CONFIGURATOR SOFTWARE SETTING
The following parameters can be set with using PC Configurator Software (model: R10CFG)
Refer to the users manual for the R30CFG for detailed operation of the software program.
■
INPUT SETTING
Each channel can be set independently.
ITEM
SETTING RANGE
DEFAULT VALUE
Clamp-on Current Sensor
CLSE-R5 / CLSE-05 / CLSE-10 / CLSE-20 / CLSE-40 / CLSE-60
CLSE-R5
Zero Input
CLSE-R5: 0.000 - 5.000 (≤ full input)
0.000
CLSE-05: 0.00 - 50.00 (≤ full input)
CLSE-10: 0.00 - 100.00 (≤ full input)
CLSE-20: 0.00 - 200.00 (≤ full input)
CLSE-40: 0.00 - 400.00 (≤ full input)
CLSE-60: 0.00 - 600.00 (≤ full input)
Full Input
CLSE-R5: 0.000 - 5.000 (≥ zero input)
0.000
CLSE-05: 0.00 - 50.00 (≥ zero input)
CLSE-10: 0.00 - 100.00 (≥ zero input)
CLSE-20: 0.00 - 200.00 (≥ zero input)
CLSE-40: 0.00 - 400.00 (≥ zero input)
CLSE-60: 0.00 - 600.00 (≥ zero input)
Zero Fine Adjust
-320.00 - 320.00
0.00 (%)
Gain Zero Adjust
-3.2000 - 3.2000
1.0000
Zero Scaling
-32000 - 32000
0
Full Scaling
-32000 - 32000
10000
Cutout
0.0 - 5.0 (%)
1.0 (%)
■
MODBUS SETTING
ITEM
SETTING RANGE
DEFAULT SETTING
Data Mode
Modbus-RTU / Modbus-ASCII
Modbus-RTU
Address
1 - 247
1
Baud Rate
38400 / 19200 / 9600 / 4800 bps
38400 bps
Parity
None / Odd / Even
None
Communication timeout duration 0.1 - 3200.0 (sec.)
3.0 sec.
Depending on data mode and parity bit setting, data bit and stop bit are as following.
DATA MODE
PARITY BIT
DATA BIT
STOP BIT
Modbus-RTU
None
8
2
Odd or Even
8
1
Modbus-ASCII
None
7
2
Odd or Even
7
1