Appendix
Addresses of MODBUS TCP/IP protocol (MAGDOS LP-Net)
65
© Lutz-Jesco GmbH 2014
Subject to technical changes.
140327
Solenoid-Diaphragm Dosing Pump
MAGDOS LP
Operating Instructions
BA-10231-02-V03
17 Appendix
17.1 Addresses of MODBUS TCP/IP protocol (MAGDOS LP-Net)
Address
Word
r/w
Type
Field
Description
0 - 3
-
4
1
r
Number
Model
0300
hex
: LP 05
0301
hex
: LP 1
0302
hex
: LP 2
0303
hex
: LP 4
0304
hex
: LP 6
0305
hex
: LP 10
0306
hex
: LP 15
5
1
r
Number
Nominal delivery capacity
Example: 380 = "3,8 l/h"
6 - 7
2
r
Text
Software Version:
Example: "1.20"
8 - 9
-
10
1
r
Number
Operating hours
11
1
r
Number
Operating seconds
12
1
r
Number
Modbus address
= 1
13 - 14
2
r
Number
MAC address
15
-
16 - 17
2
r
Number
IP address
18
1
r
Number
Watchdog
Example: 12300 = "12,3 s", max. 15000
19 - 29
-
30 - 35
6
r/w
Text
Device names
Max. of 12 characters
36 - 39
-
40 - 45
6
r
Text
Serial number
Max. of 11 characters
46 - 49
-
50
1
r
Number
Operating mode
0000
hex
: Manual operation
0001
hex
: Analog input
0002
hex
: Pulse input
0003
hex
: Batch mode
0004
hex
: Network mode
51
1
r/w
Number
Stroke frequency control
variable
0 ... 1000
The watchdog is reset to 0 by writing the control variable.
52
1
r
Number
Actual delivery rate
Example: 240 = "2,4 l/h"
Table 17-1: Addresses of MODBUS TCP/IP protocol (MAGDOS LP-Net)
Содержание MAGDOS LP
Страница 2: ......
Страница 70: ...70 Solenoid Diaphragm Dosing Pump MAGDOS LP Lutz Jesco GmbH 2014 Operating Instructions BA 10231 02 V03 Notes ...
Страница 75: ......