2 Installation Guide for CGP2730 Dimming and Switching Subplate
Panel Model Number Guide
CGP2730 (120 V
~
only)
Breakdown:
HWR - P N L S - 8 S - 1 2 0 F T - C G P 2 7 3 0
Feed
Voltage
Feed
Type
Subplate
Type
Prefix
Custom Function
2730
= Subplate designed for retrofitting up
# of Module
locations
Prefix
HWR
= Dimming & Switching Panel Subplate
Module locations and Types
The following module types may be installed in this subplate.
Max 8 modules.
Feed Type/Input Ratings
FT
V
0
2
1
h
g
u
o
h
t
-
d
e
e
F
=
~
Custom
Function
to 8 modules into a LiteTouch
TM
.
MODULE
LOCATION
#1
MODULE
LOCATION
#3
MODULE
LOCATION
#5
MODULE
LOCATION
#7
MODULE
LOCATION
#2
MODULE
LOCATION
#4
MODULE
LOCATION
#6
MODULE
LOCATION
#8
The following Modules can be placed in locations 5 through 8
The following Modules can be placed in locations 1 through 4
Four-Output Dimming (4U) & (4A)
cannot be placed in locations 5
through 8
4U
4A
4A
Four-Output Dimming (4A) cannot be
placed in locations 1 through 4
Output (Load) Ratings/Module Type Rating
4R
64 A total per module (4 circuits/module), 16 A per circuit
4U
16 A total per module (1 circuit/module), 16 A per output,
4 outputs per module
4J
16 A total per module (1 circuit/module), 6 A per output,
4 outputs per module
4M
16 A total per module (1 circuit/module), 5 A per output
(1/4 HP motor, 1 per output), 4 outputs per module
4FSQ 8 A total per module (1 circuit/module), 2 A per output
(single ceiling fan), 4 outputs per module
Four-Circuit Switching Relay (4R)
Four-Output Adaptive Dimming (4J)
Four-Output Motor (4M)
Four-Output Quiet Fan Speed (4FSQ)
Four-Output Dimming (4U)
Four-Circuit Switching Relay (4R)
Four-Output Adaptive Dimming (4J)
Four-Output Motor (4M)
Four-Output Quiet Fan Speed (4FSQ)
WARNING!
Shock hazard.
May result in serious injury or death.
Turn off all power feeding Existing
LiteTouch panel before installing HWR
retrofit devices. More than one disconnect
may be necessary to de-energize panel.
Use lockout/tagout on all disconnected
power feeds.