R10M-CT4E

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-6247  P. 2 / 7

COMPONENT IDENTIFICATION

 

FRONT VIEW

Specifications (side)

Configurator Jack

Status Indicator LED

 

STATUS INDICATORS

ID

STATUS COLOR

FUNCTION

Power

ON

Green

Power is supplied.

OFF

Power is not supplied or an abnormal-
ity occurs in the unit.

Run

ON

Green

Modbus communication is in normal 
status.

OFF

Modbus communication error or during 
no Modbus communication.

Error

ON

Red

Abnormality occurs in the unit.
(i.g. memory failure)

OFF

Normal status.

SD

ON

Green

Sending data via RS-485 

RD

ON

Green

Receiving data via RS-485

 

TERMINAL ASSIGNMENTS

1

 K1
6

 L1

2

 K2

3

 K3

4

 K4

5

 NC

7

 L2

8

 L3

9

 L4

10

 NC

11

 FE
16

SLD

12

 DB

13

 DA

14

 NC

15

FE1

17

 DG

18

 NC

19

24V

20

 0V

PIN 
NO.

ID

FUNCTION

PIN 
NO.

ID

FUNCTION

1

K1

Input 1-K

11

FE

Modbus grounding

2

K2

Input 2-K

12

DB DB

3

K3

Input 3-K

13

DA DA

4

K4

Input 4-K

14

NC Unused

5

NC Unused

15

FE1 Power grounding

6

L1

Input 1-L

16

SLD Shield

7

L2

Input 2-L

17

DG DG

8

L3

Input 3-L

18

NC Unused

9

L4

Input 4-L

19

24V Power supply 24V DC

10

NC Unused

20

0V

Power supply 0V DC

Содержание R10M-CT4E

Страница 1: ...s connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole system...

Страница 2: ...during no Modbus communication Error ON Red Abnormality occurs in the unit i g memory failure OFF Normal status SD ON Green Sending data via RS 485 RD ON Green Receiving data via RS 485 TERMINAL ASSIG...

Страница 3: ...t CLSE 40 0 00 400 00 full input CLSE 60 0 00 600 00 full input Full Input CLSE R5 0 000 5 000 zero input 0 000 CLSE 05 0 00 50 00 zero input CLSE 10 0 00 100 00 zero input CLSE 20 0 00 200 00 zero in...

Страница 4: ...ARALLEL Mounting the unit A Hook the upper hook at the rear side of the base onto the DIN rail B Push the lower part of the unit in the direction of the arrow until the base is firmly fixed to the DIN...

Страница 5: ...NSIONS unit mm inch DIN rail 35mm wide When mounting no extra space is needed between units 36 1 42 7 28 5 20 89 3 50 5 20 7 28 72 2 83 80 3 15 45 1 77 4 16 CONNECTION DIAGRAM 1 6 2 7 3 8 4 9 Jack 12...

Страница 6: ...SLD FE TERMINATOR TERMINATOR Note The terminator must be connected across DA and DB at both ends of communication line WIRING COMMUNICATION WITH HOST PC MODBUS I O MODULE WIRING INSTRUCTIONS FOR BASE...

Страница 7: ...ge error Input Register 3X 1 I Analog Input analog input 1 2 I Analog Input analog input 2 3 I Analog Input analog input 3 4 I Analog Input analog input 4 Note DO NOT access addresses other than the o...

Отзывы: