6
–
To change the value of a parameter, select it then press
.
–
If the Advanced-level password has not been entered, it will not be possible to access the modification page, and an access denied message will be displayed.
–
If access has been granted, on the other hand, the modification page will be displayed.
–
In modification mode, the value can be changed with the
▲
and
▼
buttons. Also displayed are a graphic bar indicating the setting range, the minimum and maximum values possible, the previous value and the default value.
–
Pressing
▲
and
▼
simultaneously restores the factory default value.
–
Press
MENU
to return to parameter selection. The value entered is stored.
–
Press
MENU
again to save the changes and exit set-up. The IP resets and resumes normal operation.
ATTENTION:
When restarting following a change to the parameters or commands, the output relays are temporarily de-energised.
–
If no buttons are pressed for 2 minutes, the set-up menu is abandoned automatically and the IP returns to the standard display.
PARAMETER TABLE
M01 - GENERAL
UoM
Default
Range
P01.01
Rated voltage
V
400
400 – 50000
P01.02 VT
primary
V
400
400 – 50000
P01.03 VT
secondary
V 400
50
-
500
P01.04 CT
primary
A OFF
OFF/1-10000
P01.05 CT
secondary
A 5 1-5
P01.06
Voltage connection / control
Three-phase+N / VLL Three-phase+N / VL-L
Three-phase+N / VL-N
Three-phase / VL-L
Single-phase+N / VL-N
P01.07
Rated system power
kW AUT
AUT/
1-10000
P01.08
IS activation delay time after switching on IP
s
4,00
4,00 – 300,00
P01.09
Power imbalance limit LSP control output
OUT3
OFF
OUT1
OUT3
OUT1 + OUT3
P01.10
LSP threshold 1
kW
6,0
OFF / 1.0 – 10.0
P01.11
LSP delay time 1
s 1800
1
-
3600
P01.12
LSP threshold 2
kW
10,0
OFF / 1.0 – 20.0
P01.13
LSP delay time 2
s 60
1
-
3600
P01.14
Automatic LSP restore time
min
5
OFF / 1- 60
P01.15
OUT4 output function
Global
Alarm
OFF
IS Backup
LSP
Global Alarm
Threshold 59-1
Threshold 59-2
Threshold 27-1
Threshold 27-2
Threshold 81>-1
Threshold 81>-2
Threshold 81<-1
Threshold 81<-2
Alarm A01
Alarm A02
Alarm A03
Alarm A04
Alarm A05
Alarm A06
P01.16
Backup control mode
MODE
A
OFF
MODE A
MODE B
MODE C
MODE D
P01.17
Backup control pulse duration
s
3,0
1,0 - 60,0
P01.01
– Rated voltage
P01.02
– Rated voltage of VT primary winding.
P01.03
– V of VT secondary winding.
P01.04
– Rated current of CT primary winding. If CTs are not fitted, leave at OFF. The pages on currents and powers are displayed only when CTs are used.
P01.05
– Current of CT secondary winding.
P01.06
– Type of connection and type of voltage control. Program in line with the wiring.
P01.07
– Rated active power of system. If set to AUT, the value is calculated by multiplying P01.04 * 230 * 3 (phase current * phase voltage * 3 phases).
P01.08
– IS energising delay time after applying voltage to PMVF 60.
P01.09
– LSP protection control output selection – On OUT1 (IS opening), independent on OUT3 or on both.
P01.10-11
– First-level LSP (LSP1) threshold and delay.
P01.12-13
– Second-level LSP (LSP2) threshold and delay.
P01.14
– Defines the automatic restore time after LSP tripping. If set to off, the system can only be restored manually by pressing the
▲ ▼
buttons.
P01.15
– Defines the function of the OUT4 output from those listed. The output is understood to be activated when conditions are normal (threshold not exceeded, alarm not active, etc.).
P01.16
– Defines the backup control mode, according to the logic in the Backup Activation Modes diagram on the final pages of this manual. If the backup is not used, set to OFF.
P01.17
– Backup opening pulse duration, when used in MODE C.
I48
6
GB
09
16
31
10
02
98
Minimum
admitted value
Selected
parameter
New set value
Maximum
admitted value