53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 47 / 52
Alarm Output Setting
(ALARM)
Change Setting
(SETTINGS)
Power ON delay time
(POWON DLY)
0 thr. 999 seconds (0)
Latching
(LATCHING)
DISABLE (
*
)
ENABLE
Operating mode
(MODE)
Operatint time
(OFF TIMER)
Display brightness
(BRIGHTNESS)
View type memory
(MODE)
Recover-to-default time
(TIMER)
*
7. Refer to “ALARM OUTPUT SETTING.”
*
8. The backlight turns on regardless of this setting in case of alarms/errors.
*
9. Ver.1.**
Backlight
(BACKLIGHT)
AUTO : ON by operation and at alarm
OFF by timer (
*
)
ON : Continuously ON
OFF : Continuously OFF
My Default View
(DEFAULT)
CURRENT : Save the view on display
CYCLIC : ∑ view auto cyclic switching
DISABLE : No auto recovery (
*
)
1 thr. 999 sec. from last operation
∑1
∑2
∑3
∑4
Reset customization
(RESET)
∑ View
Customization
(CUSTOMIZE)
0 : Fastest (
*
)
1 thr. 60 seconds
Display Update
Rate (UPD RATE)
Choose measurands to be displayed on
Line 1 thr. Line 3
NO : Cancel
YES : Reset
1 thr. 999 seconds (600)
1 : Dark
2 : Normal (
*
)
3 : Bright
Measurands
*
7
I1-3
IN
U12-31
U1N-3N
P
Q
S
PF
F
I1-3 AVG
IN AVG
P AVG
Q AVG
S AVG
THDI1-3
THDIN
THDU12-31
THDU1N-3N
UT12-31
High setpoint
(HIGH)
HIGH :
*
7 (0)
LOW :
*
7 (0)
Low setpoint
(LOW)
Hysteresis (deadband)
(HYSTERES)
0.0 thr. 99.9% (0.0)
0 thr. 999 seconds (0)
Alarm ON delay time
(ON DELAY)
DISABLE : Disable alarm (
*
)
DISP ONLY : Display only
DOUT4 : Discrete output 4 + display
DOUT3 : Discrete output 3 + display
DOUT2 : Discrete output 2 + display
DOUT1 : Discrete output 1 + display
Alarm output
(OUTPUT)
(
*
) or ( ) : Factory setting
Display Setting
(DISPLAY)
Reset Alarm
(CLR ALARM)
ENABLE (
*
)
DISABLE
Shortcut Menu
(SHORTCUT)
*
9
*
9
View type memory
(SAVE)
NO : Cancel
YES : Save the view on display
*
8
2.00
2.00
DO
2.00
2.00