Chapter 4 RTD Input Module (XBF-RD04A, XBF-RD01A)
4.15 Configuration and Function of Internal Memory
Here describes configuration and function of internal memory.
4.15.1 Data I/O area of RTD input module
Data I/O area of RTD input module is as shown below.
Area
(‘S’, ‘H’ type)
Area
(IEC type)
Details
Content
R/W
U0x.00.0
U0x.00.F
%UX0.x.0
%UX0.x.15
Module ERROR flag
Module READY flag
0 Bit On(1): module error
F(15) Bit On(1): module normal
R
U0x.01.0
U0x.01.1
U0x.01.2
U0x.01.3
%UX0.x.16
%UX0.x.17
%UX0.x.18
%UX0.x.19
CH0 Run flag
CH1 Run flag
CH2 Run flag
CH3 Run flag
Bit On(1): channel run
Bit Off(0): channel stop
R
U0x.01.4
U0x.01.5
U0x.01.6
U0x.01.7
%UX0.x.20
%UX0.x.21
%UX0.x.22
%UX0.x.23
CH0 Disconnection flag
CH1 Disconnection flag
CH2 Disconnection flag
CH3 Disconnection flag
Bit On(1): Disconnection
Bit Off(0): Normal
R
U0x.04
%UW0.x.4
CH0 digital output
value
Temperature value ×10
R
U0x.05
%UW0.x.5
CH1 digital output
value
−
R
U0x.06
%UW0.x.6
CH2 digital output
value
−
R
U0x.07
%UW0.x.7
CH3 digital output
value
−
R
U0x.08
%UW0.x.8
CH0 scaling value
0 ~ 4000
R
U0x.09
%UW0.x.9
CH1 scaling value
−
R
U0x.10
%UW0.x.10
CH2 scaling value
−
R
U0x.11
%UW0.x.11
CH3 scaling value
−
R
※
In the device assigned, x stands for the slot no. on which module is installed.
(1) Module ready/channel error information ( ( ) means device name of IEC type)
(a) U0x.00.F (%UX0.x.15): It will be ON when PLC CPU is powered or reset with A/D conversion
ready to process A/D conversion.
(b) U0x.00.0 ~ U0x.00.3 (%UW0.x.0~%UW0.x.3): It is a flag to display the error status of A/D
conversion module.
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10
Bit9
Bit8
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
R
eady
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Erro
r
Error status
Bit On (1): error, Bit Off (0): normal
U0x.00
Module READY
Bit On (1): normal, Bit Off (0): error
(%UW0.x.0)
4 - 21
Содержание XGB Series
Страница 70: ...XGB Analog edition manual 2 36 Program in case of IEC type ...
Страница 72: ...XGB Analog edition manual 2 38 ...
Страница 73: ...Chapter 2 Analog Input Module XBF AD04A 2 39 Program in case of IEC type ...
Страница 134: ...Chapter 4 RTD Input Module XBF RD04A XBF RD01A 4 Program example using PUT GET function block inn case of IEC 4 27 ...
Страница 340: ...XGB Analog edition manual e Select View Variable Comments Variable and comment both are displayed 9 20 ...
Страница 491: ...XGB Analog edition manual 4 Click Yes 5 As shown below the variables are registered 13 30 ...
Страница 494: ...Chapter 13 Analog Input Module XBF AD04C 4 Select View Device Comments Devices and comments are both displayed 13 33 ...
Страница 495: ...XGB Analog edition manual 5 Select View Variables Comments Variables and comments are both displayed 13 34 ...
Страница 546: ...XGB Analog edition manual 4 Program example using PUT GET instruction in case of IEC type 14 38 ...
Страница 581: ...XGB Analog edition manual 15 32 In case of IEC type APM_WRT funcion block is used ...
Страница 597: ...XGB Analog edition manual 15 48 d In case of IEC type example program In case of IEC type the following program is used ...
Страница 607: ...Appendix 2 Thermo electromotive force and compensating force Appendix 2 2 Type T Type R unit unit ...
Страница 611: ...Appendix 3 Appendix 3 1 Appendix 3 Dimension 1 Dimension of XBF AD04A Unit mm 2 Dimension of XBF DV04A DV04C Unit mm ...
Страница 613: ...Appendix 3 Appendix 3 3 5 Dimension of XBF TC04S Unit mm 6 Dimension of XBF AH04A Unit mm V I XBF AH04A ...
Страница 614: ...Appendix 3 Appendix 3 4 7 Dimension of XBF AD08A Unit mm 8 Dimension of XBO AD02A Unit mm ...
Страница 615: ...Appendix 3 Appendix 3 5 9 Dimension of XBO DA02A Unit mm 10 Dimension of XBO AH02A Unit mm ...