To  change the value of a parameter, select it then press 

.

 

– 

If the Advanced-level password has not been entered, it will not be possible to access the modification page, and an access denied message will be displayed.

 

– 

If access has been granted, on the other hand, the modification page will be displayed.

 

 

 

 

– 

In modification mode, the value can be changed with the 

 and 

 buttons. Also displayed are a graphic bar indicating the setting range, the minimum and maximum values possible, the previous value and the default value.

 

– 

Pressing 

 and 

 simultaneously restores the factory default value.

 

– 

Press 

MENU 

to return to parameter selection. The value entered is stored.

 

– 

Press 

MENU 

again to save the changes and exit set-up. The IP resets and resumes normal operation.

 

ATTENTION: 

When restarting following a change to the parameters or commands, the output relays are temporarily de-energised.

 

– 

If no buttons are pressed for 2 minutes, the set-up menu is abandoned automatically and the IP returns to the standard display.

 

 

 

PARAMETER TABLE

 

 

M01 - GENERAL

 

UoM

 

Default

 

Range

 

P01.01 

Rated  voltage 

400 

400 – 50000 

P01.02 VT 

primary 

400 

400 – 50000 

P01.03 VT 

secondary 

V 400 

50 

500 

P01.04 CT 

primary 

A OFF 

OFF/1-10000 

P01.05 CT 

secondary 

A 5 1-5 

P01.06 

Voltage connection / control 

 

Three-phase+N / VLL  Three-phase+N / VL-L 

Three-phase+N / VL-N 

Three-phase / VL-L 

Single-phase+N / VL-N 

P01.07 

Rated system power 

kW AUT 

AUT/ 

1-10000 

P01.08 

IS activation delay time after switching on IP 

4,00 

4,00 – 300,00 

P01.09 

Power imbalance limit LSP control output 

 OUT3 

OFF 

OUT1 
OUT3 

OUT1 + OUT3 

P01.10 

LSP threshold 1 

kW 

6,0 

OFF / 1.0 – 10.0 

P01.11 

LSP delay time 1 

s 1800 

3600 

P01.12 

LSP threshold 2 

kW 

10,0 

OFF / 1.0 – 20.0 

P01.13 

LSP delay time 2 

s 60 

3600 

P01.14 

Automatic LSP restore time 

min 

OFF / 1- 60 

P01.15 

OUT4 output function 

 Global 

Alarm 

OFF 

IS Backup 

LSP 

Global Alarm 

Threshold 59-1 

Threshold 59-2 

Threshold 27-1 

Threshold 27-2 

Threshold 81>-1 

Threshold 81>-2 

Threshold 81<-1 

Threshold 81<-2 

Alarm A01 
Alarm A02 
Alarm A03 
Alarm A04 
Alarm A05 
Alarm A06 

P01.16 

Backup control mode 

 MODE 

OFF 

MODE A 
MODE B 
MODE C 
MODE D 

P01.17 

Backup control pulse duration 

3,0 

1,0 - 60,0 

 

P01.01 

– Rated voltage

 

P01.02 

– Rated voltage of VT primary winding. 

 

P01.03 

– V of  VT secondary winding.

 

P01.04 

– Rated current of CT primary winding. If CTs are not fitted, leave at OFF. The pages on currents and powers are displayed only when CTs are used.

 

P01.05 

– Current of CT secondary winding.

 

P01.06 

– Type of connection and type of voltage control. Program in line with the wiring.

 

P01.07 

– Rated active power of system. If set to AUT, the value is calculated by multiplying P01.04 * 230 * 3 (phase current * phase voltage * 3 phases).

 

P01.08 

– IS energising delay time after applying voltage to PMVF  60.

 

P01.09 

– LSP protection control output selection – On OUT1 (IS opening), independent on OUT3 or on both.

 

P01.10-11 

– First-level LSP (LSP1) threshold and delay.

 

P01.12-13 

– Second-level LSP (LSP2) threshold and delay.

 

P01.14 

– Defines the automatic restore time after LSP tripping. If set to off, the system can only be restored manually by pressing the 

▲ ▼

 buttons.

 

P01.15 

– Defines the function of the OUT4 output from those listed. The output is understood to be activated when conditions are normal (threshold not exceeded, alarm not active, etc.).

 

P01.16 

– Defines the backup control mode, according to the logic in the Backup Activation Modes diagram on the final pages of this manual. If the backup is not used, set to OFF.

 

P01.17 

– Backup opening pulse duration, when used in MODE C.

 

I48

GB

 09

 16

 

31

10

02

98

 

Minimum 

admitted value 

Selected 

parameter 

New set value 

Maximum 

admitted value 

Содержание PMVF 60

Страница 1: ...die Spannungszufuhr zu den Messeing ngen trennen und die Stromwandler kurzschlie en Bei zweckwidrigem Gebrauch der Vorrichtung bernimmt der Hersteller keine Haftung f r die elektrische Sicherheit Die...

Страница 2: ...Nrail 6units LCDgraphic128x80pixel backlit 4greylevels 4displayandsettingbuttons Voltage measuring inputs three phase neutral Possibilityofoperationinthefollowinglineconfigurations Three phase with ne...

Страница 3: ...inactivestate Threepageswithtripprotectioncountersfollow dividedintototaltripcount voltagethresholdtripcountandfrequencythresholdtripcount The counters can be reset through the Commands Menu Inthepage...

Страница 4: ...AYSIN USE V F THRESHOLDS AND DELAYSCURRENTLY ACTIVE 4 IP TRIP COUNTER ISTRIPCNT BACKUPTRIPCNT 5 VOLTAGETHRESHOLDTRIPCOUNTERS CNT 59 2 CNT 59 1 CNT 27 1 CNT 27 2 6 FREQUENCYTHRESHOLDTRIPCOUNTERS CNT81...

Страница 5: ...enu thenselectthepasswordiconandpressV Thepasswordsettingwindowshownbelowwillappear Pressthe buttonstochangethevalueoftheselecteddigit Pressthe buttontoconfirmthedigitandcycletothenextones Enterthepas...

Страница 6: ...OFF 1 0 20 0 P01 13 LSP delay time 2 s 60 1 3600 P01 14 Automatic LSP restore time min 5 OFF 1 60 P01 15 OUT4 output function Global Alarm OFF IS Backup LSP Global Alarm Threshold 59 1 Threshold 59 2...

Страница 7: ...P04 01 V MAX 59 2 Threshold 115 100 130 P04 02 V MAX 59 1 Threshold 110 100 120 P04 03 V MIN 27 1 Threshold 85 20 100 P04 04 V MIN 27 2 Threshold 40 5 100 P04 05 V MAX 59 2 Delay s 0 20 0 05 1 00 P04...

Страница 8: ...perform occasional operations like resetting measurements counters alarms etc IftheAdvanced levelaccesspasswordwasentered theCommandsMenucanalsobeusedtoperformautomaticoperationsusefulforconfiguringt...

Страница 9: ...alfunction Should this indication occur contact our Customer Service office Tel 39 035 4282422 E mail service LovatoElectric com stating the code indicated CURRENT POWER AND ENERGY MEASUREMENTS IfCTsa...

Страница 10: ...S2terminalsareconnectedtoeachotherinternally The auxiliary IS contact feedback must of necessity be connected InthecaseofmultipleISs theISfeedbackcontactmustbeaparallelconnectionofalltheISs auxiliaryc...

Страница 11: ...22 BACKUP ACTIVATION MODES 14 12 24 22 24 22 24 Note The default backup control mode is A If mode D is selected Backup output mirrors the IS output See parameter P01 16 M01 GENERALMENU on page 6 TERMI...

Страница 12: ...ls 2 4forsupply 4 for voltage measurement Cablecrosssection min max 0 2 4 0mm2 24 12AWG Tightening torque 0 8Nm 7lbin Terminaltype Screw type fixed No ofterminals 6 Cablecrosssection min max 0 2 2 5mm...

Отзывы: