I305
GB
I
08
18
31100135
5
MECHANICAL DIMENSIONS [mm]
5
43.7
63
35.8
90
44.7
92.5
DIMENSIONI MECCANICHE [mm]
WIRING DIAGRAMS
O1-
O1+
Static output
30VDC 50mA max
L
L
N
O1-
O1+
L
LOAD
N
L
LINE
N
L
L
N
O1+ O1-
L
L
O1+
N
O1-
_
NPN out
+
PNP out
SCHEMI DI COLLEGAMENTO
Code Description Default Range
P-01
Password 0000 0000 - 9999
P-02
Output function 10 PUL / 1000 PUL - 100 PUL -
kWh 10 PUL - 1 PUL - THR
P-03
Threshold measure kW 01=kW - 02=kvar - 03=V
04=A - 05=Hz - 06=kWh Part
07=h Part – 08 kW demand
P-04
ON threshold 100.00 0.00 – 999.99
P-05
ON delay 5 s 0 – 9999 sec.
P-06
OFF threshold 50.00 0.00 – 999.99
P-07
OFF delay 5 s 0 – 9999 sec.
P-08
Hour counter enable OFF OFF-ON-THR
P-09
Enable demand measures OFF OFF-ON
SETUP PARAMETER TABLE
P-01
– If set to 0000 (default) the password protection is disabled.
P-02
– Defines the function of the static output from the following list:
100 PUL …1 PUL
– Static outputs operates as a pulse emitter for active energy count. These
selections define the number of pulses sent for every kWh.
THR
- The static output becomes an alarm threshold for maximum or minimum limit, depending on
values programmed in P-04 and P-06.
If P-04 > P-06, then output activates when the measure defined by P-03 is higher than P-04, end de-
activates when its value becomes less than P-06 (maximum limit with hysteresis.
If P-04 < P-06, then output activates when the measure defined by P-03 is lower than P-04, end activates
when its value becomes higher than P-06 (minimum limit with hysteresis).
P-03
– Selection of measure to compare with thresholds.
P-04 e P-05
– Threshold and delay for output activation. Note: The measurements are updated every 1
second, that means that the variability of this delay is in the range from 0 to + 1 second.
P-06 e P-07
– Threshold and delay for output de-activation.
P-08
– Defines the hor counter operation:
OFF
– hour counter disabled. It is not shown on the display.
ON
– The hour counter is incremented as long as the energy meter is supplied.
THR
– The hour counter is incremented as long as the threshold defined with previous parameter ( P-02,
P-03, P-04 e P-05) is active.
P-09
– Enable of calculation and visualization of active energy demand and max demand.
Codice Descrizione Default Range
P-01
Password 0000 0000 - 9999
P-02
Scelta funzione uscita 10 PUL / 1000 PUL - 100 PUL -
kWh 10 PUL - 1 PUL - THR
P-03
Misura per soglia kW 01=kW - 02=kvar - 03=V
04=A - 05=Hz - 06=kWh Part
07=h Part – 08 kW demand
P-04
Soglia ON 100.00 0.00 – 999.99
P-05
Ritardo soglia ON 5 sec. 0 – 9999 sec.
P-06
Soglia OFF 50.00 0.00 – 999.99
P-07
Ritardo soglia OFF 5 sec. 0 – 9999 sec.
P-08
Abilitazione contaore OFF OFF-ON-THR
P-09
Abilitazione misure demand OFF OFF-ON
TABELLA PARAMETRI DI SETUP
P-01
– Se impostato a 0000 (default) la protezione da password è disabilitata.
P-02
– Definisce la funzione dell’uscita statica programmabile:
100 PUL …1 PUL
– L’uscita statica funziona come emettitore di impulsi per il conteggio dell’energia
attiva. Con queste selezioni si definisce il numero di impulsi per per ogni kWh.
THR
- programma l’uscita come soglia di allarme di massima oppure di minima, a seconda dei valori
impostati in P-04 e P-06.
Se P-04 > P-06, allora l’uscita si attiva con la misura di P-03 > P-04, e si disattiva quando ritorna ad
essere < P-06 (funzione di soglia massima con isteresi).
Se P-04 < P-06, allora l’uscita si attiva con la misura di P-03 < P-04, e si disattiva quando ritorna ad
essere > P-06 (funzione di soglia minima con isteresi).
P-03
– Selezione misura alla quale vengono applicate le soglie.
P-04 e P-05
– Soglia e relativo ritardo per attivazione uscita. Nota: le misure vengono aggiornate ed
integrate 1 volta al secondo, quindi questo ritardo ha una variabilità da 0 a + 1 secondo.
P-06 e P-07
– Come sopra, per disattivazione uscita.
P-08
– Definisce il funzionamento del contaore:
OFF
– Contaore disabilitato, non viene visualizzato.
ON
– Il contaore si incrementa fintanto che l’energy meter è alimentato.
THR
– Il contaore si incrementa fintanto che la soglia definita con i parametri precedenti ( P-02, P-03,
P-04 e P-05) è attivata.
P-09
– Abilitazione misura e visualizzazione potenza attiva integrata attuale e massima (max demand).