Energi Savr Node
TM
0-10V / SoftSwitch
®
Installation Guide
Lutron
®
|
4
Energi Savr Node
TM
0-10 V / SoftSwitch
®
|
Installation Guide
Step 3: Load wiring
The
Energi Savr Node
unit
operates at 120-277 V . Use the following instructions to wire line voltage loads to the
Energi Savr Node
unit.
WARNING! Danger of Shock. May result in serious injury or death.
DO NOT WIRE WHEN LIVE! Switch off power to all power
feeds via circuit breaker before wiring or servicing the
Energi Savr Node
unit.
The
Energi Savr Node
unit is a feed-through device. This means that each switched output needs the Line and Load wires. THERE IS
NO INTERNAL CONNECTION BETWEEN THE CONTROL POWER TO THE UNIT AND THE SWITCHED OUTPUTS.
Zone Switching:
120-277 V
0-10 V Zones:
(QSN-4T16-S only)
Feed-Through Wiring Example 1 – 4 Circuits, Multiple Feeds
Switched Hot (1B)
Hot F
eed (1A)
Hot F
eed (2A)
Hot F
eed (3A)
Hot F
eed (4A)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
Ground Bar
Neutral Wires
Distribution
Panel
LOAD
LOAD
LOAD
LOAD
0-10 V Wiring (QSN-4T16-S only)
• 20 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
• Strip length: 1/4 in (6 mm)
• Torque: 5 in
-lbs (0.5 N
•
m)
•
Connect only NEC
®
Class 2/PELV circuits or connect
only non-
NEC
Class 2/PELV circuits to 0-10 V zones
1-4.
• 0-10 V zones 1-4 are not isolated from each other.
• Negative (–) terminals are not internally connected
to each other—both positive (+) and negative (–)
connections must be made.
• Follow all national and local codes for separation
requirements.
Load Wiring:
• Two (2) 14 AWG to
12 AWG (2.5 mm
2
to
4.0 mm
2
)
• Strip length: 3/8 in
(8.5 mm)
• Torque: 7 in-lbs
(0.79 N
•
m)
0-10 V Wiring
(QSN-4T16-S only)
Hot
Hot
Hot
Hot
Neutral
Neutral
Neutral
Neutral
Ground
Ground