R3-NL1

P. 4 / 8

EM-8427 Rev.5

I/O COMBINATIONS

A dedicated Device File for each I/O device depending upon I/O combinations is required to set up the R3-NL1 using an
integration tool such as Lon Maker.
On-line download is available for Device Image files at http://www.m-system.co.jp/.
Functional Blocks usable for respective files are not identical to all.  Refer to the table below.

FUNCTIONAL BLOCKS

 NODE OBJECT

NodeObject

NVI 1

nviRequest

SNVT_obj_request

NVO 1

nvoStatus

SNVT_obj_status

NVO 2

nvoFileDirectory

SNVT_address

NVO 3

nvoCommErr

SNVT_count

Number of internal 
communication errors

NVO 4

nvoCardState

SNVT_state

NVO 5

nvoCardErr

SNVT_state

Each module's error status

Each module status

cpMaxSendTime

cpMinSendTime

: SCPTmaxSendTime

: SCPTminSendTime

Input data sending intervals

Input data minimum sending intervals

Configuration Properties

ANALOG INPUT / OUTPUT

NO. of DATA

DEVICE IMAGE

USABLE FUNCTIONAL BLOCKS

INPUT OUTPUT

(APB FILE)

16

  0

R3NL1_1_101.APB

NodeObjet, GetValue [0 ... 15] (Can be defined from 0 to 15)

12

  4

R3NL1_2_101.APB

NodeObjet, GetValue [0 ... 11], SetValue [0 ... 3]

  8

  8

R3NL1_3_101.APB

NodeObjet, GetValue [0 ... 7], SetValue [0 ... 7]

  4

12

R3NL1_4_101.APB

NodeObjet, GetValue [0 ... 3], SetValue [0 ... 11]

  0

16

R3NL1_5_101.APB

NodeObjet, SetValue [0 ... 15]

DISCRETE INPUT / OUTPUT

NO. of DATA

DEVICE IMAGE

USABLE FUNCTIONAL BLOCKS

INPUT OUTPUT

(APB FILE)

  0

48

R3NL1_6_101.APB

NodeObjet, R3Do [0 ... 2] (One (1) block can handle 16 contacts.)

48

  0

R3NL1_7_101.APB

NodeObjet, R3Di [0 ... 2]

Содержание R3-NL1

Страница 1: ...nvironmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct AND The u...

Страница 2: ...W2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions Data Allocation Setting Dual Communication SW3 When two network modules are mounted one must be Main OFF network and the other must be Sub ON network For single communication the network module must always be set to Main OFF Input Error Data SW3 Hold When the communication from an input module is lost due to the input module err...

Страница 3: ...ess terminals with insulation sleeve do not fit Applicable wire size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 6 M3 SCREW 6 2 24 COMMUNICATION CABLE CONNECTIONS INTERNAL POWER INTERNAL COMM BUS CONFIGURATION JACK JACK BUS CONNECTOR Not provided with No Power Supply type module 1 4 RUN RUN RUN CONTACT OUTPU...

Страница 4: ... NVO 5 nvoCardErr SNVT_state Each module s error status Each module status cpMaxSendTime cpMinSendTime SCPTmaxSendTime SCPTminSendTime Input data sending intervals Input data minimum sending intervals Configuration Properties ANALOG INPUT OUTPUT NO of DATA DEVICE IMAGE USABLE FUNCTIONAL BLOCKS INPUT OUTPUT APB FILE 16 0 R3NL1_1_101 APB NodeObjet GetValue 0 15 Can be defined from 0 to 15 12 4 R3NL1...

Страница 5: ...nvoVal Value deviation to be sent SCPTnvType Network variable type etc Configuration Properties ANALOG OUTPUT FUNCTIONAL BLOCKS SetValue 0 through 15 SetValue X cpNviDefValue cpNviMaxRnge cpNviMinRnge cpNviType identical to nviVal identical to nviVal Default value at the startup Span full scale value identical to nviVal Zero value SCPTnvType Network variable type etc Configuration Properties nviVa...

Страница 6: ... 65535 0 nvoCardStatus SNVT_state Indicates that I O modules are mounted in each slot 0 or 1 Bit 0 through bit 15 are applied for slot 1 through 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Not mounted 1 Mounted nvoCardErr SNVT_state Indicates error status for each module slot 0 or 1 Bit 0 through bit 15 are applied for slot 1 through 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Normal 1 Error CONFIGURATION TYPE ...

Страница 7: ... Default nvoVal SNVT_lev_percent Data acquired from assigned channels 163 85 through 163 830 Set SNVT_lev_percent for the input types other than 0 0 discrete or temperature Change the network variable type according to the input type if necessary ConfigurationProperty value must be re read after the network variable type is changed Use ResyncCP on the LonMaker SNVT_state For descrete inputs change...

Страница 8: ...lowed by Output or SetValue R3Do The 1st output must be the 1st transmitted data in the slot next to the one with the last input data Example 1 Data Area Module 1 4 GetValue 0 3 Module 2 4 GetValue 4 7 Module 3 4 SetValue 0 Module 4 1 SetValue 1 Module 5 1 SetValue 2 Module 6 1 SetValue 3 Module 7 1 SetValue 4 Module 8 1 SetValue 5 Module 9 1 SetValue 6 Module 10 1 SetValue 7 Example 2 Data Area M...

Отзывы: