Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-403
2 - 2 Product Description
Issue 4 February 1997
Circuit Breakers
Type: KS22010
Available ratings: 10, 20, 30, 45, 60, 100
amperes
18 maximum
Fuses
Type: 74, KS-19870
Available ratings: 1-30 amperes
8 maximum
Temperature
32-122°F (0-50°C)
Altitude
-200 to 13,000 feet (-61 to 3962 meters)
For altitudes of 5000 to 13,000 feet,
derate maximum temperature by 3.6°F
per 1000 feet above 5000 feet.
For altitudes of 1524 to 3962 meters,
derate maximum temperature by 0.656°C
per 100 meters above 1524 meters.
Framework
Type: 7-foot Central Office Framework
(standard 26-inch width)
Vertical mounting centers:1.00 inch (25
mm)
Horizontal mounting centers: 24.32
inches (618 mm)
Dimensions
Height: 84 inches (2134 mm)
Width: 26 inches (660 mm)
Depth: 18.0 inches (457 mm)
Weight
(Includes 6 rectifiers): 450 pounds (204
kilograms)
Earthquake
(See Note 1)
Heat Dissipation
Full load: 3254 watts (11,093
BTU/hr)(See Note 2)
Half load: 1640 watts (5590 BTU/hr)
Rectifier, full load: 538 watts (1834
BTU/hr)
Controller, basic and options: 26 watts
(89 BTU/hr)
Converter, full load: 135 watts (460
BTU/hr)
Humidity rating
10% to 95% noncondensing
Table 2-A: Lineage
®
2000 Battery Plant Specifications
(Model H569-403)