EtherCAT SPECIFICATIONS

 

Modular Device Profile

R30GECT1 complies with the Modular Device Profile (MDP) standard, ETG.5001.1 of the EtherCAT standard.
Be sure that the master supports the MDP standard.

 

Fixed Address

R30GECT

1 supports Explicit Device Identification by allowing setting of fixed address using the fixed address setting rotary 

switches (ID selector).
The fixed address can be set to 1 to 255.
When fixed address is not used, set the ID selector to 0.

When the power is turned on with the ID selector set to other than 0, the designated address is written in the register 0x0012  
(Configured Station Alias) of ESC (EtherCAT Slave Controller) when R30GECT1 starts up.

 

Process Data Configuration

The number of data R30GECT1 can transmits: 4 points (4 words) for input; and 4 points (4 words) for output.

 

Data Configuration

The data configuration is in accordance with the EtherCAT Modular Device Profile (MDP) specifications. 

Table 1: Data Configuration

OBJECT

ADDRESS

CONTENT

Device Type

0x1000

Device type

Error register

0x1001

Error register

Manufacturer Device Name

0x1008

Device name

Manufacturer Hardware Version

0x1009

Hardware version

Manufacturer Software Version

0x100A

Software version

Identity Objects

0x1018

Vendor information

PDO Mapping Objects (RxPDO)

0x1600

Output data list

RxPDO Gap

0x1701

Output data gap

PDO Mapping Objects (TxPDO)

0x1A00

Input data list

PDO Mapping Objects (TxPDO)

0x1AFF

Status data list

TxPDO Gap

0x1B01

Input data gap

Sync Manager Type

0x1C00

Sync manager type

PDO Assign (OUT)

0x1C12

Output data transmission order

PDO Assign (IN)

0x1C13

Input data transmission order

Sync Manager Parameter Objects

0x1C32, 0x1C33

Sync manager parameter 

Manufacturer Specific Objects

0x2000

Module status

Input Area Objects

0x6000

Input data

Output Area Objects

0x7000

Output data

Information Data Objects

0x9000

Module information

Modular Device Profile Objects

0xF000

MDP information

Configured Module Ident List

0xF030

Module information collation by master module

Detected Module Ident List

0xF050

Module information list

 

EtherCAT State

EtherCAT defines four states of slave: INIT, PREOP, SAFEOP, and OP.  
TxPDO (input configuration data) is updated in the SAFEOP or OP state, and RxPDO (output configuration data) is updated 
only in the OP state.

The RUN LED turns on only in the OP state and input data and output data are updated, while only input data is updated 
in the PREOP state.

Содержание EtherCAT R30GECT1

Страница 1: ...HOT SWAPPABLE MODULES It is possible to replace a module with the power supplied provided that the module is replaced with one with the same model number and installed in the same base slot Turn off s...

Страница 2: ...ERR Error Red Off No error Blinking Invalid Configuration Single Flash Local error Double Flash Process data watchdog timeout EtherCAT watchdog timeout On Application Controller failure L A IN IN por...

Страница 3: ...t is vacant blank data is sent or received to from the PLC etc PWR COM I O1 I On HOW TO MOUNT THE MODULE 1 Engage the positioning guide of the module with the In stallation Base 2 Pivot the module on...

Страница 4: ...6 6659 8510 E mail info m system co jp EM 9029 P 4 12 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 110 4 33 25 98 98 3 86 CONNECTION DIAGRAM CONNECTOR...

Страница 5: ...ror register Manufacturer Device Name 0x1008 Device name Manufacturer Hardware Version 0x1009 Hardware version Manufacturer Software Version 0x100A Software version Identity Objects 0x1018 Vendor info...

Страница 6: ...29 FreeRun needs 3 Buffer mode 0x8000 Internal bus error at power on vendor specific error 0x8001 Internal bus error during communication vendor specific error SDO Abort Code When the master attempts...

Страница 7: ...the R30GECT1 communicates with the master normally while 0x000F is set during non communication or communication error with the master Table 5 Object Configuration for Module Status INDEX SUB INDEX DA...

Страница 8: ...ty Group 0 Group 1 Table 8 Object Configuration For PDO Allocation List INDEX SUB INDEX DATA TYPE BIT ACCESS VALUE CONTENT 0x1C12 0 UINT8 8 RO 2 Number of items 1 UINT16 16 RO 0x1600 Output data 2 UIN...

Страница 9: ...Modular Device Profile Objects MDP Information 0xF000 Modular Device Profile MDP information is allocated to 0xF000 The Index interval the maximum number of modules and the PDO group of the slave dev...

Страница 10: ...st INDEX SUB INDEX DATA TYPE BIT ACCESS VALUE CONTENT 0xF030 0 UINT8 8 RW 1 Number of items 1 UINT32 32 RW 120 Module Ident or 0 confirmed by master 0xF050 0 UINT8 8 RO 1 Number of items 1 UINT32 32 R...

Страница 11: ...ng with two alpha numeral characters followed by six numeral characters The serial number is expressed as 32 bit data divided into 6 bit 6 bit and 20 bit groups with the first two characters con verte...

Страница 12: ...Output Area Objects Input data Input Area Objects DATA FLOW R30Nx R30 Newtork module FLOW OF OUTPUT DATA EtherCAT master R30GECT1 R30 internal bus R30 Network module Host PC PLC Output data Output Are...

Отзывы: