Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-403
Issue 4 February 1997
Engineering, Planning, and Ordering 3 - 35
Table 3-H: Ordering Guide, H569-403 ECS 600-24-Volt Battery Plant
Group No.
Equipment/Features
1
Provides a battery plant, 208/220/240 volt input, +24-volt, 600-ampere
maximum output (includes controller, two rectifier shelves and charge &
discharge bus bars).
2
Same as Group 1, with a low voltage battery disconnect feature.
4
Provides 100-24-volt SR rectifier.
5
Provides optional microprocessor circuit pack (CP2) for plant controller.
CP2 provides remote/local monitoring and control functions.
7
Same as Group 5 (CP2), with voice response feature.
8
Provides optional datalogger circuit pack (CP3) for plant controller. CP3 is
a data acquisition pack that always requires a CP2 circuit pack.
9
Same as Group 8, with remote termination panel. The remote termination
panel allows external connection to the CP3 circuit pack from outside the
controller.
20
Circuit breaker panel for 10A to 100A breakers.
Items AA-AF Provide Circuit Breakers For Group 20 With These Ampere
Capacities:
AA
10-ampere breaker
AB
20-ampere breaker
AC
30-ampere breaker
AD
45-ampere breaker
AE
60-ampere breaker
AF
100-ampere breaker
41
Provides optional converter shelf assembly equipped with two +24- to
-48-volt dc, 10-ampere converters.
42
Provides optional converter shelf assembly equipped with one +24- to
-48-volt dc, 10-ampere converter.
43
Provides optional meter and fuse panel equipped with (8) 1-30 ampere load
fuses for -48-volt distribution and analog meters for monitoring the total
current and voltage delivered by the converters.
K1
Upgrade kit to add one +24- to -48-volt dc, 10 ampere converter in the field.