Chapter 8 Troubleshooting
8-1
Chapter 8 Troubleshooting
How to shoot the troubles on the high speed counter module will be described.
8.1 Error
code
Errors of the high speed counter module are as described below.
Error code
(Dec)
CH0
CH1
Description
RDY LED
status
10
Module error (ASIC Reset error)
11
Module error (ASIC Memory error)
12
Module error (ASIC Register error)
Blinks every
0.2 sec.
20
120
Counter type range exceeded
21
121
Pulse input type range exceeded
22
122
Auxiliary Mode type range exceeded
23
123
Sampling Count value range exceeded
24
124
Compared output0 type range exceeded
25
125
Compared output1 type range exceeded
26
126
Preset value exceeded counter range
27
127
Ring counter minimum. value
≥
Ring counter maximum value input
28
128
Compared output 0 minimum value exceeded maximum input range
29
129
Compared output 0 maximum value exceeded maximum input range
30
130
Compared output 0 minimum value > compared output 0 maximum value set
31
131
Compared output 1 minimum value exceeded maximum input range
32
132
Compared output 1 maximum value exceeded maximum input range
33
133
Compared output 1 minimum value > compared output1 maximum value set
34
134
Pulses per revolution range exceeded
35
135
Frequency input mode range exceeded
Blinks every
1 sec
Notes
(1) If the module is normal, RDY LED is On.
(2) If 2 or more errors occur, the module will save the first error code generated, and the displayed error will be first
deleted to let the next error deleted.
(3) In case of serious error which makes RDY LED blinks every 0.2 sec., let power OFF -> ON to delete the error.
(4) In case of slight error which makes RDY LED blinks every 1 sec., the error can be deleted without power OFF ->
ON and the module can keep operating.
(5) In case of slight error which makes RDY LED blinks every 1 sec, the parameter value causing the applicable error
is not set on the module, with the existing parameter value kept as it is.
Содержание XGF-HD2A
Страница 56: ...Chapter 4 Operation Procedures and Monitoring 4 12 ...
Страница 59: ...Chapter 4 Operation Procedures and Monitoring 4 15 ...
Страница 90: ...Chapter 7 Program 7 24 b Scan program of XGI XGR series ...
Страница 127: ...Appendix 3 GM Function Block Conversion Program App3 20 e Auxiliary Function Operating ...