Outdoor Crest Supplemental Manual

4

The Outdoor Crest - How it works...

 

1. 

Front access panels

 

Provides access to the controls compartment.

2. 

Top access panel

 

Provides access to the burner compartment.

3. 

Optional outdoor air inlet hood assembly

(shipped 

 

separately with outdoor installation kits)

 

The hood assembly is required when installing outdoors for 

 

combustion air to prevent rain and debris from entering the air 

 inlet. 

4.  Boiler drain connection

 

Location from which the heat exchanger can be drained.

5. Condensate 

drain 

connection

 

The condensate drain connection provides a connection 

 

point to install a condensate drain line using flexible hose 

 provided.

6. Condensate 

trap 

box 

(shipped separately with outdoor 

 installation 

kits) 

 

The condensate trap box comes assembled inside the outdoor 

 

installation kit.  The condensate trap box is required for 

 

outdoor installations to protect/house the condensate trap. 

7.  Control module (on control panel assembly)

 

The control module responds to internal and external signals 

 

and controls the blower, gas valves, and pump(s), depending on 

 

the application, to meet the heating demand.

8. Electronic 

display

 

Digital controls with SMART TOUCH  screen technology, full 

 

color display, and an 8" user interface screen.

9. Gas 

connection 

pipe

 

The gas connection pipe is a threaded black iron pipe 

 

connection (see Gas Connections Section for specific model 

 

pipe size requirements).  This pipe should be connected to the 

 

incoming gas supply to deliver gas to the boiler.

10.  Gas shutoff valve (inside unit)

 

The manual gas shutoff valve is used to isolate the boiler gas 

 

train from the gas supply.

11. Gas valves

 

The gas valves sense the negative pressure created by the 

 

blower, allowing gas to flow only if the gas valves are powered 

 

and combustion air is flowing.

12. Condensate trap

 

The condensate trap is sized for a 1" PVC outlet connection 

        pipe.  

13.  Line voltage junction box

 

The line voltage junction box contains the connection points 

        for the line voltage power to the boiler (and pumps if used).

14.  Line voltage wiring connections

 

Conduit connection points for the high voltage junction box.

15.  Low gas pressure switch 

 

Monitors gas supply pressure to the boiler and shuts the boiler 

 

down in the event a low gas pressure condition 

        occurs. 

16.  High gas pressure switch

Monitors gas supply pressure to the boiler and shuts the boiler 

 

down in the event a high gas pressure condition 

        occurs. 

17.  Low voltage connection board(s)

 

Connection boards used to connect external low voltage 

        devices.

18.  Low voltage wiring connections (knockouts)

Conduit connection points for the low voltage connection 

        boards.

19. Power switch

The On/Off power switch provides the ability to turn line voltage 

 

power to the boiler on and off.

20. Relief valve

 

The safety relief valve protects the heat exchanger from an over 

 

pressure condition.  The boiler comes with a 50 PSI relief valve as 

 

standard equipment.  Optional settings are available.

21. Reset switch

 

Reset switch for the low water cutoff.  Hold the switch for 10 

 

seconds to reset.

22. Test switch

 

The test switch permits manual triggering of the LWCO 

 

safety circuit to test the contacts and evaluate the integrity of the 

 

circuit. Hold the switch for 10 seconds to test.

23. Firetube heat exchanger

 

High grade stainless steel WAVE

TM

 firetube design that extracts 

 

heat from flue gases and transfers it directly into boiler water.

24. Temperature and pressure gauge 

 

Monitors the outlet temperature of the boiler as well as the system 

 water 

pressure.

25. Venturi (not shown)

 

The venturi controls air and gas flow into the burner.

26. Water inlet

An ANSI flange connects the return water from the system to the 

 heat 

exchanger.

27. Water outlet

An ANSI flange connects the hot water supply from the boiler to 

 the 

system.

28.  Flame inspection window (not shown)

 

Two large high temperature quartz observation windows 

 

provide views of the burner surface during firing.

29. Air metering valve 

The air metering valve is used to control the amount of air used 

        when firing.

30.  Air metering valve air pressure switch 

 

The air metering valve air pressure switch is used to ensure the air 

 

metering valve is open when firing gas valve 2.

31. Vent support 

(shipped in the ship loose parts box with each 

 unit)

 

The vent support is required for outdoor installations to support 

 

the vent piping.

32. Air pressure switch 

 

The air pressure switch detects blocked flue/vent conditions.

Содержание Crest OFL0751

Страница 1: ...Crest Installation and Operation Manual and the Crest Service Manual before installing Perform steps in the order given Failure to comply could result in severe personal injury death or substantial p...

Страница 2: ...EDING 3 THE OUTDOOR CREST HOW IT WORKS 4 5 RATINGS 6 1 DETERMINE BOILER LOCATION Installation Must Comply With 7 Before Locating the Boiler Check 7 Provide Clearances 8 Prevent Combustion Air Contamin...

Страница 3: ...xternal to the appliance Do not use this boiler if any part has been under water The possible damage to a flooded appliance can be extensive and present numerous safety hazards Any appliance that has...

Страница 4: ...ge junction box 15 Low gas pressure switch Monitors gas supply pressure to the boiler and shuts the boiler down in the event a low gas pressure condition occurs 16 High gas pressure switch Monitors ga...

Страница 5: ...Outdoor Crest How it works continued 2000549892 00 2000549892 00 1 8 31 3 2 DIR 2000549892 00 Front View DIR 2000549906 00 31 6 12 4 5 20 24 23 27 26 Rear View DIR 2000549910 00 19 9 10 17 29 22 18 13...

Страница 6: ...ited States Department of Energy 2 Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pic...

Страница 7: ...oper operation and prevent a hazardous condition WARNING WARNING The unit must not be installed in an area that is enclosed by walls or a fence that will block free wind movement around the appliance...

Страница 8: ...onsible for water damage in connection with this appliance or any of its components If flooding is possible elevate the boiler sufficiently to prevent water from reaching the boiler Recommended servic...

Страница 9: ...mbly DIR 2000555428 00 DIR 2000 AIR INLET HOOD ASSEMBLY MAKE CERTAIN THE FACE OF THE WIRE SCREEN FRAME OF THE HOOD IS SET FLUSH WITH THE LEADING EDGE OF THE TOP OF THE UNIT PLACE THE DISPLAY COVER OVE...

Страница 10: ...mm minimum clearance to the air inlet To avoid a blocked air inlet or blocked flue condition keep the air inlet flue outlet and condensate trap clear of leaves debris etc Do not locate unit so that hi...

Страница 11: ...lator 4 Gas regulators should be installed the greater of either 20 inches or 10 pipe diameters from the nearest fitting elbow or valve to the outlet of the regulator 5 It is recommended that the gas...

Страница 12: ...oses of input adjustment WARNING WARNING NOTICE Check boiler rating plate to determine which fuel the boiler is set for Outdoor Crest boilers CAN NOT be field converted Failure to comply could result...

Страница 13: ...mum and maximum gas supply pressures are specified in this section of the manual 9 If gas supply pressure is within normal range and no adjustments are needed proceed on to Step 11 10 If the gas press...

Страница 14: ...r should ignite promptly Flame pattern should be stable Turn system off and allow burner to cool then cycle burner again to ensure proper ignition and flame characteristics Gas valve replacement The g...

Страница 15: ...up flush the entire heating system 2 Clean the entire heating system with an approved pre commissioning cleaner comparable to Sentinel X300 or X400 and Fernox F3 or DS40 in accordance with the manufac...

Страница 16: ...minate all system leaks Continual fresh makeup water will reduce boiler life Minerals can build up in the heat exchanger reducing heat transfer overheating the heat exchanger and causing heat exchange...

Страница 17: ...of water and all system components are correctly set for operation Verify the preparation procedures of Section 3 pages 15 18 have been completed Verify electrical connections are correct and securely...

Страница 18: ...ns On the Service Maintenance Screen place heater into Service Mode by selecting the START button then selecting Set Gas Valve 1 High FIG 3 2 WARNING WARNING Table 3B Flue Products Chart 8 Once the he...

Страница 19: ...to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above on this label 2 Se...

Страница 20: ...NDENT AIR VALVE PRESS SWITCH BLOWER AIR VALVE HIGH LIMIT SWITCH M M DISCONNECT POWER BEFORE SERVICING BOILER PUMP DHW PUMP 5 0 A 3 15 A F2 LARGE GAS LARGE GAS SMALL GAS SMALL GAS USB INTERFACE X11 WIF...

Страница 21: ...TOR CONTACTOR DHW PUMP CONTACTOR HIGH VOLTAGE LOW VOLTAGE 120 VAC 1 5A EACH MAX OR AIR VALVE PRESSURE SWITCH OR BK OR AIR VALVE OR W BL OR R M 1 M 2 3 5 1 2 3 USB INTERFACE X11 R BL E GND LG CON BRD B...

Страница 22: ...5A EACH MAX X11 WIFI DONGLE X4 BOX DEPICTS OPTIONAL ITEMS BOX DEPICTS DUAL SENSOR SINGLE HOUSING HIGH VOLTAGE LOW VOLTAGE 120 VAC Notes 1 All wiring must be installed in accordance with local state p...

Страница 23: ...TURN SENSOR SYSTEM SUPPLY SENSOR 0 10V 0 10V TANK SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD A B CASCADE R R R O R O L B K B R B R Y BL HIGH LIMIT SWITCH R R X6 1 X6 2 X6 3 Y G R R...

Страница 24: ...D 1 5A EACH MAX X11 WIFI DONGLE X4 BOX DEPICTS OPTIONAL ITEMS BOX DEPICTS DUAL SENSOR SINGLE HOUSING HIGH VOLTAGE LOW VOLTAGE 120 VAC Notes 1 All wiring must be installed in accordance with local stat...

Страница 25: ...SENSOR OUTDOOR SENSOR 0 10V 0 10V BMS IN SYSTEM PUMP IN SHIELD A B CASCADE R R R O R O L B K B R B R Y BL HIGH LIMIT SWITCH R R X6 1 X6 2 X6 3 Y G R R P L B R L B R R B W R O W R O P W L B K B K B Y...

Страница 26: ...BOX DEPICTS OPTIONAL ITEMS BOX DEPICTS DUAL SENSOR SINGLE HOUSING HIGH VOLTAGE LOW VOLTAGE 120 VAC Notes 1 All wiring must be installed in accordance with local state provincial and national code req...

Страница 27: ...0 10V BMS IN SYSTEM PUMP IN SHIELD A B CASCADE R R R O R O L B K B R B R Y BL HIGH LIMIT SWITCH R R X6 1 X6 2 X6 3 Y G R R P L B R L B R R B W R O W R O P W L B K B K B Y J3 5 J3 4 J3 6 LWCO BOARD J3...

Страница 28: ...0 CN 500017507 reflects the addition of the 3501 model updates made to the Check Flame and Combustion Section on page 18 and the wiring and ladder diagrams Revision C PCP 3000029182 CN 500018624 refle...

Отзывы: