M2EXV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
EM-5133-B Rev1 P. 3 / 18
EXTERNAL VIEWS
Display
Mode Button
Set Button
Configurator Jack
Up Button
Down Button
Up
Down
Mode
Set
Output Setting DIP SW
ON
1
2
3
4
5
6
7
8
SW1
OFF
ON
1
2
3
4
5
6
7
8
SW1
OFF
PERCENT
100.00
OUTPUT
20.000
%
mA
COMPONENT
FUNCTION
Display
Indicates present values, setting values and abnormal information.
Two types of present values at up-
per and lower are displayed by setting.
Mode button
Used to shift from measuring mode to each setting mode.
Destination to shift is changed by the time
pressing and holding the button.
Used to return from each setting mode to measuring mode. (press and
hold for 2 sec. or more)
Set button
Used to change setting value of setting parameter.
When at setting changeable state, used to enter
(save) the setting value.
Used to move on through digits of setting value for input/output scaling at
setting changeable state,
Up button
Used to shift through setting parameter, and to increase or select setting value.
Down button
Used to shift through setting parameter, and to decrease or select setting value.
Configurator Jack
Used to configure with M2E configurator software (model: M2ECFG). At the same time, set the lockout
setting of the unit to ‘lock’.
DIP SWITCH
The internal DIP switch for output setting is required to select output types before setting a precise output range using front
buttons or setting with a PC.
Refer to the “PROGRAMMING” for the operation with front buttons. Refer to the users manual (EM-5147) of M2E Configurator
Software (model: M2ECFG) for setting with PC.
Output Range
SW1
1
2
3
4
5
6
7
8
0 – 20mA
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
-5 – +5V
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
-10 – +10V
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
CAUTION:
DO NOT set DIP switches while power is supplied. Otherwise, the unit may fail.