2.Street lamp Function

When the load is set to Dusk to Dawn or Evening mode, the 

 voltage and the 

Day/Night

delay t

can be set b  IoT, RS485 or bluetooth APP, and the load can be turned on or off by 

the test function during the day charging process.

2.1 

The controller recognizes day and night based on the solar array open circuit voltage. 
This day/night threshold 

voltage

 can be modified according to local light conditions and the solar array 

used. 

Max

-

EU

 

defaults to 5.0/10.0V.

Day/Night threshold

 

setting range: 3.0~10/6.0~20/9.0~30.0/12~40V(Default: 8/16/24/32V)

2.2 Day/Night delay time

In the evening, when the solar array open circuit voltage reaches the setting day/night

 detect voltage

, you 

can adjust the day/night delay time to make the load turn on a little bit later.

Day

/

Night delay time setting range: 0~30min(Default

0min)

2.3

 

Test Function

When the controller is working in 

Dusk to Dawn or Evening

 mode, press the 

MENU

 key for 

3

s to turn on 

the load. Press the 

MENU

 key again or the load turns off automatically after 1 minute.    

           

 

If the controller is operating in 

a

lways on mode, the test function does not work.

3.User-definde Mode

If the load mode is selected 

"

USE

"

, then you can switch on and off the load output manually by 

pressing 

MENU

 shortly.

The default switching state of the load in manual mode can be changed by 

IoT, RS485 or 

bluetooth APP

. At the same time, the output to the load can be turned on or off.

Day/Night threshold

 

ime 

y

Day/Night threshold

 voltage

1.If the controller turns off the load due to low voltage protection

overcurrent 

protection

short-circuit protection or over temperature protection, the load will turn on 

automatically

 

when the controller recovers from protection state.

2.Please note: Pushing the MENU button can still activate the function of the key, even 
during of the above four kinds protection states.

Faults

Reason

Troubleshooting

Battery voltage is too low

Reduce the load, the controller will resume 
work after 1minute.

After the temperature decreases, 
the controller will work normally

Battery voltage is too high

Short Circuit

Over Current

Over temperature

E1

E2

E3

E4

E5

Switch off all loads, remove short circuit, load will be 
reconnected after 1 minute automatically

Check if other sources overcharge  the battery. 
If not, controller is damaged.

Load will be reconnected when battery is recharged

7

.

1

T

roubleshooting

7, Troubleshooting,

 and maintenance

 Protections

Batter y can t 
be charged 
during daytime

'

Battery voltage is abnormal 
at start-up

PV panel fault or reverse 
connection

Check panels and connection wires

Charge or discharge the batter y so that the 
batter y voltage is within the normal 
operating range
(10~15V or 20~30V or 31~42 or 42~62V)

15

6.4 USB interface(Max-EU)

   

Max-EU series

 have two USB interfaces, maximum output 

of 

single USB is 5V 1.5A,  maximum output 

of 

two 

USB is 5V 2A, for charging mobile phones and other smart devices.
   The USB stops output only when the controller is in low voltage protection.   

Содержание Max-E Series

Страница 1: ...User Manual User Manual_Max E series_LA CE Rohs ISO9001 2015 Subject to change without notice Solar Controller 12 24 36 48V 20 30 40 50 60A Max E series 1 03 02 10019 6...

Страница 2: ...ounting Location Requirements 7 5 3 Wiring Specifications 8 5 4 Connection 8 5 5 Grounding 9 6 Operation 10 6 1 LCD Display 10 6 2 Key function 12 6 3 Parameters setting 13 7 Protections Troubleshooti...

Страница 3: ...nstalling operating and monitoring Read it with special care in your own interest and please pay attention to the safety recommendations herein indicated 1 2 The manufacturer shall not be liable for d...

Страница 4: ...s optional Max50 60 48 E Based RS 485 standard Modbus protocol with RJ11 interface to maximize the communication needs of different occasions Max50 60 48 E Full automatic electronic protect function E...

Страница 5: ...3 Dimensions 3 96 62 53 4 5 176 189 5 8 15 12 24V ATUO Solar charge controller 3 1 Max20 30 40 EU...

Страница 6: ...4 Unit mm R2 25 4 4 50 4 50 138 90 187 50 177 88 5 62 50 Max50 60 E Max50 6048 E 3 2 Max50 60 48 E...

Страница 7: ...ollect temperature information Temperature compensation Load Terminals Connected load Battery Terminals Connect the battery Solar module terminals Connected solar modules Heat Sink Dissipate controlle...

Страница 8: ...ogram 3 Real time monitoring of PV voltage PV charging current battery voltage battery current load voltage load current and other system parameters as well as charge controller status 4 Real time aut...

Страница 9: ...hazard that may occur Never install handle with batteries alone Avoid touching or short circuiting wires or terminals Be aware that voltages on given system components terminals or wires can be a mult...

Страница 10: ...is adequate for the PV module operating currents Connections must always be conducted in the sequence as described below 5 3 Wiring Specifications Wiring and installation methods must comply with nati...

Страница 11: ...within the 42 0 to 62 0Vdc If the polarity is correct the LCD on the controller will begin to display those 3rd step Connect the solar module When connecting the PV Module make sure to cover it from i...

Страница 12: ...able LVD Battery current Battery state of charge in Temperature Clear external Bluetooth Device Password Battery type Programmable Load Fault Load current and ampere hours Load voltage Programmable LV...

Страница 13: ...6 1 3 Press OK to browse the interface 6 1 2 The interface automatically cycles in the displayed sequence 11...

Страница 14: ...ll be turned off Setting parameter Load On Off Operating Status Icon Description Low voltage Over voltage Battery level shows empty fault icon display battery frame flashes the LCD screen displays E3...

Страница 15: ...at least 0 6 1 2 1 8 2 4V If it is desired to improve LVD than LVR must improved first 6 3 3 Clear Bluetooth Device Password For device passwords please refer to Bluetooth APP instructions 1 Lithium...

Страница 16: ...12 24 36 48V 10 0 64 0V default 29 4V Charge recovery voltage setting range 12 24V 9 2 31 8V default 14 0V 12 24 36 48V 9 2 63 8V default 28 7V Charging Voltage Parameters Li Note 1 2 Overcharge Reco...

Страница 17: ...to the load can be turned on or off Day Night threshold ime y Day Night threshold voltage 1 If the controller turns off the load due to low voltage protection overcurrent protection short circuit prot...

Страница 18: ...nst battery reverse polarity no damage to the controller Correct the connection to resume normal operation Should there are other energy sources to charge the battery when the battery voltage exceeds...

Страница 19: ...mmon positive 8AWG 10mm 20 50 25 80 0 100 RH IP32 4000m Around oblique line value separately on behalf of 12V and 24V system s value Item System Voltage Max Charging Current Fast Voltage Boost Voltage...

Страница 20: ...10 6V 9 6 31 0V Lithium default 12 0V 55V Lithium Gel AGM and Liquid min 30A Always on Default Street lamp User defind Mode 138 187 5 62 5mm 720g 10mA RS485 RJ11 interface IoT Cyber BT Common Positive...

Страница 21: ...ium default 29 4V 9 2 63 8V Lithium default 28 7V 9 0 60 0V Lithium default 21 0V 9 6 62 0V Lithium default 22 4V 100V Lithium Gel AGM and Liquid min 30A Always on Default Street lamp User defind Mode...

Отзывы: