3-12 Issue 9 October 1998
363-206-204
Equipment and Front Access Cable Installation
Procedure
1. Install the interbay DS1 cables (Table 3-1) and connect them to the front
access DS1 cables.
2. Route the DS1 cables out of the bay, stacking cables as shown in Figure
3-2.
!
CAUTION:
The DS1 cables are required to have a minimum length of 30 feet.
3. Remove the slack and cut the cables to the desired length at the DSX-1.
4. Tie cables to the bay cable brackets.
5. Referring to Table 3-5, carefully observe color codes and wire-wrap the
cables at the DSX-1.
DS3/EC-1 Cable Installation -Front
Access
Description
The DS3/EC-1 front access interbay cables are installed (if required) in the same
manner as the DS3/EC-1 rear access cables, except that they connect to the front
access cables instead of the backplane.
Follow the "DS3/EC-1 Cable Installation - Rear Access" in the "Equipment and
Rear Access Cable Installation" section (see note). The cables should be routed
out of the bay, stacking the cables as shown in Figure 3-2.
NOTE
:
Cables to the BBG19 DS3 circuit pack will be connected to the front of the
circuit pack after circuit pack installation.
NOTE
:
Where the procedure states "connect to backplane" the connection should
be made to the "front access cables" instead, which in turn is connected to
the backplane.
Содержание DDM-2000 OC-3
Страница 4: ...Issue 9 October 1998 363 206 204 Lucent Technologies ...
Страница 9: ...363 206 204 Issue 9 October 1998 Lucent Technologies ...
Страница 10: ...Issue 9 October 1998 363 206 204 Lucent Technologies ...
Страница 24: ...xxiv Issue 9 October 1998 363 206 204 ...
Страница 32: ...xxxii Issue 9 October 1998 363 206 204 ...
Страница 34: ...xxxiv Issue 9 October 1998 363 206 204 ...
Страница 58: ...1 ii Issue 9 October 1998 363 206 204 ...
Страница 74: ...2 iv Issue 9 October 1998 363 206 204 ...
Страница 143: ...363 206 204 Equipment and Rear Access Cable Installation Issue 9 October 1998 2 69 Figure 2 19 RJ 45 Plug and Face ...
Страница 144: ...2 70 Issue 9 October 1998 363 206 204 Equipment and Rear Access Cable Installation ...
Страница 192: ...3 46 Issue 9 October 1998 363 206 204 Equipment and Front Access Cable Installation ...
Страница 304: ...6 30 Issue 9 October 1998 363 206 204 Release 7 Installation Tests ...
Страница 330: ...7 24 Issue 9 October 1998 363 206 204 Release 8 Installation Tests ...
Страница 362: ...8 30 Issue 9 October 1998 363 206 204 Releases 9 and 11 Installation Tests Figure 8 2 DDM 2000 User Panel ...
Страница 395: ...363 206 204 Release 13 TARP Installation Tests Issue 9 October 1998 9 29 Figure 9 2 DDM 2000 User Panel ...
Страница 398: ...9 32 Issue 9 October 1998 363 206 204 Release 13 TARP Installation Tests ...
Страница 426: ...11 ii Issue 9 October 1998 363 206 204 ...
Страница 492: ...IN 14 Issue 9 October 1998 ...