R3-NM1

P.  / 7

EM-8354 Rev.4

*2. Refer to the specifications of the related series for the 
Data Allocation Type of I/O modules.

• Dual Communication

: SW3

When  two  network  modules  are  mounted,  one  must  be 
‘Main’ (OFF) network and the other must be ‘Sub’ (ON) net-
work.  For single communication, the network module must 
always be set to ‘Main’ (OFF).

• Input Error Data

: SW3

Hold

: When the communication from an input module is lost 

due to the input module error, the network module holds the 
signal and stands by until the communication recovers.

Set to ‘0’

: When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

COMPONENT IDENTIFICATION

 SIDE DIP SW

• Data allocation

: SW1, SW2

Data Allocation Type*

2

 must be assigned to each I/O module 

slot position to specify how many data areas (four types) are 
to be occupied by each.
Two bits from SW1 and SW2 are assigned to each position, 
and data areas can be specified from the slot No. 1 through 
8.  Setting for No. 9 and later slots is identical to No. 8.

RUN LED

■ 

FRONT VIEW

■ 

SIDE VIEW

ERR LED

SA1
SA2

1
2
3

4
5
6

Terminal Block

Node Address (MSD)

Node Address (LSD)

Transmission Properties

Configuration Jack

5

4 3 2 1

0

9

8

7

6

5

4 3 2 1

0

9

8

7

6

SW6

ON

8

7

6

5

4

3

2

1

FG

SLD

DG

DB

DA

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

ON

8

7

6

5

4

3

2

1

SW1

Functions

 FRONT ROTARY SW

Set the module’s node address in hexadecimal with SA1 and 
SA2.

 FRONT DIP SW

• Baud rate

: SW6

• Parity

: SW6 *

1

• Data Mode

: SW6 *

1

*1. Bit assignment according to Parity and Data Mode setting

 

 

BAUD RATE (bps)

 

 

38.4k

 (*) 

19.2k 

9600 

4800

 

  SW6-1 

OFF 

ON 

OFF 

ON

  SW6-2 

OFF 

OFF 

ON 

ON

 

 

PARITY

 

 

None

 (*) 

Odd 

Even 

N/A

 

  SW6-3 

OFF 

ON 

OFF 

ON

  SW6-4 

OFF 

OFF 

ON 

ON

 

 

DATA MODE

 

 

RTU (Binary)

 (*) 

ASCII

  SW6-5 

OFF 

ON

(*) Factory setting

 

MODE 

START 

DATA 

PARITY 

STOP

 

RTU 

1

 

 

None 

2

 

ASCII 

1

 

 

 None 

2

 

SW ASSIGNMENT 

SLOT

  SW1-1 

SW1-2 

1

  SW1-3 

SW1-4 

2

  SW1-5 

SW1-6 

3

  SW1-7 

SW1-8 

  SW2-1 

SW2-2 

5

  SW2-3 

SW2-4 

6

  SW2-5 

SW2-6 

7

  SW2-7 

SW2-8 

8

 

SW SETTING 

DATA ALLOCATION

 

OFF 

OFF 

1

 

ON 

OFF 

4

 

OFF 

ON 

8

 

ON 

ON 

16

 

 

DUAL COMMUNICATION

 

 

Main

 (*) 

Sub

  SW3-1 

OFF 

ON

 

 

INPUT ERROR DATA

 

 

Hold

 (*) 

Set to ‘0’

  SW3-2 

OFF 

ON

Содержание R3-NM1

Страница 1: ...es are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical...

Страница 2: ...rom the slot No 1 through 8 Setting for No 9 and later slots is identical to No 8 RUN LED FRONT VIEW SIDE VIEW ERR LED SA1 SA2 1 2 3 4 5 6 Terminal Block Node Address MSD Node Address LSD Transmission...

Страница 3: ...ERNAL DIMENSIONS unit mm inch MODBUS WIRING 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 6 M3 SCREW 6 2 24 TERMINATOR Tx Rx Tx Rx SG Rx Rx HOST PC DA DB DG SLD FG R3 NM1 DA...

Страница 4: ...15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within the slave read write 17 Report Slave ID 18 Program 884 M84 19 Reset Co...

Страница 5: ...7 1072 Data Error Status Input Registers 3X 1 256 I Analog Input 257 768 F Analog Input Holding Registers 4X 1 256 I Analog Output 257 768 F Analog Output I Integer 0 10000 0 100 F Floating 32 bit dat...

Страница 6: ...the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values represented in 2 s complements ACCUMULATED COUNT DATA 32 bit data models R3 PA2 PA4A WT1 WT4 et...

Страница 7: ...fo m system co jp 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF open 1 ON close DISCRETE DATA models R3 DA16 and DC16 MAIN SUB SWITCHING CONTROL 1 When the main sub...

Отзывы: