le 10 17 18 1 YD 16 YB 0V YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 24V Y0 2 EXTENSION CONNECTOR In order to improve EMC performance bond the FG terminal to ground Caution FG...

Страница 5: ...B The Master Unit can be located other than at the extreme ends of communication line DATA ALLOCATION RY n 0 F to RY n 0 0 Unused R7C DC16x 0 F 1F Interval timed Response X 0 F 1F Refresh Data Y R7C D...

Страница 6: ...trol panels with an internal panel plate both made of metal when installing the R7C Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imp...

Страница 7: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Страница 8: ...tions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to...

Страница 9: ...tus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To con...

Отзывы: