MODBUS I/O ASSIGNMENTS

TRANSMISSION DATA ASSIGNMENTS

The DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
     

Module 1 

 

4

     

Module 2 

 

4

     

Module 3 

 

4

     

Module 4 

 

1

     

Module 5 

 

1

     

Module 6 

 

1

     

Module 7 

 

1

Then the I/O data are assigned as in the table below:

 
 

ADDRESS 

POSITION

Input Registers (3X) 

1 –   4, 

257 – 264 

Slot 1

Holding Registers (4X) 

5 –   8, 

265 – 272 

Slot 2

 

9 – 12, 

273 – 280 

Slot 3

 

13, 

281 – 282 

Slot 4

 

14, 

283 – 284 

Slot 5

 

15, 

285 – 286 

Slot 6

 

16, 

287 – 288 

Slot 7

 
 

ADDRESS 

POSITION

Coil (0X) 

    1 –   64 

Slot 1

Inputs (1X) 

  65 – 128 

Slot 2

 

129 – 192 

Slot 3

 

193 – 208 

Slot 4

 

209 – 224 

Slot 5

 

225 – 240 

Slot 6

 

241 – 256 

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned 

data areas (Data Allocation Type) are allotted with the Data 

Allocation Type ‘1’ and ‘4.’  With ‘8’ and ‘16,’ 64 (4 

×

 16) are 

automatically assigned.

 

ADDRESS 

DATA FORMAT  NAME

Coil (0X) 

      1 – 1024 

 

Digital Output (discrete output)

 

1025 

 

Main / Sub Switching Command (valid only with SW3-3 set to ON)

Inputs (1X) 

      1 – 1024 

 

Digital Input (discrete input)

 

1025 – 1040 

 

Module Status

 

1041 – 1056 

 

Error Status

 

1057 – 1072 

 

Data Error Status

Input Registers (3X) 

    1 – 256 

Analog Input

 

257 – 768 

Analog Input

Holding Registers (4X) 

    1 – 256 

Analog Output

 

257 – 768 

Analog Output

I  : Integer, 0 – 10000 (0 – 100%)

F  : Floating (32-bit data cannot be accessed using floating addresses.)

Note: DO NOT access addresses other than mentioned above.  Such access may cause problems such as inadequate operation.

• Module Status indicates whether individual I/O module are mounted or not.  The bit corresponding to the mounted slots 

turns to “1,” and the unmounted slots to “0.”

• Error Status indicates error status for each module as described below.  The bit corresponding to such modules turns to 

“1.”

    R3-TSx, R3-RSx, R3-US4: Input burnout
    R3-DA16A:  

 

 Power input in error or disconnected

    R3-YSx:    

 

 Output current error (e.g. load unconnected)

• Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each 

module.  The bit corresponding to such modules turns to “1.”

• Main / Sub Switching Commands given to the network modules result as follows:

 

MAIN’ MODULE 

‘SUB’ MODULE 

OUTPUT MODE

 

Main bus is used; Red light turns on at RUN LED of the I/O modules.

 

Sub bus is used; Green light turns on at RUN LED of the I/O modules.

 

Main bus is used; Amber light turns on at RUN LED of the I/O modules.

 

Output is invalid; RUN LED of the I/O modules turns off.

Содержание R3-NM1

Страница 1: ...es are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical...

Страница 2: ...rom the slot No 1 through 8 Setting for No 9 and later slots is identical to No 8 RUN LED FRONT VIEW SIDE VIEW ERR LED SA1 SA2 1 2 3 4 5 6 Terminal Block Node Address MSD Node Address LSD Transmission...

Страница 3: ...ERNAL DIMENSIONS unit mm inch MODBUS WIRING 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 6 M3 SCREW 6 2 24 TERMINATOR Tx Rx Tx Rx SG Rx Rx HOST PC DA DB DG SLD FG R3 NM1 DA...

Страница 4: ...15 Force Multiple Coils X Digital output from the slave read write 16 Preset Multiple Registers X General purpose register within the slave read write 17 Report Slave ID 18 Program 884 M84 19 Reset Co...

Страница 5: ...7 1072 Data Error Status Input Registers 3X 1 256 I Analog Input 257 768 F Analog Input Holding Registers 4X 1 256 I Analog Output 257 768 F Analog Output I Integer 0 10000 0 100 F Floating 32 bit dat...

Страница 6: ...the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values represented in 2 s complements ACCUMULATED COUNT DATA 32 bit data models R3 PA2 PA4A WT1 WT4 et...

Страница 7: ...fo m system co jp 0 15 Input 1 Output 1 Input 2 Output 2 Input 3 Output 3 Input 16 Output 16 0 OFF open 1 ON close DISCRETE DATA models R3 DA16 and DC16 MAIN SUB SWITCHING CONTROL 1 When the main sub...

Отзывы: