15.  MAINTENANCE

For effective use and longer life of the Mini-Top electronic actuator, regular checking appropriate for its operating conditions 
are recommended.  Refer to the following table.

ITEM

CHECKING POINT

HOW TO PROCEED

Stem operation

Apply input 0%, 50%, 100%, then back to 50%, 0%.
Check that the actuator operates to the correct posi-
tions at respective input values.

Repair or calibrate the unit.

Abnormal sound

No abnormal sound is heard during operation.

Repair or calibrate the unit.

Water or rust inside 
the housing

Check that there is no water or rust inside the hous-
ing.
If there is water inside, check the packing and the 
wiring cable connector is not loose.

Remove water and dry the housing and the parts 
inside.
Replace rusted parts, if any.
Replace the packing, if damaged.
Re-tighten cable connector, if loose.

Screws

Check that screws and bolts are securely fastened.

Re-tighten them, if loose.

For repair or parts replacement, contact M-System or our representatives.

 

LUBRICATION

There is no need of oiling the Mini-Top electronic actuator in normal operating conditions.

 

REGULAR TEST RUNNING

If the valve is not frequently operated, run a test operation regularly (once a week, for example) to ensure that the actuator 
operates normally.

16.  TROUBLESHOOTING

TROUBLE

LED

POSSIBLE CAUSE

HOW TO PROCEED

PWR

INP

COM

ALM

Actuator does not 
work
(Analog input)

OFF

Power failure
Cable breakage

Check the power supply and cables.

ON

OFF

Input error

Check the input signal level.

ON

ON

Mode is set to Manual operation or 
Modbus input mode.

Check the operation mode.

ON

ON

ON Motor deadlock error

Apply input in reverse direction.

Actuator does not 
work
(Modbus input)

ON

OFF

Modbus communication is not established. Check the communication cable.

Check the Node address.
Check the baud rate.

ON

Blinks

Mode is set to Manual operation or 
Analog input mode.

Check the operation mode.

ON

ON Motor deadlock error

Clear error via Modbus.

Unstable operation

Abnormal power voltage,
Noise

Check power voltage and noise in 
input signal.

17. LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protec-
tors for protection against induced lightning surges. 

 

 

Please consult M-System to choose appropriate models.

Содержание MSP40

Страница 1: ...BLE CONNECTIONS 6 7 OUTPUT STEM STROKES 7 8 SEAL SPRING CONTRACTION AND THRUST 7 9 COMBINATION WITH VALVE 8 10 AUTO SETUP MODE 9 11 PROGRAMMING UNIT MODEL PU 2x 12 12 MODBUS COMMUNICATION 13 13 PARAME...

Страница 2: ...failure to observe the pre cautions could result in personal injury or damage to the property WARNING Remove power supply to the actuator before wiring to the unit It could cause electric shock Do not...

Страница 3: ...to withstand all vibrations M System does not guarantee long term use of the unit even with small vibrations Please use the unit only after evaluating in an actual installation environment Par ticula...

Страница 4: ...l Spring Stepping Motor Potentiometer Cover Nut Output stem Screw Figure 1 Component identification MSP40 MSP50 DA NC IN FE1 UPP UPP LOW LOW ALM ALM 24V GND COM OUT DB DG PWR UPPER LOWER INP STA COM A...

Страница 5: ...h 20 mA DC input ON Direct Output stem goes DOWN with 20 mA DC input SW1 4 OFF Output stem moves while the manual operation button is pressed in Manual Operation mode ON Output stem moves inch by inch...

Страница 6: ...retract UP extend DOWN alarm and or output signals as necessary Modbus communication allows operation without analog input and monitoring of the operation status of the unit DA DB DG IN COM OUT 24V GN...

Страница 7: ...RACTION AND THRUST Thrust and Seal Spring Contraction MODEL RATED THRUST N THRUST WHEN VALVE IS SEATED N THRUST WHEN AUTO SEUP IS COMPLETE N AJUSTABLE MAX CONTRACTION MAX THRUST N MAX THRUST WHEN OUTP...

Страница 8: ...void such a situation select an appropriate combination of an actuator and a valve to secure an enough opera tion distance In the example below the maximum stroke is 20 mm and thus the preferable oper...

Страница 9: ...h back to Automatic Operation mode Note that the actuator immediately starts to operate in accordance with a value of input signal DO NOT touch the output stem and its vicinity as it may cause serious...

Страница 10: ...ositions then stops to end Auto setup 4 Lower Upper seal springs MSP50 only 1 The output stem goes down until the valve contacts the seat surface Auto setup is interrupted if the valve reaches the low...

Страница 11: ...newly set the upper end position To complete the fine adjustment Lower end side Turn SW1 5 from OFF to ON then to OFF again to newly set the lower end position Upper end side Turn SW1 6 from OFF to ON...

Страница 12: ...e display of PU 2x comes on by power supplied to the actuator unit 3 To display a target item press ITEM then N N N represents numerical number 0 to 9 Alternatively use UP or DOWN button to shift to t...

Страница 13: ...ven if the address is writable make sure to set Modbus Operation mode address 111 in advance to enable writing ADDRESS MAP Refer to 13 PARAMETER ITEMS COMMON TO MODBUS AND PU 2x for Modbus address map...

Страница 14: ...04 Inp x R 18 I16 Position setpoint 1 5 0 to 105 0 05 Tar x R 19 I16 Position 1 5 0 to 105 0 06 Pos x R 1 The ratio to the operation distance i e a distance between the lower stop position and the up...

Страница 15: ...times when the duty cycle per minute exceeded 50 1 Clear 0 1 0 26 AccumClr x R W 52 I16 Time ratio of respective positions 1 Clear 0 1 0 27 PosRClr x R W 53 I16 Clear all diagnostics 1 Clear 0 1 0 28...

Страница 16: ...98 0 44 OpnSig x R W 136 I16 Extend DOWN signal position 5 0 to 25 0 2 0 45 ClsSig x R W 137 I16 Deadband 0 1 to 5 0 0 3 46 DBand x R W 138 I16 Restart limiting timer sec 0 0 to 30 0 1 5 47 Restart x...

Страница 17: ...guration mode Stops Modbus input Monitor mode Stops Modbus input mode Follows Modbus input Address 101 Configuration mode Stops ON N A 2 Monitor mode 4 Moves by button operation 1 Configurable on PU 2...

Страница 18: ...acement contact M System or our representatives LUBRICATION There is no need of oiling the Mini Top electronic actuator in normal operating conditions REGULAR TEST RUNNING If the valve is not frequent...

Отзывы: