background image

R3-NL1

P. 6 / 8

EM-8427 Rev.5

■ 

NodeObject FUNCTIONAL BLOCKS

NETWORK

TYPE

EXPLANATIONS

VARIABLE

{Range}
{Default}

nviRequest

SNVT_obj_request

Used for integration tools such as LonMaker.

{Usable RQ
RQ_NORMAL
RQ_REPORT_MASK
RQ_UPDATE_STATUS}

nvoStatus

Used for integration tools such as LonMaker.
• nviRequest RQ_NORMAL
   0 is set at nvoStatus.
• nviRequest RQ_REPORT_MASK
   report_mask bit is set at nvoStatus.
• nviRequest RQ_UPDATE_STATUE
   0 is set at nvoStatus.
• 1 is set at invalid_id when any value other than the above
   three types is set at nviRequest.

nvoFileDirectory

SNVT_address

Used for integration tools such as LonMaker.

nvoCommErr

SNVT_count

Counted in internal communication errors.

{0-65535}

Reset to 0 after the count has reached 65535.

{0}

nvoCardStatus

SNVT_state

Indicates that I/O modules are mounted in each slot.

{0 or 1}

Bit 0 through bit 15 are applied for slot 1 through 16.

{0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0}

0 : Not mounted     1 : Mounted

nvoCardErr

SNVT_state

Indicates error status for each module/slot.

{0 or 1}

Bit 0 through bit 15 are applied for slot 1 through 16.

{0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0}

0 : Normal     1 : Error

CONFIGURATION

TYPE

EXPLANATIONS

PROPERTY

{Range}
{Default}

cpMaxSendTime

SCPTmaxSendTime

Sending time intervals of nvoVal [0 – 15]

{0.0-6653.4}

Network variables are sent out in this time intervals even

{10.0}

when there is no change in input signals.

cpMinSendTime

SCPTminSendTime

Minimum sending time intervals of nvoVal [0 – 15]

{0.0-6653.4}

This minimum time intervals is maintained even when the

{0.0}

input signals changes faster than it.

DISCRETE OUTPUT FUNCTIONAL BLOCKS (R3Do [0] through [2])

R3Do [X]

nviDoch01
        :
nviDoch16

SNVT_switch

nvoDoState

SNVT_state

Содержание R3-NL1

Страница 1: ...nvironmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 30 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct AND The u...

Страница 2: ...W2 ON 8 7 6 5 4 3 2 1 SW3 ON 4 3 2 1 ON 8 7 6 5 4 3 2 1 SW1 Functions Data Allocation Setting Dual Communication SW3 When two network modules are mounted one must be Main OFF network and the other must be Sub ON network For single communication the network module must always be set to Main OFF Input Error Data SW3 Hold When the communication from an input module is lost due to the input module err...

Страница 3: ...ess terminals with insulation sleeve do not fit Applicable wire size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUIDE TERMINAL COVER 6 M3 SCREW 6 2 24 COMMUNICATION CABLE CONNECTIONS INTERNAL POWER INTERNAL COMM BUS CONFIGURATION JACK JACK BUS CONNECTOR Not provided with No Power Supply type module 1 4 RUN RUN RUN CONTACT OUTPU...

Страница 4: ... NVO 5 nvoCardErr SNVT_state Each module s error status Each module status cpMaxSendTime cpMinSendTime SCPTmaxSendTime SCPTminSendTime Input data sending intervals Input data minimum sending intervals Configuration Properties ANALOG INPUT OUTPUT NO of DATA DEVICE IMAGE USABLE FUNCTIONAL BLOCKS INPUT OUTPUT APB FILE 16 0 R3NL1_1_101 APB NodeObjet GetValue 0 15 Can be defined from 0 to 15 12 4 R3NL1...

Страница 5: ...nvoVal Value deviation to be sent SCPTnvType Network variable type etc Configuration Properties ANALOG OUTPUT FUNCTIONAL BLOCKS SetValue 0 through 15 SetValue X cpNviDefValue cpNviMaxRnge cpNviMinRnge cpNviType identical to nviVal identical to nviVal Default value at the startup Span full scale value identical to nviVal Zero value SCPTnvType Network variable type etc Configuration Properties nviVa...

Страница 6: ... 65535 0 nvoCardStatus SNVT_state Indicates that I O modules are mounted in each slot 0 or 1 Bit 0 through bit 15 are applied for slot 1 through 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Not mounted 1 Mounted nvoCardErr SNVT_state Indicates error status for each module slot 0 or 1 Bit 0 through bit 15 are applied for slot 1 through 16 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Normal 1 Error CONFIGURATION TYPE ...

Страница 7: ... Default nvoVal SNVT_lev_percent Data acquired from assigned channels 163 85 through 163 830 Set SNVT_lev_percent for the input types other than 0 0 discrete or temperature Change the network variable type according to the input type if necessary ConfigurationProperty value must be re read after the network variable type is changed Use ResyncCP on the LonMaker SNVT_state For descrete inputs change...

Страница 8: ...lowed by Output or SetValue R3Do The 1st output must be the 1st transmitted data in the slot next to the one with the last input data Example 1 Data Area Module 1 4 GetValue 0 3 Module 2 4 GetValue 4 7 Module 3 4 SetValue 0 Module 4 1 SetValue 1 Module 5 1 SetValue 2 Module 6 1 SetValue 3 Module 7 1 SetValue 4 Module 8 1 SetValue 5 Module 9 1 SetValue 6 Module 10 1 SetValue 7 Example 2 Data Area M...