Appendix
Addresses of MODBUS TCP/IP protocol (MAGDOS LP-Net)
66
Solenoid-Diaphragm Dosing Pump
MAGDOS LP
© Lutz-Jesco GmbH 2014
Operating Instructions
BA-10231-02-V03
53
1
r
Number
Reporting of last event
0300
hex
+
0000
hex
: Not an error
0001
hex
: Container at minimum level
0002
hex
: Container at empty level
0005
hex
: Flowcon/dosing control error
0006
hex
: Release input stop
0007
hex
: Diaphragm rupture
0008
hex
: 0/4 … 20mA input error
0009
hex
: Manual stop
000A
hex
: General unit error
000B
hex
: Over temperature/overload
000C
hex
: Offline/transfer error
000D
hex
: RTC error/battery error
000E
hex
: Stroke buffer maximum
000E
hex
: Voltage error
0010
hex
: List of messages deleted
54
-
55
1
r
Number
Current on 0/4 … 20 mA
input
Example: 1814 = "18.14 mA"
56
1
r/w
Number
Specified delivery capacity %
Example: 830 = "83.0%" (applies to the manual mode and batch
mode operating modes)
57
1
r/w
Number
Countdown specification
With batch mode, start amount specified under No. of strokes
58
1
r/w
Number
Current countdown
In batch mode, (Type Start/Stop or Ext. Start), the number of
strokes that still have to be carried out. Example: 1200 = "20
strokes"
With batch mode (interval or timer type) the strokes that have still
to be carried out at 100 % delivery capacity. You must multiply
the value by the delivery capacity (address 56).
59-60
2
r
Number
Stroke counter
Number of strokes that have been carried out up to now
61 - 62
-
63
1
r
Number
Strokes/min. max.
Maximum output after factory calibration
64
1
r/w
Number
Strokes/min. calibrated
Output after calibration by customer
65
1
r/w
Number
Specify the running time
Running time of the batch dosing in min
66
1
r/w
Number
Start the batch
Number "1" starts the batch dosing
Address
Word
r/w
Type
Field
Description
Table 17-1: Addresses of MODBUS TCP/IP protocol (MAGDOS LP-Net)