Chapter 2 Specifications
2-1
Chapter 2 Specifications
2.1 General Specifications
General specifications of XGT series
No.
Item
Specification
Related specifications
1
Operating
temperature
0
+55
℃∼
℃
-
2
Storage
temperature
-25
+70
℃∼
℃
-
3
Operating
humidity
5 95%RH,
∼
Non-condensing -
4 Storage
humidity
5 95%RH,
∼
Non-condensing -
For discontinuous vibration
-
Frequency Acceleration Amplitude
Number
10
≤
f< 57
㎐
- 0.075mm
57
≤
f
≤
150
㎐
9.8m/s2
(1G)
-
For continuous vibration
Frequency Acceleration Amplitude
10
≤
f< 57
㎐
- 0.035mm
5 Vibration
57
≤
f
≤
150
㎐
4.9m/s2
(0.5G)
-
Each 10 times in X,Y,Z
directions
IEC61131-2
6 Shocks
* Maximum impact acceleration:147
㎨
(15G)
* Authorized time :11
㎳
* Pulse wave : Signal half-wave pulse (Each 3 times in X,Y,Z
directions)
IEC61131-2
Square wave impulse noise
±1,500V
Test specifications of LS
Industrial Systems
Electrostatic discharging
Voltage : 4kV (contact discharging)
IEC 61131-2, IEC 61000-4-2
Radiated electromagnetic field noise
27 ~ 500MHz, 10 V/m
IEC 61131-2, IEC 61000-4-3
Class Power
module
Digital/
Analog I/O
communication interface
7 Impulse
Noise
Fast
Transient
/ burst
noise
Voltage 2kV
1kV
IEC 61131-2,
IEC 61000-4-4
8
Ambient
conditions
No corrosive gas or dust
-
9 Operating
height
2,000m
or
less
-
10
Pollution
degree
2 or less
-
11
Cooling type
Natural air cooling
-
Notes
1) IEC(International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in electric/electronic
fields, publishes international standards and manages applicable estimation system related with.
2) Pollution degree:
An index indicating pollution level of the operating environment which decides insulation performance of the devices. For
instance, Pollution level 2 indicates the state generally that only non-conductive pollution occurs. However, this state contains
temporary conduction due to dew produced.