33
3
Troubleshooting
(continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Sensor Shorted
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
Either the inlet water or outlet water
temperature sensor has been shorted.
• Check the sensors and their associated wiring.
Repair or replace the sensor or wiring if damaged.
• Measure the resistance of the sensors and compare
the resistance to the tables on page 26 of this
manual.
• Replace the sensor if necessary.
Louver Proving
(will require a manual
reset once the condition
has been corrected. Press
the RESET button on the
SMART SYSTEM
display
to reset.)
Louver proving input does not have 24 VAC.
• Check for loose or misplaced jumper.
• Check connection board.
• Check wiring to control board.
Flue Temp High
The stack temperature has exceeded the set
parameters for the water heater.
• Inspect the heat exchanger. Reference page 23 of
this manual for the procedure on how to clean the flue
side of the heat exchanger.
• Inspect the flue sensor and associated wiring.
Measure the resistance of the flue sensor and
compare to Table 3D on page 26 of this manual.
Replace the sensor if necessary.
• Verify that the vent/air intake pipes are properly
installed and that there are no obstructions.
• Replace the main control board.
Scaling has reduced water flow.
• Deliming may be required.
Delta T High
The temperature rise across the heat
exchanger has exceeded the set parameters
for the water heater.
• Verify that the system is full of water and that all air
has been properly purged from the system.
• Verify that the water heater is piped properly into the
heating system. Refer to Section 3 - System Piping
of the Outdoor Armor Water Heater Installation and
Operation Manual for the proper piping methods for
the outdoor water heater.
• Check for 120 VAC to the water heater pump motor on
a call for heat. If voltage is not present, check the
wiring back to the main control board. Replace the
main control board if necessary.
• If 120 VAC is present on a call for heat and the water
heater pump is not operating, replace the pump.
• Verify that the water heater pump is set to the proper
speed or that the pump is the proper size. Reference
Section 3 - System Piping of the Outdoor Armor Water
Heater Installation and Operation Manual for water
heater pump specifications.
Outdoor Armor Water Heater Service Manual
Содержание Knight 151
Страница 39: ...Notes 39 ...