Step 5: Contact Closure Inputs:
Emergency and CCI
WARNING! Danger of Shock. May result in serious
injury or death.
DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker before wiring
or servicing the
Energi Savr Node
unit.
If line voltage shield is removed, the unit must be accessed
by a certified electrician, following local codes.
• Both Contact Closure Inputs’ (Emergency and CCI) wiring is
NEC
®
Class 2/PELV. Follow all applicable national and local
codes for proper circuit separation and protection.
• CCI input must be used with dry contact closure devices.
• If the Emergency input is open, the
Energi Savr Node
unit will
enter Emergency Mode, which will turn on all loads and disable
local zone control and control from sensors and QS devices.
Note:
The
Energi Savr Node
unit will default to Emergency Mode
if the Emergency input is left open. If no Emergency contact
input is required, please leave the wire jumper in the Emergency
input terminals.
Contact Closure Wiring
CCI – CONTACT CLOSURE INPUT
COM – COMMON
COM – COMMON
EMERG – EMERGENCY
Contact Closure Wiring:
• 20 AWG to 12 AWG
(0.5 mm
2
to 4.0 mm
2
)
• Strip length: 1/4 in (6 mm)
• Torque: 5 in-lbs (0.5 N
•
m)