Energi Savr Node

TM

 0-10V / SoftSwitch

®

 Installation Guide

Lutron

®

  

|

  10

Energi Savr Node

TM

 0-10 V / SoftSwitch

®

 

|

 Installation Guide

Sample application: Out of Box Functionality (requires no commissioning)

Daylight 

Sensor

Daylight 

Sensor

Daylight 

Sensor

Daylight 

Sensor

Zone 3

Zone 1

Zone 2

Zone 4

Room 3

Room 4

Room 1

Room 2

W

indow

W

indow

W

indow

W

indow

Occupancy 

Sensor

Occupancy 

Sensor

Occupancy 

Sensor

Occupancy 

Sensor

Energi Savr 

Node 

unit

Wired 

to input 

group 

3

Wired 

to input 

group 

4

Wired 

to input 

group 

1

Wired 

to input 

group 

2

Out of Box Functionality

This section describes the default functionality that the unit will 
present when first installed.

Inputs (Occupancy, Daylight, IR, and Switch):

• 

Input group 1: controls zone 1.

• 

Input group 2: controls zone 2.

• 

Input group 3: controls zone 3.

• 

Input group 4: controls zone 4.

Occupancy Sensors (Occ)

• Corresponding 

zones will turn on when the occupancy sensor is in 

the occupied state (closed) and off when in the unoccupied state 
(open).

Daylight Sensors (Photo)

• Corresponding 

zones will turn on when light sensed by daylight 

sensor falls below the factory preset level.

• Corresponding 

zones will turn off when light sensed by daylight 

sensor rises above the factory preset level.

• 

QSN-4T16-S only: Corresponding zone light levels will raise or 
lower when light sensed by daylight sensor falls or rises based 
on a factory default setting.

IR Receivers (IR)

• S

ee IR Receiver literature for compatible transmitters.

• Corresponding 

zones respond to on, off, and Scene commands 

from compatible IR transmitters.

• 

QSN-4T16-S only: Corresponding zones respond to Raise and 
Lower commands from compatible IR transmitters.

NEC

®

 Class 2/PELV Dry Contact Closure (Switch)

 • Maintained closure or open toggles corresponding zone(s) 

between preset and off.

Contact Closure Input (CCI)

 • Momentary closure from a normally-open (NO) dry contact 

closure device will result in all zones being turned off.

Emergency Contact Closure Input (Emerg)

• If the Emergency input is open, the 

Energi Savr Node

 

unit will 

enter Emergency Mode, which will turn on all loads and disable 
local zone control and control from sensors and QS devices.

 • When the Emergency input is closed or jumpered, 

Energi Savr 

Node

 

unit zones will return to the settings or levels they were at 

prior to entering Emergency Mode.

seeTouch

®

 QS Wallstations

• All 

seeTouch

 QS lighting wallstations are Scene keypads by 

default.

• QSN-4S16-S only: Scenes 1-16 will turn all the lights on.
• QSN-4T16-S only: Scenes 1-16 will dim lights to the preset 

levels in the table below:

Scene #

Light Level: All Zones

1, 5-16

100%

2

75%

3

50%

4

25%

• Scene Off will turn all the lights off.

Содержание Energi Savr Node QSN-4S16-S

Страница 1: ...re inputs 7 QS link wiring 8 Applications 10 Out of box functionality 10 Normal operation 11 QS link input s setup 11 Troubleshooting 11 Warranty 12 Contact information 12 System Example Programming Guide available at www lutron com softswitchenergisavrnode QS link Control Power 120 277 V 4 Load Input Feeds 120 277 V 4 0 10 V Channels QSN 4T16 S only Emergency Contact Closure Input Contact Closure...

Страница 2: ...rgency contact closure input defaults to Emergency Mode in the absence of a contact closure across the input The QS Link can have up to 100 zones and 100 devices The Energi Savr Node unit counts as 1 device and 4 zones on the QS link In a system with multiple Energi Savr Node units on a QS link a maximum of 100 daylight sensors 100 occupancy sensors 100 IR receivers and 100 Pico wireless controlle...

Страница 3: ...ltage to power the Energi Savr Node unit WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all power feeds via circuit breaker before wiring or servicing the Energi Savr Node unit Buttons and LEDs in the unit are used for programming and troubleshooting If wiring is exposed when accessing buttons and LEDs the unit must be accessed by a certifie...

Страница 4: ...0 10 V Zones QSN 4T16 S only Feed Through Wiring Example 1 4 Circuits Multiple Feeds Switched Hot 1B Hot Feed 1A Hot Feed 2A Hot Feed 3A Hot Feed 4A Switched Hot 2B Switched Hot 3B Switched Hot 4B Ground Bar Neutral Wires Distribution Panel LOAD LOAD LOAD LOAD 0 10 V Wiring QSN 4T16 S only 20 AWG to 12 AWG 0 5 mm2 to 4 0 mm2 Strip length 1 4 in 6 mm Torque 5 in lbs 0 5 N m Connect only NEC Class 2...

Страница 5: ...mm2 to 4 0 mm2 Strip length 1 4 in 6 mm Torque 5 in lbs 0 5 N m Connect only NEC Class 2 PELV circuits or connect only non NEC Class 2 PELV circuits to 0 10 V zones 1 4 0 10 V zones 1 4 are not isolated from each other Negative terminals are not internally connected to each other both positive and negative connections must be made Follow all national and local codes for separation requirements Loa...

Страница 6: ...he input terminals are shown below WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all power feeds via circuit breaker before wiring or servicing the Energi Savr Node unit Buttons and LEDs in the unit are used for programming and troubleshooting If line voltage shield is removed the unit must be accessed by a certified electrician following l...

Страница 7: ...ollow all applicable national and local codes for proper circuit separation and protection CCI input must be used with dry contact closure devices If the Emergency input is open the Energi Savr Node unit will enter Emergency Mode which will turn on all loads and disable local zone control and control from sensors and QS devices Note The Energi Savr Node unit will default to Emergency Mode if the E...

Страница 8: ...shielded from Belden model 9461 Check for compatibility in your area A QS system can have up to 100 zones and 100 devices The Energi Savr Node unit counts as 1 device and up to 4 zones See diagram on the right for QS link wiring 1 Connect terminals 1 3 and 4 to all Energi Savr Node units 2 Each Energi Savr Node unit has its own built in power supply 3 The terminal 2 connection 24 V supplies power ...

Страница 9: ...nstallation Guide Energi Savr Node unit Sivoia QS Shade Sivoia QS Smart Power Panel seeTouch QS Wallstations QS Control Link Sivoia QS Smart Power Panel Sivoia QS Shade seeTouch QS Wallstations Energi Savr Node unit QS Control Link QS Link Wiring continued Daisy chain Wiring Example T tap Wiring Example ...

Страница 10: ... level QSN 4T16 S only Corresponding zone light levels will raise or lower when light sensed by daylight sensor falls or rises based on a factory default setting IR Receivers IR See IR Receiver literature for compatible transmitters Corresponding zones respond to on off and Scene commands from compatible IR transmitters QSN 4T16 S only Corresponding zones respond to Raise and Lower commands from c...

Страница 11: ...it for 3 seconds Note For more advanced programming information refer to the online Programming Guide at www lutron com softswitchenergisavrnode Using LEDs to troubleshoot WARNING Danger of Shock May result in serious injury or death DO NOT WIRE WHEN LIVE Switch off power to all power feeds via circuit breaker before wiring or servicing the Energi Savr Node unit Buttons and LEDs in the unit are us...

Страница 12: ... TO MEET ANY DUTY INCLUDING OF GOOD FAITH OR OF REASONABLE CARE NEGLIGENCE OR ANY OTHER PECUNIARY OR OTHER LOSS WHATSOEVER NOR FOR ANY REPAIR WORK UNDERTAKEN WITHOUT LUTRON S WRITTEN CONSENT ARISING OUT OF OR IN ANY WAY RELATED TO THE INSTALLATION DEINSTALLATION USE OF OR INABILITY TO USE THE UNIT OR OTHERWISE UNDER OR IN CONNECTION WITH ANY PROVISION OF THIS WARRANTY OR ANY AGREEMENT INCORPORATIN...

Отзывы: