Cable connection
............................................................................................................................................................
1
Remove the protection cap by unscrewing the two screws at the
bottom of the protection cap.
............................................................................................................................................................
2
Remove the strain relief by unscrewing the four screws.
............................................................................................................................................................
3
Connect the pre-mounted rack cables of the rack frame or the Stud
Cable Set — DC1006622 to the studs of the PI/100 unit.
............................................................................................................................................................
4
Mount the strain relief. Secure the four screws with a torque of 1 Nm
starting with the two middle screws.
Important! Spare screws are available from the other unused strain
relief.
............................................................................................................................................................
5
Mount the protection cap back in its position.
Power and ground cable installation
Power wiring (PDP - PI/100)
System cabling and final assembly
....................................................................................................................................................................................................................................
4 - 1 4