4. STATUS INDICATOR LED AND SIDE DIP SWITCH
■
STATUS INDICATOR LED
ID
COLOR
STATUS
FUNCTION
PWR
Green
ON
Power is ON.
INP
Green
ON
Position setpoint input (analog) of 0.37 V or greater is applied.
(With 250 Ω receiving resistor for current input)
STA
Green
Blinks at 1 Hz
Auto-setup is in process.
Blinks at 5 Hz for 3 sec.
Auto-setup has been successfully completed.
COM
Green
ON for 1 sec.
Returning response.
ALM
Red
Blinks at 0.5 Hz
System error (memory)
ON
Motor deadlock alarm is output.
Blinks at 5 Hz
Auto-setup has failed.
■
SIDE DIP SWITCH SETTING
SW1
FUNCTION
SW1-1
SW1-2
Specify the operation of the output stem when abnormally low input is detected.
(INP LED is OFF).
SW1-1
SW1-2
Operation of the Output Stem
–
ON
Stop
OFF
OFF
Extend (Go DOWN)
ON
OFF
Retract (Go UP)
SW1-3
OFF
Reverse (Output stem goes UP with 20 mA DC input)
ON
Direct (Output stem goes DOWN with 20 mA DC input)
SW1-4
OFF
Output stem moves while the manual operation button is pressed in Manual Operation mode.
ON
Output stem moves inch by inch each time the manual operation button is pressed in Manual Opera-
tion mode for fine adjustment.
SW1-5
The output stem position when the switch is turned OFF is recorded as the upper-end position.
SW1-6
The output stem position when the switch is turned OFF is recorded as the lower-end position.
SW1-7
Auto-setup starts when the switch is turned OFF in Manual Operation mode.
SW1-8
OFF
Automatic operation
(Operation is performed based on input signal or Modbus)
ON
Manual operation
(Manual operation buttons are enabled and Auto-setup can be started.)
■
MANUAL OPERATION BUTTON
ID
FUNCTION
UPPER
The output stem moves upward in Manual Operation mode as the button is pressed.
LOWER
The output stem moves downward in Manual Operation mode as the button is pressed.
■
PU-2X MODULAR JACK
Parameter settings for Auto-setup and communication settings for Modbus can be configured on PU-2x.
In addition, operation status of the unit can be monitored on PU-2x.