Appendix 3 GM Function Block Conversion Program
App3-6
(2) XGI/XGR auxiliary function setting function block
(a) Auxiliary function type setting
Function Block type
Classification
Variable
name
Type
Contents
REQ BOOL
FB execution
Executed when changing “0->1” ( : Rising
edge)
BASE USINT
Base Number
Base number where HSC module is
equipped
SLOT USINT
Slot Number
Slot number where HSC module is equipped
Ch0
_Fxy_CH0_AUX_MODE 18
MADDR
UINT
CH
Ch1
_Fxy_CH1_AUX_MODE 43
0
Not use
1
Count clear
2
Latch count
3
Sampling count
4
Measure input Freq.
5
Revolution/unit time
Input
DATA DWORD
Auxiliary
function
type
setting
6
Disable count
DONE BOOL
Execution status
If it completes, it outputs 1 and holds. If error
occurs, it outputs 0
Output
STAT USINT
Error status
In case of error, outputs error code
(b) Sampling count setting
Function Block type
Classification
Variable
name
Data type
Contents
REQ BOOL
FB execution
Executed when changing “0->1” ( : Rising
edge)
BASE USINT
Base Number
Base number where HSC module is equipped
SLOT USINT
Slot Number
Slot number where HSC module is equipped
Ch0
_Fxy_CH0_PERIOD 19
MADDR
UINT
CH
Ch1
_Fxy_CH1_PERIOD 44
Input
DATA DWORD
Sampling
setting value
1~65,535(ms)
DONE BOOL
Execution
status
If it completes, it outputs 1 and holds. If error
occurs, it outputs 0
Output
STAT USINT
Error status
In case of error, outputs error code
Содержание XGF-HD2A