7

 

 

 

 
 

M02 – UTILITY

 

UoM

 

Default

 

Range

 

P02.01

 

Language 

 

English English 

Italiano 

P02.02

 

LCD contrast 

% 55 

0-100 

P02.03

 

Display backlighting intensity high 

% 100 

0-100 

P02.04

 

Display backlighting intensity low 

% 30 0-50 

P02.05

 

Low backlight delay 

s 30 

5-600 

P02.06

 

Default page return 

60 

OFF / 10-600 

P02.07

 

Default page 

 

IP MEASUREMENTS 

IP – SYN – EVE … 

P02.08

 

Default sub-page 

 

GR 

IN / HI / LO / AV / GR 

P02.09

 

Display update time 

0,5 

0,1 – 5,0 

 

P02.06 

– If set to OFF, the display always remains on the page where the user left it. If set to a value, after this time the display returns to the page set with P02.07. 

P02.07 

– Abbreviation for the start page on switching on and that the display returns to automatically once the time P02.06 since a button was last pressed has elapsed. 

P02.08 

– Type of sub-page that the display returns to after P02.06 has elapsed. 

 

M03 – PASSWORD

 

UoM

 

Default

 

Range

 

P03.01

 

Enable passwords

 

 

ON

 

OFF-ON

 

P03.02

 

User-level password

 

 

1000

 

0-9999

 

P03.03

 

Advanced-level password

 

 

2000

 

0-9999

 

 

P03.01 

– If set to OFF, password management is disabled.

 

P03.02 

– With P03.01 active, value to specify to activate user-level access. See Password-Protected Access section on page 5.

 

P03.03 

– As P03.02, with reference to Advanced-level access.

 

 

M04 – IP THRESHOLDS

 

UoM

 

Default

 

Range

 

P04.01 

V MAX 59-2 Threshold 

115 

100 - 130 

P04.02 

V MAX 59-1 Threshold 

110 

100 - 120 

P04.03 

V MIN 27-1 Threshold 

% 85 

20 

100 

P04.04 

V MIN 27-2 Threshold 

% 40 

100 

P04.05 

V MAX 59-2 Delay 

0,20 

0,05 - 1,00 

P04.06 

V MAX 59-1 Delay 

3,00 

0,20 - 100,00 

P04.07 

V MIN 27-1 Delay 

0,40 

0,05 - 5,00 

P04.08 

V MIN 27-2 Delay 

0,20 

0,05 - 5,00 

P04.09 

F MAX 81>-2 Threshold 

Hz 

OFF 

OFF / 50,0 - 53,0 

P04.10 

F MAX 81>-1 Threshold 

Hz 

52,50 

OFF / 50,0 – 53,0 

P04.11 

F MIN 81<-1 Threshold 

Hz 

47,50 

OFF / 47,0 - 50,0 

P04.12 

F MIN 81<-2 Threshold 

Hz 

OFF 

OFF / 47,0 - 50,0 

P04.13 

F MAX 81>-2 Delay 

0,10 

0,05 - 5,00 

P04.14 

F MAX 81>-1 Delay 

0,10 

0,05 - 5,00 

P04.15 

F MAX 81<-1 Delay 

4,00 

0,05 - 5,00 

P04.16 

F MIN 81<-2 Delay 

4,00 

0,05 – 5,00 

P04.17 

Backup energizing delay  

0,5 

0,1 – 10,0 

P04.18 Local 

command 

 OFF 

OFF 

– 

ON 

P04.19 

IP Restore delay   

0,08 

0,04 – 300,00 

P04.20 

Threshold type selection for 59-1 

 59AV 

59AV 

59-1 

P04.21 

Threshold ROCOF 81R   
                                                                                 

Hz/s 

OFF 

OFF / 0.01 – 5.00 

P04.22 

Threshold Vector Shift 78 

° 

OFF 

OFF / 1 - 50 

 

P04.01...P04.16, P04.20…P04.22 

– Adjustment of trip thresholds and delay times defined by the SHAMS  DUBAI  -  DRRG  STANDARDS  VERSION  2.0   standard.

 

P04.17 

– Maximum IS opening waiting time, before IS locking is recognised with consequent backup opening command  (with  P01.16  set  to  MODE A, MODE B or MODE C) .

 

P04.18 

– Local control setting via parameter. 

 

P04.19 

– IS restore (reset) time. IS reclosing delay time after all thresholds are ok again. 

I48

GB

 09

 16

 

31

10

02

98

 

Содержание PMVF 60

Страница 1: ...die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweckwidrigem Gebrauch der Vorrichtung bernimmt der Hersteller keine Haftung f r die elektrische Sicherheit Die...

Страница 2: ...Nrail 6units LCDgraphic128x80pixel backlit 4greylevels 4displayandsettingbuttons Voltage measuring inputs three phase neutral Possibilityofoperationinthefollowinglineconfigurations Three phase with ne...

Страница 3: ...inactivestate Threepageswithtripprotectioncountersfollow dividedintototaltripcount voltagethresholdtripcountandfrequencythresholdtripcount The counters can be reset through the Commands Menu Inthepage...

Страница 4: ...AYSIN USE V F THRESHOLDS AND DELAYSCURRENTLY ACTIVE 4 IP TRIP COUNTER ISTRIPCNT BACKUPTRIPCNT 5 VOLTAGETHRESHOLDTRIPCOUNTERS CNT 59 2 CNT 59 1 CNT 27 1 CNT 27 2 6 FREQUENCYTHRESHOLDTRIPCOUNTERS CNT81...

Страница 5: ...enu thenselectthepasswordiconandpressV Thepasswordsettingwindowshownbelowwillappear Pressthe buttonstochangethevalueoftheselecteddigit Pressthe buttontoconfirmthedigitandcycletothenextones Enterthepas...

Страница 6: ...OFF 1 0 20 0 P01 13 LSP delay time 2 s 60 1 3600 P01 14 Automatic LSP restore time min 5 OFF 1 60 P01 15 OUT4 output function Global Alarm OFF IS Backup LSP Global Alarm Threshold 59 1 Threshold 59 2...

Страница 7: ...P04 01 V MAX 59 2 Threshold 115 100 130 P04 02 V MAX 59 1 Threshold 110 100 120 P04 03 V MIN 27 1 Threshold 85 20 100 P04 04 V MIN 27 2 Threshold 40 5 100 P04 05 V MAX 59 2 Delay s 0 20 0 05 1 00 P04...

Страница 8: ...perform occasional operations like resetting measurements counters alarms etc IftheAdvanced levelaccesspasswordwasentered theCommandsMenucanalsobeusedtoperformautomaticoperationsusefulforconfiguringt...

Страница 9: ...alfunction Should this indication occur contact our Customer Service office Tel 39 035 4282422 E mail service LovatoElectric com stating the code indicated CURRENT POWER AND ENERGY MEASUREMENTS IfCTsa...

Страница 10: ...S2terminalsareconnectedtoeachotherinternally The auxiliary IS contact feedback must of necessity be connected InthecaseofmultipleISs theISfeedbackcontactmustbeaparallelconnectionofalltheISs auxiliaryc...

Страница 11: ...22 BACKUP ACTIVATION MODES 14 12 24 22 24 22 24 Note The default backup control mode is A If mode D is selected Backup output mirrors the IS output See parameter P01 16 M01 GENERALMENU on page 6 TERMI...

Страница 12: ...ls 2 4forsupply 4 for voltage measurement Cablecrosssection min max 0 2 4 0mm2 24 12AWG Tightening torque 0 8Nm 7lbin Terminaltype Screw type fixed No ofterminals 6 Cablecrosssection min max 0 2 2 5mm...

Отзывы: