W2XF
P. / 4
EM-5507
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
OUTPUT RANGING
The internal DIP switch setting is required to select output
types before setting a precise output range using PC Con-
figurator Software (model: W2CFG).
For detailed information on the PC configuration, refer to
the W2CFG users manual.
EXTERNAL VIEWS
Table 1. DIP switch setting: Output 1 type
OUTPUT 1 TYPE SW1-1
SW1-2
SW1-3
SW1-4
0 – 20mA DC
OFF
OFF
ON
OFF
-10 – +10V DC
OFF
ON
OFF
ON
-5 – +5V DC
ON
OFF
OFF
ON
Table 2. DIP switch setting: Output 2 type
OUTPUT 2 TYPE SW2-1
SW2-2
SW2-3
SW2-4
0 – 20mA DC
OFF
OFF
ON
OFF
-10 – +10V DC
OFF
ON
OFF
ON
-5 – +5V DC
ON
OFF
OFF
ON
LED1 (LD1)
LED2 (LD2)
LED3 (LD3)
Configurator Jack
■
FRONT VIEW
■
SIDE VIEW
SW1
SW2
Output 2
Configuration DIP SW
Output 1
Configuration DIP SW
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
*
Provided only for two-output type.
*
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Check DIP switch setting.
3) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
4) Input: Check that the input signal is within 0 – 100% of
the full-scale.
5) Output: Check that the load resistance meets the de-
scribed specifications.
6) LED: Confirm that the LEDs indicate the normal oper-
ating mode.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
■
DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■
WALL MOUNTING
Refer to the external di-
mensions.
10
11
3
+
+
U (+)
V (–)
+
7
8
6
CONFIGURATOR
JACK
+
CURRENT INPUT (Z1)
+
VOLTAGE INPUT (S1, S2)
5
1
2
OUTPUT 1
OUTPUT 2
POWER
The section enclosed by broken line is only with 2nd output option
–
–
–
–
Rugghölzli 2
CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18
Fax +41 (0)56 222 10 12
www.sentronic.com
Produkte, Support und Service
SENTRONIC
AG