background image

M2EXV

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-5133-B Rev1  P. 10 / 18

[22] Output decimal point

Set decimal point position for [20] 0 % and [21] 100 % output scaling.

SETTING VALUE DESCRIPTION

INITIAL VALUE

oooooo

Decimal point: None

2 places of 
decimals

ooooo.o

Number of decimal places: 1

oooo.oo

Number of decimal places: 2

ooo.ooo

Number of decimal places: 3

oo.oooo

Number of decimal places: 4

o.ooooo

Number of decimal places: 5

[26] Loop test

As pressing Set button enables to blink ‘Cancel’, changing to ‘Set’ by pressing Up or Down and pressing ‘Set’ allows to indicate 
Loop Test display.  Present value is indicated.  Increase or decrease it by pressing Up and Down button.  Press and hold them 
enables to change value continuously.*

1

Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test.

ITEM

26

Loop test

ITEM

26

DATA (Setting) 

DATA (Setting) 

Loop test

Loop test

Up/Down

button

Set button

Set

mA

4.000

0.00

%

Cancel

Output engineering value

Output % value

*1.   While loop test is performing, actual input is disregarded. 

 

While loop test is performing and ‘Display timeout’ is enabled to display off, return to the display on by pressing a front button.

Содержание M2EXV

Страница 1: ...in a panel system The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conform ity Install lightning surge protecto...

Страница 2: ...UNTING Set the base socket so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of base socket on the DIN rail and push in the lower When removing the socket push dow...

Страница 3: ...ing changeable state used to enter save the setting value Used to move on through digits of setting value for input output scaling at setting changeable state Up button Used to shift through setting p...

Страница 4: ...g of the Advanced mode for settings DISPLAY IN EACH SETTING MODE For each setting current values of setting parameter ITEM number and setting value are indicated During setting Setting is indicated at...

Страница 5: ...T POWER ON Measuring Mode Hold down Mode button for 2 seconds Hold down Mode button for 2 seconds Basic Setting Mode Option Mode Advanced Mode Hold down Mode button for 2 seconds Hold down Mode button...

Страница 6: ...ontinuously Down button Press Down button to move through setting parameters Selecting setting value while changing settings decreasing a setting value to set value Keeping pressing Down button enable...

Страница 7: ...seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down...

Страница 8: ...00 900 0 1000 0 9 000 10 000 mA mV V 20 00 14 0 input scaling 99999 999999 0 00 15 100 input scaling 99999 999999 100 00 16 Input decimal point No decimal point The number of decimal places 1 5 2 pla...

Страница 9: ...ing Set the display value of 100 input setting SETTING RANGE INITIALVALUE 99999 999999 100 00 16 Input decimal point Set the decimal point position of 14 0 and 15 100 input display scaling SETTING VAL...

Страница 10: ...Set button enables to blink Cancel changing to Set by pressing Up or Down and pressing Set allows to indicate Loop Test display Present value is indicated Increase or decrease it by pressing Up and D...

Страница 11: ...old down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down 1 1 0 30 5 000 5 000 95 000 105 000 5 000...

Страница 12: ...on enables to move on selected characters Set button enables to select a character While setting pressing Mode button enables to delete a character pressing and holding Mode button ena bles to discard...

Страница 13: ...Mode button for 6 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down 1 1 4 0 1 60 OFF RESET Lock Unlock Advanced Mode Paramete...

Страница 14: ...ust brightness of display It is available to set the range between 1 darkest 4 brightest Initial value 4 92 Display timeout Set the time to off the display when there is no operation within a certain...

Страница 15: ...button for 8 seconds Hold down Mode button for 2 seconds Set Set Set Set Set Set Set Set Set Set Set Set Set Up Down Up Down Up Down Up Down Up Down Up Down Up Down Up Down Disable Enable 2 111 5 00...

Страница 16: ...een 5 to 105 for both X and Y For X it is required to set in ascending order from X001 Be sure that if it is set with other than ascending order cor rect conversion is not carried out Initial value X0...

Страница 17: ...display settng Error is indicated blinking at upper or lower When multiple error occurs only high priority error is displayed Order of priority is EEPROM ERROR OVER RANGE SCALING ERROR in descending o...

Страница 18: ...47 when adjusting with M2E Configurator Software model M2ECFG And then follow the procedure shown below INPUT FINE ADJUSTMENT 1 Set the input signal to 0 and adjust the input display to 0 by 69 Input...

Отзывы: