This feature has been disabled by the manufacturer. To
enable this feature change the
Service Notification in Months
parameter to the desired time range.
Service Notification Running Time
When the water heater control determines that a scheduled
service is due based on the hours of actual operation, the water
heater display will turn yellow and a new status screen will
appear informing the installer that maintenance is required.
This parameter is adjustable by the installer by accessing the
Service Notification Running Time
parameter. The time range
for this parameter is 0 hours to 17,500 hours. The default time
is 8,760 hours.
Service Notification Cycles
When the water heater control determines that a scheduled
service is due based on the number of water heater cycles, the
water heater display will alternate the standard water heater
display text with the message SERVICE DUE every 5 seconds.
This parameter is adjustable by the installer by accessing
the
Service Notification Cycles
parameter. The range for this
parameter is 0 cycles to 100,000 cycles. The default is 50,000
cycles.
Reset Maintenance Reminder
Once service has been completed, the service notification
counter should be reset. This parameter can be reset by
the installer by accessing the
Reset Maintenance Reminder
parameter. Once accessed, press the RESET key to reset the
service notification counter.
Installer Name and Phone Number
When a Maintenance Reminder timer or counter has expired,
a Maintenance Reminder screen will appear on the display.
By programming the installer’s name and phone number, this
information will appear on the Maintenance Reminder Screen
at that time. This can be programmed by accessing the
Service
Name and Phone Number
parameter. When selected, another
menu will appear with PHONE and NAME.
1. Rotate the NAVIGATION dial to point to the
name/phone number to program and press the
NAVIGATION dial. The screen will now display the
selected item (either PHONE or NAME).
2. Press the NAVIGATION dial again. A cursor will
appear at the bottom of the screen. By rotating the
NAVIGATION dial, various numbers and characters
will appear. When the desired number/character is
found, press the NAVIGATION dial. The cursor will
move to the next position.
3. Repeat this procedure until the entire message is
entered. If you make a mistake and wish to back up
one character, rotate the NAVIGATION dial until
the back arrow (
) character is displayed and press the
NAVIGATION
dial.
4. When finished, press the RIGHT SELECT [SAVE] key
to return to the previous menu.
Please note that the brackets ([]) denote
screen status.
NOTICE
Rate at Maximum Volts
When programmed for BMS control through the 0 -
10V BMS input or through ModBus and the BMS Type
is programmed as POWER, the modulation percentage
represented by the
Volts at Maximum
parameter is set by
the
Rate at Maximum Volts
parameter. The minimum value
is the
Rate at Minimum Volts
setting and the maximum is
100%. The default value is 100%.
Set Point at Minimum Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus and the BMS Type is
programmed as SETPOINT, the set point represented by
the
Volts at Minimum
parameter is set by the
Set Point at
Maximum Volts
parameter. The minimum value is 32°F
(0°C) and the maximum is the
Set Point at Maximum Volts
setting. The default value is 70°F (21°C).
Set Point at Maximum Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus and the BMS Type is
programmed as SETPOINT, the set point represented by
the
Volts at Maximum
parameter is set by the
Set Point at
Maximum Volts
parameter. The minimum value is the
Set
Point at Minimum Volts
setting and the maximum is 190°F
(88°C). The default value is 180°F (82°C).
On Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus and the BMS Thermostat
Input is set to INACTIVE, the
On Volts
parameter determines
the 0 - 10V BMS input voltage at which the water heater is
enabled. The minimum value is 0.5V and the maximum is
10.0V. The default value is 2.0V.
Off Differential Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus and the BMS Thermostat
Input is set to INACTIVE, the
Off Differential Volts
parameter
determines how far below the
On Volts
setting the 0 - 10V
BMS input voltage must be in order to disable the water
heater. The minimum value is 0.2V and the maximum is the
On Volts
setting. The default value is 1.0V.
Service Notification
Service Notification in Months
When the water heater control determines that a scheduled
service is due based on days of installation, the water heater
display will alternate the standard water heater display text
with the message SERVICE DUE every 5 seconds. This
parameter is adjustable by the installer by accessing the
Service Notification in Months
parameter. The time range for
this parameter is 0 months to 100 months. The default time
is 12 months.