3
Troubleshooting
(continued)
27
Table 3E Troubleshooting Chart - Noisy System
FAULT
CAUSE
CORRECTIVE ACTION
Noisy
Operation
- Supply gas problem. Natural gas pressures
should be between 4 inches w.c. and 14
inches w.c. LP gas pressures should be
between 8 inches w.c. and 14 inches w.c.
• Refer to Section 4 - Gas Connections of the Outdoor Armor
Water Heater Installation and Operation Manual for
detailed information concerning the gas supply.
- Gas/air mixture problem.
• Refer to the Gas Valve Adjustment Procedure on
pages 37-38 of this manual for the proper gas valve
setting.
- Dirty/damaged burner.
• Refer to page 22 in this manual for the burner removal
and inspection procedure. Clean or replace the burner
as
necessary.
- Low water flow through the heat exchanger.
• Refer to Section 3 - System Piping of the Armor
Outdoor Water Heater Installation and Operation Manual
for minimum flow rates.
- Air in the piping system.
• Properly purge all air from the piping system.
- Low system water pressure.
• Verify system pressure is a minimum of 12 PSI.
No Pump
Operation
- Blown fuse.
• Replace fuse F1 on the control board, see page 24 of
this
manual.
- Faulty pump.
• Replace pump.
- Faulty pump relay.
• Replace pump relay.
- Internal fault on control board.
• Replace main control board.
Relief Valve
Opening
-
System pressure exceeds relief valve
setting.
• Lower the system pressure below the 150 PSI rating of
the supplied relief valve.
Outdoor Armor Water Heater Service Manual