2.Street lamp Function
When the load is set to Dusk to Dawn or Evening mode, the
voltage and the
Day/Night
delay t
can be set b IoT, RS485 or bluetooth APP, and the load can be turned on or off by
the test function during the day charging process.
2.1
The controller recognizes day and night based on the solar array open circuit voltage.
This day/night threshold
voltage
can be modified according to local light conditions and the solar array
used.
Max
-
EU
defaults to 5.0/10.0V.
Day/Night threshold
setting range: 3.0~10/6.0~20/9.0~30.0/12~40V(Default: 8/16/24/32V)
2.2 Day/Night delay time
In the evening, when the solar array open circuit voltage reaches the setting day/night
detect voltage
, you
can adjust the day/night delay time to make the load turn on a little bit later.
Day
/
Night delay time setting range: 0~30min(Default
:
0min)
2.3
Test Function
When the controller is working in
Dusk to Dawn or Evening
mode, press the
MENU
key for
3
s to turn on
the load. Press the
MENU
key again or the load turns off automatically after 1 minute.
If the controller is operating in
a
lways on mode, the test function does not work.
3.User-definde Mode
①
If the load mode is selected
"
USE
"
, then you can switch on and off the load output manually by
pressing
MENU
shortly.
②
The default switching state of the load in manual mode can be changed by
IoT, RS485 or
bluetooth APP
. At the same time, the output to the load can be turned on or off.
Day/Night threshold
ime
y
Day/Night threshold
voltage
1.If the controller turns off the load due to low voltage protection
、
overcurrent
protection
、
short-circuit protection or over temperature protection, the load will turn on
automatically
when the controller recovers from protection state.
2.Please note: Pushing the MENU button can still activate the function of the key, even
during of the above four kinds protection states.
Faults
Reason
Troubleshooting
Battery voltage is too low
Reduce the load, the controller will resume
work after 1minute.
After the temperature decreases,
the controller will work normally
Battery voltage is too high
Short Circuit
Over Current
Over temperature
E1
E2
E3
E4
E5
Switch off all loads, remove short circuit, load will be
reconnected after 1 minute automatically
Check if other sources overcharge the battery.
If not, controller is damaged.
Load will be reconnected when battery is recharged
7
.
1
T
roubleshooting
7, Troubleshooting,
and maintenance
Protections
Batter y can t
be charged
during daytime
'
Battery voltage is abnormal
at start-up
PV panel fault or reverse
connection
Check panels and connection wires
Charge or discharge the batter y so that the
batter y voltage is within the normal
operating range
(10~15V or 20~30V or 31~42 or 42~62V)
15
6.4 USB interface(Max-EU)
Max-EU series
have two USB interfaces, maximum output
of
single USB is 5V 1.5A, maximum output
of
two
USB is 5V 2A, for charging mobile phones and other smart devices.
The USB stops output only when the controller is in low voltage protection.