53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 14 / 52
ADDR.
WORD
PARAMETER
5735
1
Long register (32-bit words assignments)
0 : Normal (*) Lower digit word at the lower address
1 : Swap Lower digit word at the higher address
(*) Factory setting
■
DEMAND SETTING
ADDR.
WORD
PARAMETER
UNIT
5857
1
Average (demand) current update interval
0 : External trigger signal
1 to 60 : Minutes
Factory setting : 30
Minutes
5858
1
Average (demand) power update interval
0 : External trigger signal
1 to 60 : Minutes
Factory setting : 30
Minutes
■
STYLE SETTING
ADDR.
WORD
PARAMETER
5985
1
Input line indication
0 : 1 – 2 – 3 (*)
1 : R – S – T
5986
1
Phase difference direction indication
0 : IND / CAP (*)
1 : LEAD / LAG
5987
1
Power factor (PF1 through PF3, PF) sign
0 : Standard (IEC) (*)
Identical to the active energy
1 : Special type 1 (IEEE) Positive in LAG, Negative in LEAD
5988
1
Reactive power (Q1 through Q3, Q) sign
0 : Standard (IEC) (*)
Positive from [PF = 1.0] to 180° in LAG direction; Negative for the other direction
1 : Special type 1
Positive in LAG, Negative in LEAD
5989
1
Reactive power (Q1 through Q3) calculation (Q = Q1 + Q2 + Q3)
0 : Standard (*)
Qn =
√
Sn
2
– Pn
2
1 : Reactive power meter method Qn =
1
Nsmp
Nsmp
(Un
i
– Nu
i
) I
i + (Nsmp / 4)
∑
i = 1
5990
1
Apparent power (S) calculation
0 : Standard
(*)
S =
√
P
2
+ Q
2
1 : Sum
S =
S1 + S2 + S3
5991
1
Unit used to indicate power up to 9999
2.00
0 : With ‘k’ (0.000 k) (*)
1 : Without ‘k’ (0000)
(*) Factory setting
Note: ‘1,’ ‘2,’ ‘3’ in expressions like Q1, Q2, Q3 indicate ‘R,’ ‘S,’ ‘T’ respectively.
■
DISCRETE I/O SETTING
DO
DI
ADDR.
WORD
PARAMETER
6113
1
Discrete output 1 function
0 : Undefined (*)
1 : Energy count
2 : Alarm
6114
1
Discrete output 1 contact type
0 : Normally open contact (*)
1 : Normally closed contact
The contact opens at the power OFF regardless of this setting.
6115
1
Discrete input function
0 : Undefined (*)
1 : Update demand
2 : Reset energy count
3 : Reset alarm trip
4 : Tariff setting for Energy count (ON: high tariff)