Chapter 5 Internal Memory & I/O Signals
5-2
5.1.2 Details & Data Configuration
1) Count mode setting
(CH0: 0 address, CH1: 25 address)
Setting value(Dec)
Details
0 Linear
count
1 Ring
count
2) Pulse input mode setting
(CH0: 1 address, CH1: 26 address)
Setting value(Dec)
Details
0 2-phase
1-multiplication
1 2-phase
2-multiplication
2 2-phase
4-multiplication
3 CW
/
CCW
4 1-phase,
1-input,
1-multiplication
5 1-phase,
1-input,
2-multiplication
6 1-phase,
2-input,
1-multiplication
7 1-phase,
2-input,
2-multiplication
3)
Comparison output types
(CH0: 8, 9 address, CH1: 33, 34 address)
Setting value
Details
0
If present value < compared reference value, OUT
□
is On
1
If present value =< compared reference value, OUT
□
is On
2
If present value = compared reference value, OUT
□
is On
3
If present value >= compared reference value, OUT
□
is On
4
If present value > compared reference value, OUT
□
is On
5
If compared minimum value =< present value =< compared maximum value, OUT
□
is On
6
If compared minimum value >= present value, present value >= compared maximum
value, OUT
□
is On
※
Here,
□
means 0 or 1.
4) Auxiliary mode setting
(CH0: 18 address, CH1: 43 address)
Setting value(Dec)
Details
0
Auxiliary mode is not used
1 Count
Clear
2 Count
Latch
3 Sampling
Count
4 Input
Frequency
Measure
5 Revolution/Unit
time
6 Count
Disable
5) Frequency
mode
setting
(CH0: 21 address, CH1: 46 address)
Setting value(Dec)
Details
0
1 Hz unit displayed
1
10 Hz unit displayed
2
100 Hz unit displayed
3
1000 Hz unit displayed ( = 1kHz )
6) Output status setting at PLC stop
(CH0, CH1 common: 50 address)
Setting value(Dec)
Details
0 Output
disable
1
Output kept as it is
Содержание XGF-HD2A