53U
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6485-B Rev.21 P. 22 / 52
ADDR.
WORD
PARAMETER
UNIT
6511
1
THD U1N thr. THD U3N - Phase voltage total harmonic distortion : Alarm output
0 : Disable (*)
1 : Display only
2 : D discrete output 1
3 : D discrete output 2
4 : D discrete output 3
5 : D discrete output 4
—
6512
1
THD U1N thr. THD U3N - Phase voltage total harmonic distortion : Hysteresis (dead-
band)
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
%/10
6513
1
THD U1N thr. THD U3N - Phase voltage total harmonic distortion : ON delay time
0 to 999 : Seconds
Factory setting : 0
Seconds
6515
2
UT12 thr. UT31 - Phase angle between phase voltages : High setpoint
2.00
Factory setting : 0
°
6517
2
UT12 thr. UT31 - Phase angle between phase voltages : Low setpoint
2.00
Factory setting : 0
°
6519
1
UT12 thr. UT31 - Phase angle between phase voltages : Alarm output
2.00
0 : Disable (*)
1 : Display only
2 : D discrete output 1
3 : D discrete output 2
4 : D discrete output 3
5 : D discrete output 4
—
6520
1
UT12 thr. UT31 - Phase angle between phase voltages : Hysteresis (deadband)
2.00
0 to 999 : Specified value × 0.1 (%)
Factory setting : 0
%/10
6521
1
UT12 thr. UT31 - Phase angle between phase voltages : ON delay time
2.00
0 to 999 : Seconds
Factory setting : 0
Seconds
(*) Factory setting