background image

22

Startup and maintenance

Ensure that the boiler and solar water piping are free of 

 leaks.

If there is an oil lubricated circulator in the system, make 

 

sure it is lubricated as called for by the circulator 

 manufacturer.

Make sure that the heat source is maintained in accordance 

 

with the manufacturer’s instructions.

If a water treatment system is required to keep the water 

 

chemistry within the parameters shown in Table 2A (see 

 

Section 2 - Pre-Installation), make sure that this system is 

 properly 

maintained.

Annual service by a qualified service technician 
should include the following:

  Any procedure required by local codes.

  Verify system pressure. Air venting procedure may require 

 

adding water to bring boiler system up to pressure, typically 

 

12 psig minimum.

  Manually operate T&P relief valve at least once a year.  

 

This will release some hot water. 

 WARNING

Before operating a T&P relief valve, make 
sure no one is in front of or around the T&P 
relief valve discharge piping.  Hot discharge 
water can cause severe personal injury or 
substantial property damage.

 DANGER

Plugging the T&P relief valve or discharge 
piping can cause excessive pressure in the 
water heater, resulting in severe personal 
injury, death, or substantial property 
damage.

 

Move operating lever to open position for a few seconds 

 

and then move it back, allowing it to snap closed. After the 

 

T&P relief valve is operated, if it continues to release water, 

 

close the cold water inlet to the water heater immediately. 

 

Follow the draining instructions, and replace the T&P 

 

relief valve. If the T&P relief valve weeps periodically, it may 

 

be due to thermal expansion. Do not plug the T&P relief 

 

valve or discharge piping. In this case, ensure that the 

 

expansion tank is properly sized and charged to the 

 appropriate 

pressure.

       

Installation & Operation Manual

1.  Make sure the system is free of leaks and that air is 
 

purged from the system.

 

CAUTION

Fix any leaks found before proceeding 
further. Leakage from the heat source and 
solar piping can result in severe damage to 
the system.

2. Many soldering fluxes contain Zinc Chloride which 
 

can cause severe corrosion damage to stainless steel.  After 

  completing all domestic water connections, flush the 
  Strato-Therm+ tank and indirect coil thoroughly before 
 

leaving the installation. This is particularly important if the 

 

Strato-Therm+ will be unused for an extended period of 

 

time after installation. Flush the storage tank by drawing at 

 

least three times its volume from the tank.

3.  Make sure that each zone valve or circulator operates 
 

when, and only when, its thermostat calls for heat.  Let each 

 

zone operate long enough to purge any remaining air from 

 the 

system.

 

Refer to the heat source and solar Installation and Operation 

 

Manuals for additional start-up information.

System startup

Maintenance Schedule

The Lochinvar Strato-Therm+ solar tank is an extremely simple 
device and as such requires very little maintenance.  There are, 
however, several items which should be inspected on an annual 
or as needed basis to ensure a reliable supply of hot water:

  Verify that expansion tank pressure is equal to system 

 pressure.

Содержание Strato-Therm+ STU150

Страница 1: ...sed by a qualified heating installer service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death or subst...

Страница 2: ...ed to personal injury or property damage HAZARD DEFINITIONS 2 PLEASE READ BEFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Tank Shipment 4 Components 4 6 Spherical Heat Exchanger 7 2...

Страница 3: ...gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING NOTICE WARNING WARNING 3 The following chart details...

Страница 4: ...ry if your specific application is not covered in this manual The tank is not intended for use in gravity water heating applications Table 1A Strato Therm Tank Component Materials Component Material T...

Страница 5: ...300 STU257 30 34 1 2 98 83 225 14 5 2875 STU350 36 40 1 2 98 83 325 14 5 3775 STU423 36 40 1 2 115 97 400 16 0 4650 STU504 42 46 1 2 121 103 475 17 0 5475 STU650 48 52 1 2 131 111 625 20 0 7050 STU752...

Страница 6: ...ger Outlet Blue Label Table 1D Tapping Measurements Model A in B in C in D in E in F in G in H in I in O in P in STU150 2 1 4 12 1 4 21 1 4 28 3 4 33 50 3 4 55 1 4 71 76 3 4 3 1 2 3 1 2 STU200 3 1 2 1...

Страница 7: ...l heat exchanger w tank Table 1E Tank with Spherical Measurements Model Spherical Model A in B in STU150 SHX40000 44 1 2 28 STU200 SHX40000 48 1 4 32 STU257 SHX40001 50 1 4 34 STU350 SHX40001 56 1 4 4...

Страница 8: ...led outdoors as it is certified as an indoor appliance and must also be kept vertical on a level surface 2 Table 1C on page 5 shows the weight of all the tanks filled with water Ensure that the locati...

Страница 9: ...sioning must be carried out by a licensed contractor Take appropriate safety measures when carrying out any installation work on the roof and observe all relevant accident prevention regulations It is...

Страница 10: ...URE GAUGE TYPICAL SOLAR PUMP STATION CONTROLLER PRESSURE RELIEF VALVE FILL AND FLUSH VALVE EXPANSION TANK TEMPERATURE GAUGE SPHERICAL HEAT EXCHANGER SOLAR SENSOR IMG00040 Installation Operation Manual...

Страница 11: ...d to allow water to flow in only one direction preventing back flow g Drain required Used to drain the tank for inspection or servicing h Mixing valve required Used to mix hot water with cold water to...

Страница 12: ...ainless steel coil As part of a continuous slow moving loop warm water is circulated directly back into the coil via the lance maintaining tank stratification Reference FIG 4 5 on page 18 for typical...

Страница 13: ...building recirculation system is installed the return water is brought back to the storage tank so as not to disturb the stratification of the Strato Therm Anti scald mixing valves Anti scald valves u...

Страница 14: ...2 8 3 10 7 13 3 14 7 STU200 STU257 STU350 0 1 0 7 1 8 3 2 5 0 7 1 9 5 12 2 15 1 16 7 STU423 0 1 0 8 2 0 3 6 5 6 7 9 10 6 13 6 16 9 18 7 STU504 0 1 0 8 2 1 3 7 5 8 8 2 11 0 14 2 17 7 19 5 STU650 STU75...

Страница 15: ...elief valve must be certified by a nationally recognized testing laboratory that maintains periodic inspection of listed equipment or materials The equipment and materials must meet the requirements f...

Страница 16: ...tly connected to a drain Refer to local codes subject to freezing WARNING Do not install any valve between the relief valve and its connection or on the relief valve discharge piping Improper placemen...

Страница 17: ...cal codes NOTICE IMG00042 SHUTOFF VALVE DOMESTIC HOT WATER CHECK VALVE DOMESTIC COLD WATER RECIRCULATION LINE MIXING VALVE DRAIN CIRCULATION PUMP TEMPERATURE GAUGE SHOCK ARRESTOR BACKUP HEAT SOURCE LO...

Страница 18: ...ired by local codes NOTICE Figure 4 6 Recirculation Piping Flow Over 2 gal min RECIRCULATION LINE CIRCULATION PUMP SHOCK ARRESTOR SHUTOFF VALVE MIXING VALVE TEMPERATURE GAUGE RECIRCULATION LANCE DOMES...

Страница 19: ...ese illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE Figure 4 7 Multiple Tank Domestic Piping BUIL...

Страница 20: ...r flow are more balanced throughout each tank To ensure even charging and discharging of each tank it is recommended that only tanks of the same size are placed in the same manifold It is recommended...

Страница 21: ...CHECK VALVE Y STRAINER TYPICAL EXPANSION TANK FILL VALVE PRESSURE RELIEF VALVE AIR SEPARATOR TEMPERATURE GAUGE BACKUP HEAT SOURCE SENSOR Please note that these illustrations are meant to show system p...

Страница 22: ...ter heater immediately Follow the draining instructions and replace the T P relief valve If the T P relief valve weeps periodically it may be due to thermal expansion Do not plug the T P relief valve...

Страница 23: ...Installation of a Temperature Pressure T P relief valve is required Owner monthly maintenance to include Visually check valves pipes and fittings for leaks Call a qualified service technician to repa...

Страница 24: ...gpm First Hour Rating gal hr STU150 16 1035 23 1516 15 997 STU200 19 1244 27 1774 18 1125 STU257 19 1365 27 1965 18 1250 STU350 19 1550 27 2223 18 1395 STU423 27 1690 36 2451 26 1600 STU504 28 1816 3...

Страница 25: ...5 507 555 507 555 507 555 507 555 507 555 507 555 507 555 18 1080 537 411 537 411 537 411 537 411 537 411 537 411 537 411 537 411 537 411 19 1140 567 267 567 267 567 267 567 267 567 267 567 267 567 26...

Страница 26: ...8 528 548 528 548 528 548 528 548 528 548 528 548 528 548 528 548 528 14 840 590 722 590 722 590 722 590 722 590 722 590 722 590 722 590 722 590 722 15 900 632 917 632 917 632 917 632 917 632 917 632...

Страница 27: ...328 418 328 418 12 720 358 274 358 274 358 274 358 274 358 274 358 274 358 274 358 274 358 274 13 780 388 130 388 130 388 130 388 130 388 130 388 130 388 130 388 130 388 130 14 840 417 986 417 986 41...

Страница 28: ...Revision Notes Revision A ECO C09107 initial release STU I O Rev A 10 11 Printed in U S A...

Отзывы: