background image

R30GECT1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9029    P. 10 / 12

 

Detected Module Ident List (Module Information List: 0xF050)

Module information list is allocated to 0xF050.
Each Sub-Index number in the list represents the module address. 
0 is set as the Sub-Index number for a non-existing module.  See Table 13 below.

 

Configured Module Ident List (Module Information Collation by Master Module: 0xF030)

0xF030 is referred to for confirming the configuration of modules registered on the master module.
Module Indent is written for each module that is existing (recognized by the master) with Sub-Index number as the module 
address.
The slave confirms the Module Ident to determine whether writing is correct (successful) or wrong (failed).
When all is correct, objects 0xF030 and 0xF050 show the same configuration.
0xF030 is solely for the confirmation by the master, and thus can be omitted. 

Table 13: Object Configuration For Module Information List 

INDEX

SUB-INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0xF030

0

UINT8

8

RW

1

Number of items

1

UINT32

32

RW

120

Module Ident or 0 (confirmed by master)

0xF050

0

UINT8

8

RO

1

Number of items

1

UINT32

32

RO

120

Module Ident or 0

 

Device Type (0x1000)

The device type is allocated to 0x1000.
The device type is 5001.

Table 14: Object Configuration For Device Type

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1000

UINT32

32

RO

5001

Device type

 

ERROR REGISTER (0x1001)

The object 0x1001 is not used.

 

Manufacturer Device Name (0x1008)

The device name is allocated to 0x1008 in String form.

Table 15: Object 0x1008 Configuration

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1008

STRING

32

RO

R30GECT1

Model number

 

Manufacturer Hardware Version (0x1009)

The hardware device version is allocated to 0x1009 in String form.
The version format is ‘n.nn’.

Table 16: Object Configuration For Hardware Version

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x1009

STRING

32

RO

n.nn

Hardware version

 

Manufacturer Software Version (0x100A)

The software version is allocated to 0x100A in String form.
The version format is ‘n.nn’.

Table 17: Object Configuration For Software Version

INDEX

DATA TYPE

BIT

ACCESS

VALUE

CONTENT

0x100A

STRING

32

RO

n.nn

Software version

Содержание EtherCAT R30GECT1

Страница 1: ...HOT SWAPPABLE MODULES It is possible to replace a module with the power supplied provided that the module is replaced with one with the same model number and installed in the same base slot Turn off s...

Страница 2: ...ERR Error Red Off No error Blinking Invalid Configuration Single Flash Local error Double Flash Process data watchdog timeout EtherCAT watchdog timeout On Application Controller failure L A IN IN por...

Страница 3: ...t is vacant blank data is sent or received to from the PLC etc PWR COM I O1 I On HOW TO MOUNT THE MODULE 1 Engage the positioning guide of the module with the In stallation Base 2 Pivot the module on...

Страница 4: ...6 6659 8510 E mail info m system co jp EM 9029 P 4 12 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 110 4 33 25 98 98 3 86 CONNECTION DIAGRAM CONNECTOR...

Страница 5: ...ror register Manufacturer Device Name 0x1008 Device name Manufacturer Hardware Version 0x1009 Hardware version Manufacturer Software Version 0x100A Software version Identity Objects 0x1018 Vendor info...

Страница 6: ...29 FreeRun needs 3 Buffer mode 0x8000 Internal bus error at power on vendor specific error 0x8001 Internal bus error during communication vendor specific error SDO Abort Code When the master attempts...

Страница 7: ...the R30GECT1 communicates with the master normally while 0x000F is set during non communication or communication error with the master Table 5 Object Configuration for Module Status INDEX SUB INDEX DA...

Страница 8: ...ty Group 0 Group 1 Table 8 Object Configuration For PDO Allocation List INDEX SUB INDEX DATA TYPE BIT ACCESS VALUE CONTENT 0x1C12 0 UINT8 8 RO 2 Number of items 1 UINT16 16 RO 0x1600 Output data 2 UIN...

Страница 9: ...Modular Device Profile Objects MDP Information 0xF000 Modular Device Profile MDP information is allocated to 0xF000 The Index interval the maximum number of modules and the PDO group of the slave dev...

Страница 10: ...st INDEX SUB INDEX DATA TYPE BIT ACCESS VALUE CONTENT 0xF030 0 UINT8 8 RW 1 Number of items 1 UINT32 32 RW 120 Module Ident or 0 confirmed by master 0xF050 0 UINT8 8 RO 1 Number of items 1 UINT32 32 R...

Страница 11: ...ng with two alpha numeral characters followed by six numeral characters The serial number is expressed as 32 bit data divided into 6 bit 6 bit and 20 bit groups with the first two characters con verte...

Страница 12: ...Output Area Objects Input data Input Area Objects DATA FLOW R30Nx R30 Newtork module FLOW OF OUTPUT DATA EtherCAT master R30GECT1 R30 internal bus R30 Network module Host PC PLC Output data Output Are...

Отзывы: