53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 26 / 52
SET VALUE.
ID
PARAMETER
30
31
32
THD I1
THD I2
THD I3
Current total harmonic distortion, Line 1
Current total harmonic distortion, Line 2
Current total harmonic distortion, Line 3
33
THD IN
Neutral current total harmonic distortion
34
35
36
THD U12
THD U23
THD U31
Delta voltage total harmonic distortion, 1 – 2
Delta voltage total harmonic distortion, 2 – 3
Delta voltage total harmonic distortion, 3 – 1
37
38
39
THD U1N
THD U2N
THD U3N
Phase voltage total harmonic distortion, Phase 1
Phase voltage total harmonic distortion, Phase 2
Phase voltage total harmonic distortion, Phase 3
43
T-Q
Reactive power for bidirectional current
44
T-PF
Power factor for bidirectional current
■
∑ VIEW DISPLAY PARAMETER SETTING
2.00
ADDR.
WORD
PARAMETER
7393
1
∑1, Line 1 - Measurand to be assigned - Refer to the table below.
7394
1
∑1, Line 2 - Measurand to be assigned - Refer to the table below.
7395
1
∑1, Line 3 - Measurand to be assigned - Refer to the table below.
7397
1
∑2, Line 1 - Measurand to be assigned - Refer to the table below.
7398
1
∑2, Line 2 - Measurand to be assigned - Refer to the table below.
7399
1
∑2, Line 3 - Measurand to be assigned - Refer to the table below.
7401
1
∑3, Line 1 - Measurand to be assigned - Refer to the table below.
7402
1
∑3, Line 2 - Measurand to be assigned - Refer to the table below.
7403
1
∑3, Line 3 - Measurand to be assigned - Refer to the table below.
7405
1
∑4, Line 1 - Measurand to be assigned - Refer to the table below.
7406
1
∑4, Line 2 - Measurand to be assigned - Refer to the table below.
7407
1
∑4, Line 3 - Measurand to be assigned - Refer to the table below.
■
∑ VIEW MEASURANDS AND SELECTABLE POSITIONS (lines,
✓
= selectable)
2.00
SET VALUE.
ID
PARAMETER
UNIT
LINE 1
LINE 2
LINE 3
0
NULL
Undefined
—
✓
✓
✓
1
I
Current
A
✓
2
U
Voltage
V
✓
3
P
Active power
W
✓
4
Q
Reactive power
var
✓
5
S
Apparent power
VA
✓
6
PF
Power factor
PF
✓
7
F
Frequency
Hz
✓
■
SHORTCUT MENU FUNCTION
2.00
ADDR.
WORD
PARAMETER
7553
1
Resetting alarm trip
0 : Disable
1 : Enable (*)
(*) Factory setting