XGB Analog edition manual
15 - 28
Indication contents of PID STATE
Item
Indication
Flag name
Contents
ALARM
16#0001
PV_MIN_MAX_ALM
Current value exceeds range of maximum, minimum
value
16#0002
PID_SCANTIME_AL
M
Operation cycle is too short.
16#0003
PID_dPV_WARN
Variation of current value of this PID cycle exceeds the
current value variation limit.
16#0004
PID_dMV_WARN
Variation of manipulated value of this PID cycle exceeds
the manipulated value variation limit.
16#0005
PID_MV_MAX_WAR
N
Manipulated value of this PID cycle exceeds maximum
manipulated value.
16#0006
PID_MV_MIN_WAR
N
Manipulated value of this PID cycle is smaller than
minimum manipulated value.
ERROR
16#0100
MV_MIN_MAX_ERR
Maximum manipulated value is set to be smaller than
minimum manipulated value.
16#0200
PV_MIN_MAX_ERR
Maximum current value is set to be smaller than current
manipulated value.
16#0300
PWM_PERIOD_ER
R
PWM output cycle is set to be smaller than 100(10ms).
16#0400
SV_RANGE_ERR
In case of forward operation, set value at start of auto-
tuning is smaller than current value. In case of reverse
operation, set value at start of auto-tuning is larger than
current value.
16#0500
PWM_ADDRESS_E
RR
PWM
output
is
set
as
contact
point
other
than %QX0.0.0~0.0.31.
16#0600
P_GAIN_SET_ERR
Proportional constant is set to be smaller than 0.
16#0700
I_TIME_SET_ERR
Integral constant is set to be smaller than 0
16#0800
D_TIME_SET_ERR
Differential constant is set to be smaller than 0
16#0900
CONTROL_MODE_
ERR
Control mode is other than P, PI, PD and PID.
16#0B00
PID_PERIOD_ERR;
PIC operation cycle is set to be smaller than 100(10ms)
16#0C00
HBD_WRONG_DIR
In combined operation, directional parameter of forward
operation loop is set as reverse operation or directional
parameter of reverse operation loop is set as forward
operation
16#0D00
HBD_SV_NOT_MAT
CH
In combined operation, set values of two loops are different
16#0E00
LOOP_EXCEED
PID LOOP number is larger 15
Содержание XGB Series
Страница 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Страница 72: ...XGB Analog edition manual 2 38 ...
Страница 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Страница 134: ...Chapter 4 RTD Input Module XBF RD04A XBF RD01A 4 Program example using PUT GET function block inn case of IEC 4 27 ...
Страница 340: ...XGB Analog edition manual e Select View Variable Comments Variable and comment both are displayed 9 20 ...
Страница 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Страница 494: ...Chapter 13 Analog Input Module XBF AD04C 4 Select View Device Comments Devices and comments are both displayed 13 33 ...
Страница 495: ...XGB Analog edition manual 5 Select View Variables Comments Variables and comments are both displayed 13 34 ...
Страница 546: ...XGB Analog edition manual 4 Program example using PUT GET instruction in case of IEC type 14 38 ...
Страница 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Страница 597: ...XGB Analog edition manual 15 48 d In case of IEC type example program In case of IEC type the following program is used ...
Страница 607: ...Appendix 2 Thermo electromotive force and compensating force Appendix 2 2 Type T Type R unit unit ...
Страница 611: ...Appendix 3 Appendix 3 1 Appendix 3 Dimension 1 Dimension of XBF AD04A Unit mm 2 Dimension of XBF DV04A DV04C Unit mm ...
Страница 613: ...Appendix 3 Appendix 3 3 5 Dimension of XBF TC04S Unit mm 6 Dimension of XBF AH04A Unit mm V I XBF AH04A ...
Страница 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Страница 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...
Страница 616: ...Appendix 3 Appendix 3 6 11 Dimension of XBO RD01A Unit mm 12 Dimension of XBO TC02A Unit mm ...