M2EXV
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
EM-5133-B Rev1 P. 10 / 18
[22] Output decimal point
Set decimal point position for [20] 0 % and [21] 100 % output scaling.
SETTING VALUE DESCRIPTION
INITIAL VALUE
oooooo
Decimal point: None
2 places of
decimals
ooooo.o
Number of decimal places: 1
oooo.oo
Number of decimal places: 2
ooo.ooo
Number of decimal places: 3
oo.oooo
Number of decimal places: 4
o.ooooo
Number of decimal places: 5
[26] Loop test
As pressing Set button enables to blink ‘Cancel’, changing to ‘Set’ by pressing Up or Down and pressing ‘Set’ allows to indicate
Loop Test display. Present value is indicated. Increase or decrease it by pressing Up and Down button. Press and hold them
enables to change value continuously.*
1
Pressing and holding Mode button more than 2 seconds or turning off the power enable to exit loop test.
ITEM
26
Loop test
ITEM
26
DATA (Setting)
DATA (Setting)
Loop test
Loop test
Up/Down
button
Set button
Set
mA
4.000
0.00
%
Cancel
Output engineering value
Output % value
*1. While loop test is performing, actual input is disregarded.
While loop test is performing and ‘Display timeout’ is enabled to display off, return to the display on by pressing a front button.