Energi Savr Node
TM
0-10V / SoftSwitch
®
Installation Guide
Lutron
®
|
3
Energi Savr Node
TM
0-10 V / SoftSwitch
®
|
Installation Guide
Step-by-step installation instructions
Step 1: Mounting the unit
Note: Mount the
Energi Savr Node
unit
in a position where it can
be easily located and accessed if service or troubleshooting is
necessary.
• Remove metal outer panel cover.
• Remove internal plastic line voltage shield.
• For indoor use only!
• NEMA, Type 1 enclosure, IP20.
• Mount panel where audible noise is acceptable (internal relays
click).
• Mount panel so line voltage wiring is at least 6 ft (1.8 m) from
audio or electronic equipment and associated wiring (prevents
radio frequency interference).
• Install in accordance with all national and local electrical codes.
Mechanical Dimensions
All dimensions shown as inches (mm)
Control Power Wiring
11.25
(285.75)
10.25
(260.35)
0.20 (5.16) dia.
Typical 4 places
1.00
(25.40)
1.5
(38.10)
1.22
(30.99)
1.66
(42.16)
1.31
(33.27)
0.88
(22.35)
1.22
(30.99)
1.62
(41.15)
9.25
(234.95)
7.50
(190.50)
3.16
(80.26)
13.25
(336.55)
Step 2: Control power wiring
The
Energi Savr Node
unit
operates at 120-277 V . Use the
following instructions to wire line voltage to power the
Energi
Savr Node
unit.
WARNING! Danger of Shock. May result in serious
injury or death.
DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker before wiring
or servicing the
Energi Savr Node
unit.
Buttons and LEDs in the unit are used for programming
and troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
1. Remove metal outer panel cover.
2. Remove internal plastic line voltage shield.
3. Use 14 AWG to 12 AWG (2.5 mm
2
to 4.0 mm
2
) conductors (de-
pending on breaker rating) to feed the control power wiring. The
Energi Savr Node
unit draws less than 0.5 A.
4. Wire the line voltage cables to the terminals labeled H (Hot) and
N (Neutral). A two-position terminal block is provided.
5. The
Energi Savr Node
unit
is grounded through the ground bar.
Attach the ground wire.
6. Reinstall internal plastic line voltage shield.
7. Turn on the circuit breaker to power up the
Energi Savr Node
unit. The ‘Wired’ LED on the
Energi Savr Node
unit will light
when properly energized. If the LED does not light, turn off
power, then check the control power wiring.
8. Turn power off.
Control Power Wiring:
• Two (2) 14 AWG to 12 AWG
(2.5 mm
2
to 4.0 mm
2
)
• Strip length: 3/8 in (8.5 mm)
• Torque: 7 in-(0.79 N
•
m)
Neutral (N)
Hot (H)
Ground
Line Voltage Shield