The combustion air inlet of the outdoor cap
must
be located at least one foot (0.30m)
above grade and above normal snow levels.
The water heater
must
be at least 10 feet
(3.05m) away from any forced air inlet and
at least 3 feet (0.91m) outside any overhang.
Do not install in locations where rain from
building runoff drains will spill onto the
water heater.
Lochinvar
must
furnish an outdoor vent kit
in accordance with CSA international
requirements. Each kit includes the flue
outlet/combustion air inlet, assembly, gasket
and pump cover.
Freeze Protection-
Outdoor Installation
A snow screen should be installed to prevent
snow and ice accumulation around the
appliance or its venting system.
If for any reason the unit is to be shut off:
(a.) Shut off water supply.
(b.) Drain unit completely.
(c.) Drain pump and piping.
If freeze protection is not provided for the
system, a low ambient temperature alarm or
automatic drain system is recommended.
GAS SUPPLY
The gas pressure regulator supplied is for
low pressure service. If upstream pressure
exceeds 6 oz. (10.5" water column), an
intermediate gas pressure regulator, of the
lock up type,
must
be installed.
The gas line should be a separate line
direct from meter, unless the existing
gas line is of sufficient capacity. Verify
pipe size with your gas supplier.
L o c h i n v a r
D E S I G N E R
’
S
G U I D E
C O P P E R
-
F I N
I I
W A T E R
H E A T E R
6 1 5 - 8 8 9 - 8 9 0 0
1 7
(TABLE I) - OUTDOOR VENT KIT PART NUMBERS
MODEL
NUMBER
PART NUMBER
CF401
0DK3052
CF501
0DK3052
CF651
0DK3053
CF751
ODK3053
CF991
ODK3049
CF1261
ODK3050
CF1441
ODK3050
CF1801
ODK3051
CF2071
ODK3051
(TABLE J) – GAS SUPPLY PIPE SIZING
Length of Pipe In Straight Feet
Nominal Iron
Pipe Size, Inches
10
20
30
40
50
60
70
80
90
100
125
150
175
200
369
256
205
174
155
141
128
121
113
106
95
86
79
74
697
477
384
328
292
267
256
246
210
200
179
164
149
138
1,400
974
789
677
595
543
502
472
441
410
369
333
308
287
2,150
1,500
1,210
1,020
923
830
769
707
666
636
564
513
472
441
4,100
2,820
2,260
1,950
1,720
1,560
1,440 1,330
1,250
1,180
1,100
974
871
820
6,460
4,460
3,610
3,100
2,720
2,460
2,310 2,100
2,000
1,900
1,700
1,540
1,400
1,300
11,200
7,900
6,400
5,400
4,870
4,410
4,000 3,800
3,540
3,300
3,000
2,720
2,500
2,340
23,500 16,100 13,100 11,100 10,000
9,000
8,300 7,690
7,380
6,870
6,150
5,640
5,130
4,720
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14” Inches Water Column (0.5 PSIG) or less and a total
system pressure drop of 0.05 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
1
1
/
4
3
/
4
1
1
/
2
1
2
1
/
2
3
1
/
2
3
2
1.