Energi Savr Node
TM
0-10V / SoftSwitch
®
Installation Guide
Lutron
®
|
11
Energi Savr Node
TM
0-10 V / SoftSwitch
®
|
Installation Guide
Normal Operation
In normal operation, the following buttons allow the user to ac-
cess certain basic functions:
1.
(Raise)
— QSN-4T16-S: Raises zone light level in 1% incre-
ments from 0-100%.
— QSN-4S16-S: Turns selected zone on.
2.
(Lower)
— QSN-4T16-S: Decreases zone light level in 1%
decrements from 100-0%.
— QSN-4S16-S: Turns selected zone off.
Note:
On QSN-4T16-S only - For any zone, simultaneously
pressing and holding the and buttons will toggle the
zone between high end and low end.
QS Link Input(s) Setup
seeTouch
QS Wallstation or GRAFIK Eye
®
QS unit - Scenes
and Off
Assigns a
seeTouch
QS Wallstation or
GRAFIK Eye
QS unit to any
Energi Savr Node
unit zone on the QS link.
1. To assign a
seeTouch
QS Wallstation or
GRAFIK Eye
QS unit to
an
Energi Savr Node
unit(s), simultaneously press and hold the
top and bottom buttons on the wallstation or
GRAFIK Eye
QS
unit for 3 seconds. The QS link enters Programming Mode. The
sensor LEDs on the
Energi Savr Node
unit(s) will flash sequen-
tially through each input and group.
2. To assign or un-assign desired zone(s) to a wallstation, simul-
taneously press and hold the the and buttons for the desired
zone. A blinking ‘Zone’ LED indicates an assigned zone.
3. To exit Programming Mode, simultaneously press and hold the
the top and bottom buttons on the wallstation or
GRAFIK Eye
QS
unit for 3 seconds.
Note:
For more advanced programming information, refer to the
online Programming Guide at:
www.lutron.com/softswitchenergisavrnode
Using LEDs to troubleshoot
WARNING! Danger of Shock. May result in serious
injury or death.
DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker before wiring
or servicing the
Energi Savr Node
unit.
Buttons and LEDs in the unit are used for programming and
troubleshooting.
If line voltage shield is removed, the unit
must be accessed by a certified electrician, following local
codes.
LED
LED Behavior
Description
Occ
(Occupancy
Sensor)
Continuous On
Sensor detects Vacancy
1 flash per second
Sensor detects
Occupancy
Off
Sensor never detected
Photo
(Daylight
Sensor )
Continuous On
Sensor is detected
Flashing
Sensor information
transmitting on the QS link
Off
Sensor never detected/
sensor not seeing light
IR
(Infrared
Receiver)
Continuous On
Receiver is detected
Flashing
IR button press detected
Off
Receiver never detected
Switch
(NEC
®
Class 2
Switch)
Continuous On
Switch detected/open
Flashing
Switch button press
detected
Off
Switch never detected
CCI
(Contact Clo-
sure Input)
Continuous On
Contact detected/open
Flashing
Contact closed
Off
Contact never detected
Emerg
(Emergency
Contact Clo-
sure Input)
Continuous On
Normal operation/Contact
Closed/Jumpered
Rapid flash
Emergency Mode/Contact
Open/Jumper missing
QS Link
On/Flashing
Device transmitting/
receiving on the QS link
3 quick flashes
every 4 seconds
Communication error
Off
Device not transmitting/
receiving on the QS link
Wired
Continuous On
Wired sensor
Zone
Continuous On
Load is on
Off
Load is off