Pre-installation

1.  The installation must conform to the instructions in this 
 

manual and all applicable local, state, provincial, and 

  national codes, laws, regulations, and ordinances. 
 

Installations in Canada must conform to B149.2 Installation 

 Code.

2.  Ensure that the domestic water supply to the stainless 
 

steel coil has physical and chemical characteristics that fall 

 

within the limits shown in Table 2A. Where questions exist 

 

as to the composition of the water on the job site, a qualified 

 

water treatment expert should be consulted.

Water with characteristics outside the limits 
shown in Table 2A may severely shorten 
the life of the domestic water coil due to 
corrosion. Damage in such cases is not 
covered under warranty.

3.  Read and understand all installation requirements in 
 this 

manual.

Table 2A

Water Chemistry Requirements

Domestic potable water must have characteristics falling 
within the following limits:

Characteristic

Min.

Max.

pH

6.5

9.5

Chloride (PPM)

--

200

 

CAUTION

Locating the Tank

1.  Choose a location for the Strato-Therm+ centralized to 
           the piping system. You must also locate the Strato-Therm+ 
 

where it will not be exposed to freezing temperatures.  

 

Additionally, you will need to place the appliance so that 

 

the controls, drain, and inlet/outlets are easily accessible. 

 

This appliance must not be installed outdoors, as it is 

 

certified as an indoor appliance, and must also be kept 

 

vertical on a level surface.

2.  Table 1C on page 5 shows the weight of all the tanks filled 
 

with water.  Ensure that the location chosen for the tank 

 

is capable of supporting the weight.

This appliance must be placed where 
leakage from the relief valve, leakage from 
the related piping, or leakage from the 
tank or connections, will not result in 
damage to the surrounding areas, or to 
the lower floors of the building. A water 
heater should always be located in an area 
with a floor drain or installed in a drain 
pan suitable for water heaters.  Lochinvar 
shall not be held liable for any such water 
damage.

 

CAUTION

Failure to properly support the tank could 
result in property damage or personal 
injury.

 WARNING

Recommended Clearances

The installation location must provide adequate clearances 
for servicing and proper operation of the appliance. 

 

A 12-inch vertical clearance is recommended from the top of 
the appliance. A zero clearance is allowed for the sides of the 
appliance. However, boiler and servicing clearances must be 
figured when locating the appliance.

3.  The tank may be located some distance from the heat  
 

source provided that the pump is designed to to provide 

 

enough flow for both units to perform properly. The 

 

further the distance from the tank to the heat source, the 

 

longer the response time will be to provide sufficient heat 

 

to the tank. Insulate piping between the heat source and 

 the 

tank.

       

Installation & Operation Manual

Содержание Strato-Therm+ STU150

Страница 1: ...sed by a qualified heating installer service technician Read all instructions before installing Perform steps in the order given Failure to comply could result in severe personal injury death or subst...

Страница 2: ...ed to personal injury or property damage HAZARD DEFINITIONS 2 PLEASE READ BEFORE PROCEEDING 3 1 GENERAL INFORMATION Operating Restrictions 4 Tank Shipment 4 Components 4 6 Spherical Heat Exchanger 7 2...

Страница 3: ...gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING NOTICE WARNING WARNING 3 The following chart details...

Страница 4: ...ry if your specific application is not covered in this manual The tank is not intended for use in gravity water heating applications Table 1A Strato Therm Tank Component Materials Component Material T...

Страница 5: ...300 STU257 30 34 1 2 98 83 225 14 5 2875 STU350 36 40 1 2 98 83 325 14 5 3775 STU423 36 40 1 2 115 97 400 16 0 4650 STU504 42 46 1 2 121 103 475 17 0 5475 STU650 48 52 1 2 131 111 625 20 0 7050 STU752...

Страница 6: ...ger Outlet Blue Label Table 1D Tapping Measurements Model A in B in C in D in E in F in G in H in I in O in P in STU150 2 1 4 12 1 4 21 1 4 28 3 4 33 50 3 4 55 1 4 71 76 3 4 3 1 2 3 1 2 STU200 3 1 2 1...

Страница 7: ...l heat exchanger w tank Table 1E Tank with Spherical Measurements Model Spherical Model A in B in STU150 SHX40000 44 1 2 28 STU200 SHX40000 48 1 4 32 STU257 SHX40001 50 1 4 34 STU350 SHX40001 56 1 4 4...

Страница 8: ...led outdoors as it is certified as an indoor appliance and must also be kept vertical on a level surface 2 Table 1C on page 5 shows the weight of all the tanks filled with water Ensure that the locati...

Страница 9: ...sioning must be carried out by a licensed contractor Take appropriate safety measures when carrying out any installation work on the roof and observe all relevant accident prevention regulations It is...

Страница 10: ...URE GAUGE TYPICAL SOLAR PUMP STATION CONTROLLER PRESSURE RELIEF VALVE FILL AND FLUSH VALVE EXPANSION TANK TEMPERATURE GAUGE SPHERICAL HEAT EXCHANGER SOLAR SENSOR IMG00040 Installation Operation Manual...

Страница 11: ...d to allow water to flow in only one direction preventing back flow g Drain required Used to drain the tank for inspection or servicing h Mixing valve required Used to mix hot water with cold water to...

Страница 12: ...ainless steel coil As part of a continuous slow moving loop warm water is circulated directly back into the coil via the lance maintaining tank stratification Reference FIG 4 5 on page 18 for typical...

Страница 13: ...building recirculation system is installed the return water is brought back to the storage tank so as not to disturb the stratification of the Strato Therm Anti scald mixing valves Anti scald valves u...

Страница 14: ...2 8 3 10 7 13 3 14 7 STU200 STU257 STU350 0 1 0 7 1 8 3 2 5 0 7 1 9 5 12 2 15 1 16 7 STU423 0 1 0 8 2 0 3 6 5 6 7 9 10 6 13 6 16 9 18 7 STU504 0 1 0 8 2 1 3 7 5 8 8 2 11 0 14 2 17 7 19 5 STU650 STU75...

Страница 15: ...elief valve must be certified by a nationally recognized testing laboratory that maintains periodic inspection of listed equipment or materials The equipment and materials must meet the requirements f...

Страница 16: ...tly connected to a drain Refer to local codes subject to freezing WARNING Do not install any valve between the relief valve and its connection or on the relief valve discharge piping Improper placemen...

Страница 17: ...cal codes NOTICE IMG00042 SHUTOFF VALVE DOMESTIC HOT WATER CHECK VALVE DOMESTIC COLD WATER RECIRCULATION LINE MIXING VALVE DRAIN CIRCULATION PUMP TEMPERATURE GAUGE SHOCK ARRESTOR BACKUP HEAT SOURCE LO...

Страница 18: ...ired by local codes NOTICE Figure 4 6 Recirculation Piping Flow Over 2 gal min RECIRCULATION LINE CIRCULATION PUMP SHOCK ARRESTOR SHUTOFF VALVE MIXING VALVE TEMPERATURE GAUGE RECIRCULATION LANCE DOMES...

Страница 19: ...ese illustrations are meant to show system piping concept only the installer is responsible for all equipment and detailing required by local codes NOTICE Figure 4 7 Multiple Tank Domestic Piping BUIL...

Страница 20: ...r flow are more balanced throughout each tank To ensure even charging and discharging of each tank it is recommended that only tanks of the same size are placed in the same manifold It is recommended...

Страница 21: ...CHECK VALVE Y STRAINER TYPICAL EXPANSION TANK FILL VALVE PRESSURE RELIEF VALVE AIR SEPARATOR TEMPERATURE GAUGE BACKUP HEAT SOURCE SENSOR Please note that these illustrations are meant to show system p...

Страница 22: ...ter heater immediately Follow the draining instructions and replace the T P relief valve If the T P relief valve weeps periodically it may be due to thermal expansion Do not plug the T P relief valve...

Страница 23: ...Installation of a Temperature Pressure T P relief valve is required Owner monthly maintenance to include Visually check valves pipes and fittings for leaks Call a qualified service technician to repa...

Страница 24: ...gpm First Hour Rating gal hr STU150 16 1035 23 1516 15 997 STU200 19 1244 27 1774 18 1125 STU257 19 1365 27 1965 18 1250 STU350 19 1550 27 2223 18 1395 STU423 27 1690 36 2451 26 1600 STU504 28 1816 3...

Страница 25: ...5 507 555 507 555 507 555 507 555 507 555 507 555 507 555 18 1080 537 411 537 411 537 411 537 411 537 411 537 411 537 411 537 411 537 411 19 1140 567 267 567 267 567 267 567 267 567 267 567 267 567 26...

Страница 26: ...8 528 548 528 548 528 548 528 548 528 548 528 548 528 548 528 548 528 14 840 590 722 590 722 590 722 590 722 590 722 590 722 590 722 590 722 590 722 15 900 632 917 632 917 632 917 632 917 632 917 632...

Страница 27: ...328 418 328 418 12 720 358 274 358 274 358 274 358 274 358 274 358 274 358 274 358 274 358 274 13 780 388 130 388 130 388 130 388 130 388 130 388 130 388 130 388 130 388 130 14 840 417 986 417 986 41...

Страница 28: ...Revision Notes Revision A ECO C09107 initial release STU I O Rev A 10 11 Printed in U S A...

Отзывы: