Lochinvar Knight 151 Скачать руководство пользователя страница 16

16

1  

Service 

Control modes

BMS Thermostat Input

When controlling the water heater through the 0 - 10V 
BMS input or through ModBus, the water heater can 
be enabled one of two ways.  With the 

BMS Thermostat 

Input parameter

 set to ACTIVE, the water heater will be 

enabled by closing the tank thermostat input.  When set 
to INACTIVE, the water heater will be enabled by the 
voltage level on the 0 - 10V input (in the case of 0 - 10V 
BMS control), or the 0 - 10V input value received through 
ModBus.  The default value is INACTIVE.

BMS 

The set point or modulation of the water heater may be 
controlled through the 0 - 10V BMS input or through 
ModBus.  When the 

BMS parameter

 is set to INACTIVE, 

the 0 - 10V input will be ignored.  When set to ACTIVE, 
the set point or modulation will be controlled by the voltage 
on the 0 - 10V input (in the case of 0 - 10V BMS control), 
or the 0 - 10V input value received through ModBus.  The 
default value is INACTIVE.

ModBus

When BMS is set to ACTIVE (see BMS) and the water 
heater is being controlled through ModBus, set 

ModBus

 

parameter to ACTIVE.  Otherwise, set the 

ModBus

 

parameter to INACTIVE.  Note that the water heater can 
still be monitored by ModBus with this parameter set to 
INACTIVE.  The default value is INACTIVE.

ModBus T/O 

The ModBus T/O is the amount of time the unit controls 
will wait to receive a communication string from the 
BMS controller before reverting back to its own internal 
parameters. This parameter is adjustable by the installer 
by accessing the 

ModBus T/O

 parameter

.  

The adjustment 

range of this parameter is 5 seconds to 2 minutes. 

 

The 

default value is 10 seconds.

Cascade Address

The water heater designated as the Leader needs to be 
programmed with address 0.  All the Member water heaters 
require addresses from 1 to 7, and the addresses must be 
different for each Member.  The addresses can be in any 
order, regardless of the order in which the units are wired 
together.  This parameter is adjustable by the installer by 
accessing the 

Cascade Address

 parameter.  The tank sensor 

must be connected to the Leader water heater.  The default 
address is 1.

Cascade Type

There are two (2) options for the way a Cascade divides the 
load between its heaters.  The first is Lead/Lag, designated 
as L/L in the menu.  This method is used when it is desired 
to have the least amount of total flow through the water 
heaters.  This method will modulate the last two (2) water 
heaters.  This provides for smooth transitions when a water 
heater turns on or off.  When the last water heater reaches 
100% and the calculated load is still increasing, it will start 
the next water heater at 20% and reduce the previous 
water heater to 80%, thus eliminating the sudden jump in 
total output of the Cascade.  When the calculated load is 
decreasing and the last water heater gets down to 20% fire, 
it will hold it there and start lowering the firing rate on 
the next-to-last water heater.  When the next-to-last water 
heater reaches 20%, it will turn the last water heater off and 
raise the rate of the next-to-last water heater to 40%, thus 
eliminating the sudden drop in total output of the Cascade.

The other Cascade divider method is Efficiency 
Optimization, designated as EFF in the menu.  This 
method is used, as the name implies, when it is desired to 
have the most efficient system.  When the first water heater 
reaches a certain rate (default = 90%), it lowers its rate to 
45% and turns on the next water heater at 45%.  The two 
(2) water heaters then modulate at the same rate.    

As the calculated load increases further and both water 
heaters ramp up to 90%, it lowers the rate of the first two 
(2) water heaters to 60% and brings the next water heater 
on at 60%.

   

The three (3) water heaters then modulate 

together.   As the calculated load decreases, the water 
heaters will reach a lower threshold (default = 30%), at 
which time the last water heater (the third in our example) 
will turn off and the Cascade will increase the rates of the 
remaining water heaters to provide the equivalent total 
output as before ((3 x 30%) / 2 = 45% in our example).

Efficiency optimization is automatically selected when 
heaters of different sizes are programmed into the Leader 
water heataer (see 

Boiler Size

 on page 17).

  

Outdoor Armor Water Heater Service Manual

Содержание Knight 151

Страница 1: ...cian Read all instructions including this manual and the Outdoor Armor Water Heater Installation and Operation Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial property damage WARNING Save this manual for future reference OAW SER Rev C ...

Страница 2: ...nce that are important but not related to personal injury or property damage CONTENTS 2 Hazard Definitions 2 PLEASE READ BEFORE PROCEEDING 3 Handling Ceramic Fiber Materials 3 When servicing water heater 3 Water heater operation 3 WHAT IS IN THIS MANUAL 4 1 SERVICE The Outdoor Armor Water Heater Display 5 Control Inputs 6 Control Outputs 7 General Operation 8 Sequence of Operation 9 Display Panel ...

Страница 3: ... or replacing the ceramic materials it is advisable that the installer follow these safety guidelines Avoid breathing dust and contact with skin and eyes Use NIOSH certified dust respirator N95 This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written Other types of respirators may be needed depending on the job site conditions Current NIOSH r...

Страница 4: ...eneral Data Logging Functions DHW Settings Anti Cycling Control Modes Circulation Pumps BMS Service Notification Maintenance Service and maintenance schedules Address reported problems Inspect water heater area and water heater interior Clean condensate trap Check all piping for leaks Check air openings Flue vent system and air piping Check water system Check water heater relief valve Inspect igni...

Страница 5: ...ormation on the bottom of the display shows the functions of the two SELECT keys on either corner and the NAVIGATION dial in the center MENU Left SELECT Key SETPOINTS NAVIGATION Dial Pressing Down SHDN Right SELECT Key Outdoor Armor Water Heater Service Manual ...

Страница 6: ...EQUENCER BUILDING MANAGEMENT SYSTEM LOW VOLTAGE CONNECTION BOARD INLET TEMPERATURE SENSOR OUTLET TEMPERATURE SENSOR FLUE GAS SENSOR LOUVER PROVING SWITCH FLAME SENSOR LOW WATER CUTOFF BLOCKED DRAIN SWITCH DISPLAY PANEL PC INTERFACE SMART SYSTEM CONTROL BOARD AIR PRESSURE SWITCH O TEMP HEAT EXCHANGER SWITCH DOOR TEMPERATURE SWITCH ...

Страница 7: ...OL BOARD ALARM BELL RUN TIME CONTACTS SEQUENCER BUILDING MANAGEMENT SYSTEM WATER HEATER PUMP IGNITOR BLOWER GAS VALVE DISPLAY PANEL PC INTERFACE BUILDING RECIRCULATION PUMP Control outputs 1 Service continued Outdoor Armor Water Heater Service Manual ...

Страница 8: ...n adjust tank target temperatures by pressing the NAVIGATION dial when SETPOINTS is flashing at the bottom of the display The date and time and the temperature units can also be changed Installer Most parameters are available only to the installer accessible by entering the installer password 5309 Saving parameters reference the Parameter Table Table 1D on pages 12 and 13 of this manual Please not...

Страница 9: ...gain On the 501 and larger models the control will lock out if this second attempt also fails On the 400 and smaller models the control will perform a total of 4 attempts before locking out 6 If flame is detected it holds the firing rate steady for a few seconds to let the flame stabilize then it begins to modulate the firing rate based on a set point or some other command such as a 0 10V BMS sign...

Страница 10: ... 5 seconds Rotate the NAVIGATION dial clockwise until 5 is displayed first digit on the left Press the NAVIGATION dial to select the next digit Rotate the NAVIGATION dial clockwise until 3 is shown in the display Press the NAVIGATION dial 2 times to move to the last digit Rotate the NAVIGATION dial counterclockwise until 9 is displayed SAVE Press the RIGHT SELECT soft key SAVE Rotate the NAVIGATIO...

Страница 11: ...tering the installer access code Rotate the NAVIGATION dial counterclockwise until the arrow is next to DHW SETTINGS Press the NAVIGATION dial one time Rotate the NAVIGATION dial counterclockwise until the arrow is next to TANK MIN SETPT Press the NAVIGATION dial one time Rotate the NAVIGATION dial to the desired temperature SAVE Press the RIGHT SELECT soft key SAVE one time EXIT Press the LEFT SE...

Страница 12: ...ight Setback On Times 14 No No Yes Yes DHW Night Setback Off Times 14 No No Yes Yes Display Timeout 15 No No Yes Yes Reset Log Errors 15 No No Yes Yes Service Mode Delay 15 No No Yes Yes Tank Set Point 15 Yes Yes Yes Yes Tank Set Point Offset 15 Yes Yes Yes Yes Tank Set Point Differential 15 No No Yes Yes Tank Minimum Set Point 15 No No Yes Yes Tank Maximum Set Point 15 No No Yes Yes Anti Cycling ...

Страница 13: ...Min 17 No No Yes Yes Volts at Max 17 No No Yes Yes Rate at Min Volts 17 No No Yes Yes Rate at Max Volts 18 No No Yes Yes Set Point at Min Volts 18 No No Yes Yes Set Point at Max Volts 18 No No Yes Yes On Volts 18 No No Yes Yes Off Differential Volts 18 No No Yes Yes Service Notification Months 18 No No Yes Yes Service Notification Running Time 18 No No Yes Yes Service Notification Cycles 18 No No ...

Страница 14: ... 7 day week These settings are referred to as triggers Multiple start or stop triggers may be set within a single day if desired When a start trigger and a stop trigger are set to the same time the stop trigger has priority The installer may adjust the DHW start triggers in the DHW Night Setback On Times parameter This screen shows the start trigger number the day of the week and the time of day 1...

Страница 15: ...illuminated The range is 10 seconds to 10 minutes The default is 3 minutes Data Logging Reset log errors The reset log errors function clears the last 10 errors log Functions Service Mode Delay By pressing the pin button on the front of the display for five 5 seconds the control will be placed in Service Mode This will override all other heat demands The Service Mode allows the installer to set th...

Страница 16: ...nk sensor must be connected to the Leader water heater The default address is 1 Cascade Type There are two 2 options for the way a Cascade divides the load between its heaters The first is Lead Lag designated as L L in the menu This method is used when it is desired to have the least amount of total flow through the water heaters This method will modulate the last two 2 water heaters This provides...

Страница 17: ...s shown Press the RIGHT SELECT SAVE key 3 Rotate the NAVIGATION dial to select the address of the next boiler in the Cascade Repeat Step 2 4 Once the size of the last boiler in the Cascade has been entered and saved press the LEFT SELECT EXIT key to return to the Control Modes menu 5 If no other parameters are to be adjusted press the RIGHT SELECT HOME key to save the new settings and return to th...

Страница 18: ...VIGATION dial until the back arrow character is displayed and press the NAVIGATION dial 4 When finished press the RIGHT SELECT SAVE key to return to the previous menu Please note that the brackets denote screen status NOTICE Rate at Maximum Volts When programmed for BMS control through the 0 10V BMS input or through ModBus and the BMS Type is programmed as POWER the modulation percentage represent...

Страница 19: ...ication per Section 7 in the Armor Outdoor Installation and Operation Manual Flame inspection stable uniform Flame signal at least 10 microamps at high fire Clean the heat exchanger if flue temperature is more than 54 F above return water temperature Check Delta T Temperature Rise If combustion or performance indicate need Clean heat exchanger Remove and clean burner using compressed air only Clea...

Страница 20: ...ration Manual If any of these are present in the water heater intake air vicinity they must be removed Inspect water heater interior 1 Remove the front access cover and inspect the interior of the water heater 2 Vacuum any sediment from inside the water heater and components Remove any obstructions Clean condensate trap 1 Inspect the condensate drain line condensate PVC fittings and condensate tra...

Страница 21: ... before proceeding further Safety relief valves should be re inspected AT LEAST ONCE EVERY THREE YEARS by a licensed plumbing contractor or authorized inspection agency to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally Certain naturally occurring conditions may corrode the ...

Страница 22: ...ration Manual 2 Verify cold fill pressure is correct and that operating pressure does not go too high Check burner flame 1 Inspect flame through observation window 2 If the flame is unsatisfactory at either high fire or low fire turn off water heater and allow water heater to cool down Remove the burner and clean it thoroughly using a vacuum cleaner or compressed air Do not use compressed air to c...

Страница 23: ...ly use the kit provided brush or an equivalent replacement nylon brush CAUTION 5 Remove the condensate hose from the heat exchanger end Connect a field supplied 3 4 diameter hose to a drain pan Using field supplied means cover the refractory in the back of the combustion chamber of the heat exchanger 6 Use a vacuum cleaner to remove any accumulation on the water heater heating surfaces Do not use ...

Страница 24: ...al 8 inches w c LP with gas flowing verify during water heater startup Check control module fuses ALWAYS check control module fuses before replacing control module or any major components blower etc If one of these fuses is blown it can prevent the control module or other components from operating 1 Turn OFF power to the water heater at the external line switch 2 Remove top access cover 3 Remove t...

Страница 25: ...eplace fuse F3 on the main control board see page 24 of this manual No Burner Operation Main control board temperature set point satisfied Review temperature setting Remote thermostat satisfied Review remote thermostat setting Unit locked out on fault Consult display for specific fault Refer to fault descriptions on pages 28 35 of this manual for corrective actions Unit Does Not Modulate Above 50 ...

Страница 26: ...sor and S3a S3b flue sensor Please reference the wiring diagram in the Outdoor Armor Water Heater Installation and Operation Manual for correct terminal location S1a Wire Color R BK and Y S1b Wire Color G and Y Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance 50 19 553 158 2 004 50 40 030 158 3 478 68 12 690 176 1 464 68 25 030 176 2 492 86 8 406 194 1 08...

Страница 27: ...s manual for the burner removal and inspection procedure Clean or replace the burner as necessary Low water flow through the heat exchanger Refer to Section 3 System Piping of the Armor Outdoor Water Heater Installation and Operation Manual for minimum flow rates Air in the piping system Properly purge all air from the piping system Low system water pressure Verify system pressure is a minimum of ...

Страница 28: ... HEX Temp Sw Open will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset Either the air pressure switch contacts are open the O temp heat exchanger switch has opened or the burner door temperature switch has opened APS Check the wiring connections to switch Wires should be connected to the common and normally closed terminals A...

Страница 29: ...res should be between 8 14 inches w c Refer to Section 4 Gas Connections of the Armor Outdoor Water Heater Installation and Operation Manual for detailed information concerning the gas supply Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged Verify that the vent air intake pipes are correctly installed and that there are no obstructions Check for 24 V...

Страница 30: ...nual for detailed information concerning the gas supply Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged Verify that the vent air intake pipes are installed correctly and there are no obstructions Check for 24 VAC to the gas valve at the 2 pin connection on the side of the main control board during the ignition attempt If no voltage is present replac...

Страница 31: ...mp If the system pump is a variable speed pump ensure that the system flow is not less than the water heater flow If operating on something other than an outlet sensor check temperature setting of the main control board If the manual reset high limit has tripped check setting of the device Check resistance of water sensors and compare to Table B on page 26 of this manual Replace sensor if necessar...

Страница 32: ...h will require a manual reset once the condition has been corrected Press the RESET button on the SMART SYSTEM display to reset The actual fan RPM is 30 higher than what is being called for Vent air intake lengths exceed the maximum allowed lengths Check for obstruction or blockage in the vent air intake pipes or at terminations Check the wiring connections at the fan and at the main control board...

Страница 33: ...nsor and associated wiring Measure the resistance of the flue sensor and compare to Table 3D on page 26 of this manual Replace the sensor if necessary Verify that the vent air intake pipes are properly installed and that there are no obstructions Replace the main control board Scaling has reduced water flow Deliming may be required Delta T High The temperature rise across the heat exchanger has ex...

Страница 34: ...int of the external control Check the wiring between the external control and the unit Replace the control Service Blk While the unit is in Service Mode the outlet temperature has exceeded 185 F Establish a heating load to remove the heat from the water heater loop Verify that the system is full of water and that all air has been properly purged from the system Verify that the water heater is pipe...

Страница 35: ...nsformer Watch Dog Error The main control board has detected an internal fault Replace the main control board Write EEProm The main control board has detected an internal fault Replace the main control board CRC Parameters The main control board has detected an internal fault Replace the main control board No Error Stored The main control board has detected an internal fault Replace the main contr...

Страница 36: ...mbustion Levels POSSIBLE CAUSE CORRECTIVE ACTION Vent Air Intake Length or Obstruction Check for obstructions at the vent air intake terminals Gas Supply Pressure Refer to Section 4 Gas Connections of the Outdoor Armor Water Heater Installation and Operation Manual for the proper gas supply for the outdoor water heater Dirty Damaged Burner Refer to page 22 of this manual for burner removal and cle...

Страница 37: ... the combustion is still not within the specified range revisit the possible causes in Table 3H on page 36 or replace the gas valve Figure 3 2 Gas Valve Adjustment Models 151 286 Model 400 Locate the throttle adjustment screw on the top of the gas valve see FIG 3 3 Using a screwdriver turn the screw 1 8 turn counterclockwise to increase CO2 levels or 1 8 turn clockwise to decrease CO2 levels After...

Страница 38: ...ADJUSTMENT SCREW Figure 3 4 Gas Valve Adjustment Model 501 3 Troubleshooting Models 601 801 Locate the throttle adjustment screw on top of the gas valve see FIG 3 5 Using an Allen wrench turn the screw a 1 4 turn counterclockwise to increase CO2 levels or a 1 4 turn clockwise to decrease CO2 levels After one adjustment on the valve follow the Combustion Analysis Procedure on page 36 of this manual...

Страница 39: ...Notes 39 ...

Страница 40: ...s Revision A ECO C10942 initial release Revision B ECO C14411 reflects condensate trap changes R6594 on page 20 Revision C ECO C15251 reflects the addition of the burner door temperature switch R6322 on pages 6 and 28 OAW SER Rev C 06 14 ...

Отзывы: