background image

Model

 Rated charging
 current

 

 Rated 
discharging
 current

 

Solar wire 
diameter
(mm²/AWG)

Battery wire 
diameter
(mm²/AWG)

Load wire 
diameter
(mm²/AWG)

Max20-EU                        20A                      20A                     5/10                   5/10                   5/10

Max30-EU                        30A                      30A                      6/9                     6/9                     6/9

Max40-EU                        40A                      40A                    10/8                    10/8                   10/8

Max50/5048-E                50A                      30A                    16/5                    16/5                    6/9

Max60/6048-E                60A                      30A                    16/5                    16/5                    6/9

5.4 Connection

We

 

strongly

 

recommend

 

connecting

 

a

 

fuse

 

directly

 

to

 

the

 

battery

 

terminal

 

to

 

protect

 

from

 

any

 

short

 

circuit

 

in

 

the

 

battery

 

circuit

PV

-

modules

 

generate

 

current

 

whenever

 

light

 

shines

 

on

 

them

The

 

generated

 

current

 

is

 

directly

 

proportional

 

to

 

the

 

light

 

intensity

Even

 

low

 

levels

 

of

 

light

will

 

deliver

 

the

 

PV

-

Modules

 

no

 

load

full

 

voltage

It

 

is

 

thus

 

utterly

 

advisable

 

to

 

protect

 

PV

-

modules

 

from

 

any

 

incident

 

light

 

during

 

installation;

 

Never

 

touch

 

uninsulated

 

cables

 (

ends

), 

only

 

use

 

electric

 

insulated

 

tools

and

 

make

 

sure

 

that

 

the

 

wire

 

cross

 

section

 

is

 

adequate

 

for

 

the

 

PV

 

module

 

operating

 

currents

Connections

 

must

 

always

 

be

 

conducted

 

in

 

the

 

sequence

 

as

 

described

 

below

5.3 Wiring Specifications 

Wiring

 

and

 

installation

 

methods

 

must

 

comply

 

with

 

national

 

and

 

local

 

electrical

 

code

/

specifications

.

The

 

wiring

 

specifications

 

of

 

the

 

PV

-

system

 

battery

 

must

 

be

 

selected

 

according

 

to

 

rated

 

currents

Please

 

check

 

following

 

table

 

for

 

wiring

 

specifications

:

!

controller

 

or

 

between

 

the

 

controller

 

and

 

the

 

battery

 

are

 

required

than

 

larger

 

capacity

 

cables

 

must

 

be

 

used

 

to

 

reduce

 

voltage

 

drop

 

and

 

improve

 

system

 

performance

.

The

 

indicated

 

cable

/

wire

 

sizes are

 

for

 

reference

 

only

If

 

longer

 

runs

 

between

 

the

 

PV

 

array

 

and

 

the

 

WARNING: 

The

 

PV

-

module

/

array

 

can

 

produce

 

open

-

circuit

 

voltages

 

in

 

excess

 

of

 

100

 

Vdc

 

when

 

exposed

 

to

 

sunlight

Pay

 

highest

 

attention

 

to

 

this

 

fact.

WARNING: 

Risk

 

of

 

explosion

In

 

case

 

the

 

battery

'

s

 

positive

 

and

 

negative

 

terminals

 

or

 

leads

 

get

 

ever

 

in

 

touch

i

.

e

short

-

circuited

a

 

fire

 

or

 

explosion

 

hazard

 

might

 

get

 

triggered

Always

 

pay

 

maximum

 

when

 

handling

 

batteries

 

and

 

related

 

circuits

.

8

Inverter

 

Relay

Содержание Max-E Series

Страница 1: ...User Manual User Manual_Max E series_LA CE Rohs ISO9001 2015 Subject to change without notice Solar Controller 12 24 36 48V 20 30 40 50 60A Max E series 1 03 02 10019 6...

Страница 2: ...ounting Location Requirements 7 5 3 Wiring Specifications 8 5 4 Connection 8 5 5 Grounding 9 6 Operation 10 6 1 LCD Display 10 6 2 Key function 12 6 3 Parameters setting 13 7 Protections Troubleshooti...

Страница 3: ...nstalling operating and monitoring Read it with special care in your own interest and please pay attention to the safety recommendations herein indicated 1 2 The manufacturer shall not be liable for d...

Страница 4: ...s optional Max50 60 48 E Based RS 485 standard Modbus protocol with RJ11 interface to maximize the communication needs of different occasions Max50 60 48 E Full automatic electronic protect function E...

Страница 5: ...3 Dimensions 3 96 62 53 4 5 176 189 5 8 15 12 24V ATUO Solar charge controller 3 1 Max20 30 40 EU...

Страница 6: ...4 Unit mm R2 25 4 4 50 4 50 138 90 187 50 177 88 5 62 50 Max50 60 E Max50 6048 E 3 2 Max50 60 48 E...

Страница 7: ...ollect temperature information Temperature compensation Load Terminals Connected load Battery Terminals Connect the battery Solar module terminals Connected solar modules Heat Sink Dissipate controlle...

Страница 8: ...ogram 3 Real time monitoring of PV voltage PV charging current battery voltage battery current load voltage load current and other system parameters as well as charge controller status 4 Real time aut...

Страница 9: ...hazard that may occur Never install handle with batteries alone Avoid touching or short circuiting wires or terminals Be aware that voltages on given system components terminals or wires can be a mult...

Страница 10: ...is adequate for the PV module operating currents Connections must always be conducted in the sequence as described below 5 3 Wiring Specifications Wiring and installation methods must comply with nati...

Страница 11: ...within the 42 0 to 62 0Vdc If the polarity is correct the LCD on the controller will begin to display those 3rd step Connect the solar module When connecting the PV Module make sure to cover it from i...

Страница 12: ...able LVD Battery current Battery state of charge in Temperature Clear external Bluetooth Device Password Battery type Programmable Load Fault Load current and ampere hours Load voltage Programmable LV...

Страница 13: ...6 1 3 Press OK to browse the interface 6 1 2 The interface automatically cycles in the displayed sequence 11...

Страница 14: ...ll be turned off Setting parameter Load On Off Operating Status Icon Description Low voltage Over voltage Battery level shows empty fault icon display battery frame flashes the LCD screen displays E3...

Страница 15: ...at least 0 6 1 2 1 8 2 4V If it is desired to improve LVD than LVR must improved first 6 3 3 Clear Bluetooth Device Password For device passwords please refer to Bluetooth APP instructions 1 Lithium...

Страница 16: ...12 24 36 48V 10 0 64 0V default 29 4V Charge recovery voltage setting range 12 24V 9 2 31 8V default 14 0V 12 24 36 48V 9 2 63 8V default 28 7V Charging Voltage Parameters Li Note 1 2 Overcharge Reco...

Страница 17: ...to the load can be turned on or off Day Night threshold ime y Day Night threshold voltage 1 If the controller turns off the load due to low voltage protection overcurrent protection short circuit prot...

Страница 18: ...nst battery reverse polarity no damage to the controller Correct the connection to resume normal operation Should there are other energy sources to charge the battery when the battery voltage exceeds...

Страница 19: ...mmon positive 8AWG 10mm 20 50 25 80 0 100 RH IP32 4000m Around oblique line value separately on behalf of 12V and 24V system s value Item System Voltage Max Charging Current Fast Voltage Boost Voltage...

Страница 20: ...10 6V 9 6 31 0V Lithium default 12 0V 55V Lithium Gel AGM and Liquid min 30A Always on Default Street lamp User defind Mode 138 187 5 62 5mm 720g 10mA RS485 RJ11 interface IoT Cyber BT Common Positive...

Страница 21: ...ium default 29 4V 9 2 63 8V Lithium default 28 7V 9 0 60 0V Lithium default 21 0V 9 6 62 0V Lithium default 22 4V 100V Lithium Gel AGM and Liquid min 30A Always on Default Street lamp User defind Mode...

Отзывы: